background image

16

441 01 2610 00

NOTE:

Adjustment screw cover

MUST

be placed on gas valve be-

fore reading manifold pressure and operating furnace.

3. For altitudes up to 2000

¢

, set pressure to value shown in

Table 2

. For altitudes between 2000

¢

to 8000

¢

, see Section

6.

”Gas Supply and Piping”

for correct pressure value.

Adjust Pilot Burner

The furnace has a pilot flame to light the main burner. The flame

should surround

3

/

8

²

to

1

/

2

²

of the flame rod. See

Figure 14.

To ad-

just, remove cap from pilot adjusting screw on gas valve. Turn

screw counterclockwise to increase or clockwise to decrease

flame as required. Replace cap after adjusting screw.

Pilot Burner

Figure 14

Proper Flame

Adjustment

Flame Rod

Hot Surface

Igniter

10--11--65

Main Burner Flame Check

Allow the furnace to run approximately 10 minutes then inspect

the main burner and pilot flames. See

Figure 15

.

Check for the following (

Figure 15

):

·

Stable and blue flames. Dust may cause orange tips or

wisps of yellow, but flames

MUST NOT

have solid, yellow

tips.

·

Flames extending directly from burner into heat exchanger.

·

Flames do

NOT

touch sides of heat exchanger

If any problems with main burner flames are noted, it may be nec-

essary to adjust gas pressures, or check for drafts.

Main Burner

Burner Face

10--10--78

Figure 15

Temperature Rise Check

The blower speed

MUST

be set to give the correct air temperature

rise through the furnace as marked on the rating plate. Tempera-

ture rise is the difference between supply and return air tempera-

tures.

To check temperature rise,use the following procedure:

1. Place thermometers in supply and return air registers as

close to furnace as possible, avoiding direct radiant heat from

heat exchangers.

2. Take readings and compare with range specified on rating

plate.

3. If the temperature rise is not in the correct range, the blower

speed must be changed. A higher blower speed will lower the

temperature rise. A lower blower speed will increase the tem-

perature rise.

Changing Blower Speed

ELECTRICAL SHOCK HAZARD.
Failure to do so can result in death, personal injury

and/or property damage.
Turn OFF power to furnace before changing speed

taps.

!

NOTE

: The speed taps that the manufacture sets from the factory

for this product are based on a nominal 400 CFM per ton cooling

and the basic mid range on the temperature rise for heating.

Since the manufacturer cannot establish the static pressure

that will be applied to the unit, it is the responsibility of the

installer dealer/contractor to select the proper speed taps for

the application when the unit is installed.

If it is necessary to change speeds, refer to steps below.
1. Refer to

Furnace Wiring Diagram

for location of the heating

and cooling speed taps located on the electronic fan control

as well as location of unused blower motor speed leads. Use

the chart (

Table 6

) to determine the blower motor speed set-

tings.

Table 6

Blower Speed Chart

Wire Color

Motor Speed

Black

High

Orange

*

Med--High

Blue

Medium

Red

Low

*

Med--High speed may not be provided on all models.

2. Change the heat or cool blower motor speed by removing the

motor lead from the “

Heat

” or “

Cool

” terminal and replace it

with the desired motor speed lead from the

“Unused Motor

Lead

” location. Connect the wire previously removed from

the “

Heat

” or “

Cool

” terminal to the vacated

“Unused Motor

Lead

” terminal.

3. If the same speed must be used for both heating and cooling,

remove the undesired motor speed lead from the

“Heat

” or

“Cool

” terminal and connect that lead to the open terminal at

“Unused Motor Lead

” location or tape off. Attach a jumper

between the “

Heat

” and “

Cool

” terminals and the remaining

motor speed lead.

Note

: When using the same speed on motors with (4) speed

leads, it will be necessary to tape off the terminal of the motor

speed lead removed from the “

Heat

” or “

Cool

” terminal with

electrical tape since an open terminal will not be available at

the

“Unused Motor Lead

” location.

Continuous Fan Operation

A terminal is provided on the electronic fan control located in the

circulating blower compartment for operation of the continuous

fan option. This connection is intended for the low speed motor

Содержание H8UH5050B12

Страница 1: ...nel can perform basic maintenance functions such as cleaning and replacing air filters All other operations must be performed by trained service personnel When working on heating equipment observe precautions in the literature on tags and on labels attached to or shipped with the unit and other safety precautions that may apply Follow all safety codes In the United States follow all safety codes i...

Страница 2: ...of Supply Air F or C Temperature of Return Air F or C Rise Supply Temp Return Temp F or C Filter Type and Size Fan Time ON Setting Fan Time OFF Setting Manual Gas Shut Off Upstream of Furnace Drip Leg YES NO Drip Leg Upstream of Gas Valve YES NO Blower Speed Checked YES NO All Electrical Connections Tight YES NO Gas Valve OK YES NO Measured Line Pressure When Firing Unit Calculated Firing Rate See...

Страница 3: ...lt to provide many years of safe and dependable service providing it is properly installed and maintained However abuse and or improper use can shorten the life of the unit and create hazards for you the owner A The U S Consumer Product Safety Commission recom mends that users of gas burning appliances install carbon monoxide detectors There can be various sources of carbon monoxide in a building ...

Страница 4: ...e necessary to resize the existing vent line and chimney to prevent oversizing problems for the other remaining appliances s See applicable codes and Venting and Combustion Air Check and Gas Vent Installation section Location and Clearances If furnace is a replacement it is usually best to install the furnace where the old one was Choose the location or evaluate the exist ing location based upon t...

Страница 5: ...RONT 3 Recommended For Service 30 ALL SIDES Of SUPPLY PLENUM 1 SIDES 0 VENT Single Wall Vent 6 Type B 1 Double Wall Vent 1 TOP OF FURNACE 1 Horizontal position Line contact is permissible only between lines formed by intersections of top and two sides of furnace jacket and building joists studs or framing DIMENSIONAL INFORMATION Unit Cabinet Top Bottom Unit Capacity A B F C D H8UH5050B12 H8UH5075B...

Страница 6: ...nd ventilation air can result in death and or personal injury Use methods described here to provide combus tion and ventilation air Furnaces require ventilation openings to provide sufficient air for proper combustion and ventilation of flue gases All duct or open ingsforsupplyingcombustion andventilation airmustcomplywith the gas codes or in the absence of local codes the applicable na tional cod...

Страница 7: ...re 1 square inch of free area per4 000 BTUHfor combined input of all gas appliances in area see Table 1 One permanent opening commencing within 12 of the top of the enclosure shall be permitted where the equipment has clear ances ofatleast1 fromthe sides and back and 6 fromthe frontof the appliance The opening shall directly communicate with the outdoors or shall communicate through a vertical or ...

Страница 8: ...this furnace can result in death personal injury and or property damage Install the vent in compliance with codes of the country having ju risdiction local codes or ordinances and these instructions These fan assisted combustion furnaces have been classified as Category I appliances which means that they MUST operate with a negative vent pressure Category I Safe Venting Requirements NOTE The follo...

Страница 9: ...icates sufficient infiltration air Venting to Existing Masonry Chimney NOTE The tables and notes referred to below are found in the most recent printing of the United States National Fuel Gas Code venting tables Use the United States National Fuel Gas Code or NFGC Tables to size the chimney orvent Dedicatedventing ofone fanassisted furnace into any masonry chimney is restricted The chimney must fi...

Страница 10: ...for installations below 2000 in altitude Table 3 Orifice Sizes below 2000 Gas Type Manifold Pressure Specific Gravity Heating Value BTU per Cubic Ft Orifice Size Drill Natural 3 5 w c 800 40 3 5 w c 0 9kP 0 6 900 41 0 9kPa w c 0 6 1000 42 w c 1100 43 Propane 10 w c 2 5kPa w c 1 53 2500 54 Operation Above 2000 Altitude FIRE EXPLOSION CARBON MONOXIDE POISON ING HAZARD This conversion shall be done b...

Страница 11: ...FERENT SPECIFIC GRAVITY CONSULT THE LATEST EDITION OF THE NATIONAL FUEL GAS CODE ANSI Z223 1 and CAN B149 NOTE The derating of these units at 2 Natural and 4 L P has been tested and approved by AGA High Altitude Air Pressure Switch Altitudes over 4 000 require a different air pressure switch than the one installed at thefactory Check parts list for pressure switch and consult your distributor for ...

Страница 12: ...vide a 1 8 inch plug for test gauge connection immediate ly up stream of gas supply connection to furnace 7 Use two pipe wrenches when making connections to prevent gas valve from turning Typical Gas Piping Figure 8 25 24 35a Union Manual Valve Drip leg pipe cap left side entry 8 Flexible corrugated metal gas connector may NOT be used inside the furnace or be secured or supported by the furnace or...

Страница 13: ...s Fieldwiringconnectionsmustbemadeinsidethefurnaceconnec tion box A suitable strain relief should be used at the point the wires exit the furnace casing Copper conductors shall be used Line voltage wires should be sized for the input amps stated on the rating plate Furnace must be connected to its own separate circuit Thermostat Thermostat location has an important effect on the operation of the u...

Страница 14: ...bjectionable when the unitis located very close to a living area Itis often advisable to route the return air ducts under the floor or through the attic Refer to furnace Technical Support Manual Blower Data for air flow information Size ductwork to handle air flow for heating and air condition ing if used Duct Installation Requirements When furnace supply ducts carry air outside furnace area seal ...

Страница 15: ...e high velocity filter providing they meet the minimum size areas Washable high velocity filters can be replaced ONLY with same type and size 2 5 2 0 3 1 Figure 12 Optional Duct Standoff 20 x 25 Optional Filter Rack Filter Installation using Optional Filter Rack When installing or removing a bottom mounted filter slide the two side filter clips to the back of the furnace BEFORE installing or re mo...

Страница 16: ...Blower Speed ELECTRICAL SHOCK HAZARD Failure to do so can result in death personal injury and or property damage Turn OFF power to furnace before changing speed taps NOTE The speed taps that the manufacture sets from the factory for this product are based on a nominal 400 CFM per ton cooling and the basic mid range on the temperature rise for heating Since the manufacturer cannot establish the sta...

Страница 17: ...s removed from EFT Cool motor speed de energized after 90 second Cool Fan Off Delay time Circulating Fan G Request 24 VAC signals applied to G terminals of EFT control Heat motor speed energized without delay G signal removed from EFT Heat motor speed de energized without delay NOTE 1 Furnaces with PSC blower motors de energize the Low Heat fan speed during the heat exchanger warm up period on a c...

Страница 18: ...ry count exceeded failed to light within 4 trials for ignition 6 Flashes 2 Notes 1 2 Soft Lockout Maximum recycle count exceeded Last failure was Flame Sense Lost During Run Cycling Pressure Switch or Blocked Condensate 6 Flashes 3 Notes 1 2 Soft Lockout Maximum recycle count exceeded Last failure was Airflow Proving Circuit Opened During Run 6 Flashes 4 Notes 1 2 Soft Lockout Maximum recycle coun...

Отзывы: