background image

14

441 01 2610 00

Control Center Fuse

The 24V circuit contains a 5--amp, automotive--type fuse located

on control center. (See

Figure 10

) Any electrical shorts of 24V wir-

ing during installation, service, or maintenance may cause fuse to

blow. If fuse replacement is required, use only a fuse of identical

size (5 amp.)

Fan Timer Connections

Figure 10

25--23--41

DIP Switch

FUSE

8. Ductwork and Filter (Upflow/Horizontal)

CARBON MONOXIDE POISONING HAZARD.
Failure to properly seal duct can result in death

and/or personal injury.
Do NOT draw return air from inside a closet or

utility room where furnace is located. Return air

duct MUST be sealed to furnace casing.

!

Duct Connections

This furnace may be installed in only a bottom or side return ap-

plication. Return air through the back of the unit is

NOT

allowed.

Side connections can be made by cutting out the embossed area

shown in

Figure 11.

Cutting Side Return Air Opening

Starting

Hole

Figure 11

Bottom returns can be made by removing the knockout panel in

the furnace base. Do

NOT

remove knock-out except for a bottom

return.

Duct Design

Design and install air distribution system to comply with Air Condi-

tioning Contractors of America manuals or other approved meth-

ods that conform to local codes and good trade practices.

When the furnace is located in an area near or adjacent to the liv-

ing area, the system should be carefully designed with returns to

minimize noise transmission through the return air grille. Any

blower moving a high volume of air will produce audible noise

which could be objectionable when the unit is located very close to

a living area. It is often advisable to route the return air ducts under

the floor or through the attic.

·

Refer to furnace

Technical Support Manual

(Blower Data)

for air flow information.

·

Size ductwork to handle air flow for heating and air condition-

ing if used.

Duct Installation Requirements

·

When furnace supply ducts carry air outside furnace area,

seal return air duct to furnace casing and terminate duct out-

side furnace space.

·

When a refrigeration coil is used in conjunction with this unit, it

must be installed on the discharge side of the unit to avoid

condensation on the heat exchanger.

·

If separate evaporator and blower unit is used, install good

sealing dampers for air flow control. Chilled air going through

the furnace could cause condensation and shorten furnace

life. Dampers (purchased locally) can be either automatic or

manual. Manually operated dampers

MUST

be equipped

with a means to prevent furnace or air conditioning operation

unless damper is in the full heat or cool position.

!

CARBON MONOXIDE POISONING HAZARD.

This could result in personal injury and/or death.
Cool air passing over heat exchanger can cause

condensate to form resulting in heat exchanger failure.

·

Installation of locking-type dampers are recommended in all

branches, or in individual ducts to balance system’s air flow.

·

If air return grille is located close to the fan inlet, install at least

one, 90

°

air turn between fan and inlet grille to reduce noise.

·

Ductwork installed in attic, or exposed to outside tempera-

tures requires a minimum of 2

²

of insulation with outdoor type

vapor barrier.

·

Ductwork installed in an indoor unconditioned space requires

a minimum of 1

²

of insulation with indoor type vapor barrier.

Содержание H8UH5050B12

Страница 1: ...nel can perform basic maintenance functions such as cleaning and replacing air filters All other operations must be performed by trained service personnel When working on heating equipment observe precautions in the literature on tags and on labels attached to or shipped with the unit and other safety precautions that may apply Follow all safety codes In the United States follow all safety codes i...

Страница 2: ...of Supply Air F or C Temperature of Return Air F or C Rise Supply Temp Return Temp F or C Filter Type and Size Fan Time ON Setting Fan Time OFF Setting Manual Gas Shut Off Upstream of Furnace Drip Leg YES NO Drip Leg Upstream of Gas Valve YES NO Blower Speed Checked YES NO All Electrical Connections Tight YES NO Gas Valve OK YES NO Measured Line Pressure When Firing Unit Calculated Firing Rate See...

Страница 3: ...lt to provide many years of safe and dependable service providing it is properly installed and maintained However abuse and or improper use can shorten the life of the unit and create hazards for you the owner A The U S Consumer Product Safety Commission recom mends that users of gas burning appliances install carbon monoxide detectors There can be various sources of carbon monoxide in a building ...

Страница 4: ...e necessary to resize the existing vent line and chimney to prevent oversizing problems for the other remaining appliances s See applicable codes and Venting and Combustion Air Check and Gas Vent Installation section Location and Clearances If furnace is a replacement it is usually best to install the furnace where the old one was Choose the location or evaluate the exist ing location based upon t...

Страница 5: ...RONT 3 Recommended For Service 30 ALL SIDES Of SUPPLY PLENUM 1 SIDES 0 VENT Single Wall Vent 6 Type B 1 Double Wall Vent 1 TOP OF FURNACE 1 Horizontal position Line contact is permissible only between lines formed by intersections of top and two sides of furnace jacket and building joists studs or framing DIMENSIONAL INFORMATION Unit Cabinet Top Bottom Unit Capacity A B F C D H8UH5050B12 H8UH5075B...

Страница 6: ...nd ventilation air can result in death and or personal injury Use methods described here to provide combus tion and ventilation air Furnaces require ventilation openings to provide sufficient air for proper combustion and ventilation of flue gases All duct or open ingsforsupplyingcombustion andventilation airmustcomplywith the gas codes or in the absence of local codes the applicable na tional cod...

Страница 7: ...re 1 square inch of free area per4 000 BTUHfor combined input of all gas appliances in area see Table 1 One permanent opening commencing within 12 of the top of the enclosure shall be permitted where the equipment has clear ances ofatleast1 fromthe sides and back and 6 fromthe frontof the appliance The opening shall directly communicate with the outdoors or shall communicate through a vertical or ...

Страница 8: ...this furnace can result in death personal injury and or property damage Install the vent in compliance with codes of the country having ju risdiction local codes or ordinances and these instructions These fan assisted combustion furnaces have been classified as Category I appliances which means that they MUST operate with a negative vent pressure Category I Safe Venting Requirements NOTE The follo...

Страница 9: ...icates sufficient infiltration air Venting to Existing Masonry Chimney NOTE The tables and notes referred to below are found in the most recent printing of the United States National Fuel Gas Code venting tables Use the United States National Fuel Gas Code or NFGC Tables to size the chimney orvent Dedicatedventing ofone fanassisted furnace into any masonry chimney is restricted The chimney must fi...

Страница 10: ...for installations below 2000 in altitude Table 3 Orifice Sizes below 2000 Gas Type Manifold Pressure Specific Gravity Heating Value BTU per Cubic Ft Orifice Size Drill Natural 3 5 w c 800 40 3 5 w c 0 9kP 0 6 900 41 0 9kPa w c 0 6 1000 42 w c 1100 43 Propane 10 w c 2 5kPa w c 1 53 2500 54 Operation Above 2000 Altitude FIRE EXPLOSION CARBON MONOXIDE POISON ING HAZARD This conversion shall be done b...

Страница 11: ...FERENT SPECIFIC GRAVITY CONSULT THE LATEST EDITION OF THE NATIONAL FUEL GAS CODE ANSI Z223 1 and CAN B149 NOTE The derating of these units at 2 Natural and 4 L P has been tested and approved by AGA High Altitude Air Pressure Switch Altitudes over 4 000 require a different air pressure switch than the one installed at thefactory Check parts list for pressure switch and consult your distributor for ...

Страница 12: ...vide a 1 8 inch plug for test gauge connection immediate ly up stream of gas supply connection to furnace 7 Use two pipe wrenches when making connections to prevent gas valve from turning Typical Gas Piping Figure 8 25 24 35a Union Manual Valve Drip leg pipe cap left side entry 8 Flexible corrugated metal gas connector may NOT be used inside the furnace or be secured or supported by the furnace or...

Страница 13: ...s Fieldwiringconnectionsmustbemadeinsidethefurnaceconnec tion box A suitable strain relief should be used at the point the wires exit the furnace casing Copper conductors shall be used Line voltage wires should be sized for the input amps stated on the rating plate Furnace must be connected to its own separate circuit Thermostat Thermostat location has an important effect on the operation of the u...

Страница 14: ...bjectionable when the unitis located very close to a living area Itis often advisable to route the return air ducts under the floor or through the attic Refer to furnace Technical Support Manual Blower Data for air flow information Size ductwork to handle air flow for heating and air condition ing if used Duct Installation Requirements When furnace supply ducts carry air outside furnace area seal ...

Страница 15: ...e high velocity filter providing they meet the minimum size areas Washable high velocity filters can be replaced ONLY with same type and size 2 5 2 0 3 1 Figure 12 Optional Duct Standoff 20 x 25 Optional Filter Rack Filter Installation using Optional Filter Rack When installing or removing a bottom mounted filter slide the two side filter clips to the back of the furnace BEFORE installing or re mo...

Страница 16: ...Blower Speed ELECTRICAL SHOCK HAZARD Failure to do so can result in death personal injury and or property damage Turn OFF power to furnace before changing speed taps NOTE The speed taps that the manufacture sets from the factory for this product are based on a nominal 400 CFM per ton cooling and the basic mid range on the temperature rise for heating Since the manufacturer cannot establish the sta...

Страница 17: ...s removed from EFT Cool motor speed de energized after 90 second Cool Fan Off Delay time Circulating Fan G Request 24 VAC signals applied to G terminals of EFT control Heat motor speed energized without delay G signal removed from EFT Heat motor speed de energized without delay NOTE 1 Furnaces with PSC blower motors de energize the Low Heat fan speed during the heat exchanger warm up period on a c...

Страница 18: ...ry count exceeded failed to light within 4 trials for ignition 6 Flashes 2 Notes 1 2 Soft Lockout Maximum recycle count exceeded Last failure was Flame Sense Lost During Run Cycling Pressure Switch or Blocked Condensate 6 Flashes 3 Notes 1 2 Soft Lockout Maximum recycle count exceeded Last failure was Airflow Proving Circuit Opened During Run 6 Flashes 4 Notes 1 2 Soft Lockout Maximum recycle coun...

Отзывы: