background image

6

441 01 2610 00

Horizontal

If you purchased a dual--position furnace, it can be installed hori-

zontally in an attic, basement, crawl space, alcove, or suspended

from a ceiling in a basement or utility room in either a right or left

airflow position. (see

Figure 3

)

The minimum clearances to combustibles

MUST

be maintained

between the furnace and adjacent construction, as shown in

Figure 1

.

ONLY

the corner of the cabinet is allowed to contact the

rafters

Figure 3

. All other clearances

MUST

be observed as

shown in

Figure 1.

Typical Horizontal Installation

Figure 3

VENT

GAS SUPPLY

SUPPLY

AIR

RETURN

AIR

25- 23- 18a

If the furnace is to be suspended from the floor joists in a crawl

space or the rafters in an attic, it is necessary to use steel pipe

straps or an angle iron frame to attach the furnace. These straps

should be attached to the furnace with sheet metal screws and to

the rafters or joists with bolts. The preferred method is to use an

angle iron frame bolted to the rafters or joists.
If the furnace is to be installed ground level in a crawl space, con-

sult local codes. A concrete pad 1

²

to 2

²

thick is recommended.

Thirty inches (30

²

) is recommended between the front of the fur-

nace and adjacent construction or other appliances. This should

be maintained for service clearance.
Keep all insulating materials clear from louvered door. Insulating

materials may be combustible.
The horizontal furnaces may be installed directly on combustible

wood flooring or supports, however, it is recommended for further

fire protection cement board or sheet metal is placed between the

furnace and the combustible wood floor and extend 12

²

beyond

the front of the furnace louver door. (This is a recommendation

only, not a requirement).
This furnace

MUST NOT

be installed directly on carpeting, tile or

other combustible material other than wood flooring or supports.

3. Combustion & Ventilation Air

CARBON MONOXIDE POISONING HAZARD.
Failure to provide adequate combustion and

ventilation air can result in death and/or personal

injury.
Use methods described here to provide combus-

tion and ventilation air.

!

Furnaces require ventilation openings to provide sufficient air for

proper combustion and ventilation of flue gases. All duct or open-

ings for supplying combustion and ventilation air must comply with

the gas codes, or in the absence of local codes, the applicable na-

tional codes.

When the installation is complete, check that all appliances have

adequate combustion air and are venting properly. See

Venting

And Combustion Air Check

in “

Gas Vent Installation”

Section in

this manual.

Contaminated Combustion Air

Installations in certain areas or types of structures will increase the

exposure to chemicals or halogens that may harm the furnace.

These instances must use only outside air for combustion.

The following areas or types of structures may contain or have ex-

posure to the substances listed below. The installation must be

evaluated carefully as it may be necessary to provide outside air

for combustion.

·

Commercial buildings.

·

Buildings with indoor pools.

·

Furnaces installed in laundry rooms.

·

Furnaces installed in hobby or craft rooms.

·

Furnaces installed near chemical storage areas.

·

Permanent wave solutions for hair.

·

Chlorinated waxes and cleaners.

·

Chlorine based swimming pool chemicals.

·

Water softening chemicals.

·

De--icing salts or chemicals.

·

Carbon tetrachloride.

·

Halogen type refrigerants.

·

Cleaning solvents (such as perchloroethylene).

·

Printing inks, paint removers, varnishes, etc.

·

Hydrochloric acid.

·

Sulfuric Acid.

·

Solvent cements and glues.

·

Antistatic fabric softeners for clothes dryers.

·

Masonry acid washing materials.

Confined Space Installation

NOTE

: A confined space is defined as an area with less than 50

cubic feet per 1,000 BTUH input rating for all gas appliances

installed in the area.

Air Openings and Connecting Ducts

1. Total input rating for all gas appliances

MUST

be considered

when determining free area of openings.

2. Connect ducts or openings directly to outside.

3. When screens are used to cover openings, the openings

MUST

be no smaller than

1

/

4

²

mesh.

4. The minimum dimension of rectangular air ducts

MUST NOT

be less than 3

²

.

Содержание H8UH5050B12

Страница 1: ...nel can perform basic maintenance functions such as cleaning and replacing air filters All other operations must be performed by trained service personnel When working on heating equipment observe precautions in the literature on tags and on labels attached to or shipped with the unit and other safety precautions that may apply Follow all safety codes In the United States follow all safety codes i...

Страница 2: ...of Supply Air F or C Temperature of Return Air F or C Rise Supply Temp Return Temp F or C Filter Type and Size Fan Time ON Setting Fan Time OFF Setting Manual Gas Shut Off Upstream of Furnace Drip Leg YES NO Drip Leg Upstream of Gas Valve YES NO Blower Speed Checked YES NO All Electrical Connections Tight YES NO Gas Valve OK YES NO Measured Line Pressure When Firing Unit Calculated Firing Rate See...

Страница 3: ...lt to provide many years of safe and dependable service providing it is properly installed and maintained However abuse and or improper use can shorten the life of the unit and create hazards for you the owner A The U S Consumer Product Safety Commission recom mends that users of gas burning appliances install carbon monoxide detectors There can be various sources of carbon monoxide in a building ...

Страница 4: ...e necessary to resize the existing vent line and chimney to prevent oversizing problems for the other remaining appliances s See applicable codes and Venting and Combustion Air Check and Gas Vent Installation section Location and Clearances If furnace is a replacement it is usually best to install the furnace where the old one was Choose the location or evaluate the exist ing location based upon t...

Страница 5: ...RONT 3 Recommended For Service 30 ALL SIDES Of SUPPLY PLENUM 1 SIDES 0 VENT Single Wall Vent 6 Type B 1 Double Wall Vent 1 TOP OF FURNACE 1 Horizontal position Line contact is permissible only between lines formed by intersections of top and two sides of furnace jacket and building joists studs or framing DIMENSIONAL INFORMATION Unit Cabinet Top Bottom Unit Capacity A B F C D H8UH5050B12 H8UH5075B...

Страница 6: ...nd ventilation air can result in death and or personal injury Use methods described here to provide combus tion and ventilation air Furnaces require ventilation openings to provide sufficient air for proper combustion and ventilation of flue gases All duct or open ingsforsupplyingcombustion andventilation airmustcomplywith the gas codes or in the absence of local codes the applicable na tional cod...

Страница 7: ...re 1 square inch of free area per4 000 BTUHfor combined input of all gas appliances in area see Table 1 One permanent opening commencing within 12 of the top of the enclosure shall be permitted where the equipment has clear ances ofatleast1 fromthe sides and back and 6 fromthe frontof the appliance The opening shall directly communicate with the outdoors or shall communicate through a vertical or ...

Страница 8: ...this furnace can result in death personal injury and or property damage Install the vent in compliance with codes of the country having ju risdiction local codes or ordinances and these instructions These fan assisted combustion furnaces have been classified as Category I appliances which means that they MUST operate with a negative vent pressure Category I Safe Venting Requirements NOTE The follo...

Страница 9: ...icates sufficient infiltration air Venting to Existing Masonry Chimney NOTE The tables and notes referred to below are found in the most recent printing of the United States National Fuel Gas Code venting tables Use the United States National Fuel Gas Code or NFGC Tables to size the chimney orvent Dedicatedventing ofone fanassisted furnace into any masonry chimney is restricted The chimney must fi...

Страница 10: ...for installations below 2000 in altitude Table 3 Orifice Sizes below 2000 Gas Type Manifold Pressure Specific Gravity Heating Value BTU per Cubic Ft Orifice Size Drill Natural 3 5 w c 800 40 3 5 w c 0 9kP 0 6 900 41 0 9kPa w c 0 6 1000 42 w c 1100 43 Propane 10 w c 2 5kPa w c 1 53 2500 54 Operation Above 2000 Altitude FIRE EXPLOSION CARBON MONOXIDE POISON ING HAZARD This conversion shall be done b...

Страница 11: ...FERENT SPECIFIC GRAVITY CONSULT THE LATEST EDITION OF THE NATIONAL FUEL GAS CODE ANSI Z223 1 and CAN B149 NOTE The derating of these units at 2 Natural and 4 L P has been tested and approved by AGA High Altitude Air Pressure Switch Altitudes over 4 000 require a different air pressure switch than the one installed at thefactory Check parts list for pressure switch and consult your distributor for ...

Страница 12: ...vide a 1 8 inch plug for test gauge connection immediate ly up stream of gas supply connection to furnace 7 Use two pipe wrenches when making connections to prevent gas valve from turning Typical Gas Piping Figure 8 25 24 35a Union Manual Valve Drip leg pipe cap left side entry 8 Flexible corrugated metal gas connector may NOT be used inside the furnace or be secured or supported by the furnace or...

Страница 13: ...s Fieldwiringconnectionsmustbemadeinsidethefurnaceconnec tion box A suitable strain relief should be used at the point the wires exit the furnace casing Copper conductors shall be used Line voltage wires should be sized for the input amps stated on the rating plate Furnace must be connected to its own separate circuit Thermostat Thermostat location has an important effect on the operation of the u...

Страница 14: ...bjectionable when the unitis located very close to a living area Itis often advisable to route the return air ducts under the floor or through the attic Refer to furnace Technical Support Manual Blower Data for air flow information Size ductwork to handle air flow for heating and air condition ing if used Duct Installation Requirements When furnace supply ducts carry air outside furnace area seal ...

Страница 15: ...e high velocity filter providing they meet the minimum size areas Washable high velocity filters can be replaced ONLY with same type and size 2 5 2 0 3 1 Figure 12 Optional Duct Standoff 20 x 25 Optional Filter Rack Filter Installation using Optional Filter Rack When installing or removing a bottom mounted filter slide the two side filter clips to the back of the furnace BEFORE installing or re mo...

Страница 16: ...Blower Speed ELECTRICAL SHOCK HAZARD Failure to do so can result in death personal injury and or property damage Turn OFF power to furnace before changing speed taps NOTE The speed taps that the manufacture sets from the factory for this product are based on a nominal 400 CFM per ton cooling and the basic mid range on the temperature rise for heating Since the manufacturer cannot establish the sta...

Страница 17: ...s removed from EFT Cool motor speed de energized after 90 second Cool Fan Off Delay time Circulating Fan G Request 24 VAC signals applied to G terminals of EFT control Heat motor speed energized without delay G signal removed from EFT Heat motor speed de energized without delay NOTE 1 Furnaces with PSC blower motors de energize the Low Heat fan speed during the heat exchanger warm up period on a c...

Страница 18: ...ry count exceeded failed to light within 4 trials for ignition 6 Flashes 2 Notes 1 2 Soft Lockout Maximum recycle count exceeded Last failure was Flame Sense Lost During Run Cycling Pressure Switch or Blocked Condensate 6 Flashes 3 Notes 1 2 Soft Lockout Maximum recycle count exceeded Last failure was Airflow Proving Circuit Opened During Run 6 Flashes 4 Notes 1 2 Soft Lockout Maximum recycle coun...

Отзывы: