![TENEO LoRaWAN CO2 stoplicht Скачать руководство пользователя страница 13](http://html1.mh-extra.com/html/teneo/lorawan-co2-stoplicht/lorawan-co2-stoplicht_manual_1086438013.webp)
Manual LoRaWAN CO
2
stoplicht
13
©
Copyright
2021
Teneo
Sales
BV.
All rights reserved.
All information in this manual Is subject to change without further notice.
+31 (0)543 535 535
Port 1: CO
2
Measurement:
Byte
Length
Description
0
1 Header
1
1 RFU
2..5
4 CO
2
display
6..7
2 Temperature
display
8..9
2 Humidity
display
These values are not the actual values of the measurements, they must first be converted. For this
calculation see the relevant chapters.
The CO
2
sensor controls the current measurement values.
This message is sent with an adjustable interval (period time).
For example, this message looks like this:
0x0F 00 00 01 53 3B 07 53 11 4D
The meaning of this post is:
Byte 0:0x0F = System voltage: 3.5 V
Byte 1:0x00 = RFU
Byte 2..5:0x00 01 53 3B = 868.43 PPM
Byte 6..7:0x07 53 = 18.75 degrees Celsius
Byte 8..9:0x11 4D = 44.29% RH
Header:
Bit number
Description
3..0
Battery view
The system voltage is calculated as follows:
2+ (Battery display/10)
If the battery display in the message is 0x0C (12), the system voltage calculation becomes:2 + (12/10) =
3.2 V.
Measured CO
2
value:
Byte number
Length
Description
2..5
4 CO
2
display
This byte shows the measured CO
2
value. To convert this value to the actual measured value, this
calculation must be used:
CO
2
in PPM = CO
2
value /100
0x0001533B: This has a decimal value of 86843.
86843/100 = 868.43 PPM
Measured temperature:
Byte number
Length
Description
6..7
2 Temperature
value
The temperature can be negative, to convert it, the MSB must be looked at.
If this MSB is 1 then the temperature is: - (65536 – temperature value
) /
100.
If this MSB is 0 then the temperature is: temperature value
/100.