background image

10

441 01 2610 00

CARBON MONOXIDE POISONING, FIRE AND

EXPLOSION HAZARD.
Failure to follow these instructions can result in

death, personal injury and/or property damage.
Models designated for Natural Gas are to be used

with Natural Gas ONLY, unless properly converted

to use with LP gas.

!

Gas Supply Requirements

·

Use only the Type of gas approved for this furnace. See rating

plate for approved gas type.

·

Gas input must not exceed the rated input shown on the rating

plate. Overfiring will result in failure of heat exchanger and

cause dangerous operation.

·

Do not allow minimum supply pressure to vary downward.

Doing so will decrease input to furnace. Refer to

Table 2

for

Gas supply and manifold pressures.

Table 2

Gas Pressures

Gas

T

Supply Pressure

Manifold

P

Type

Recommended

Max.

Min.

Pressure

Natural

7

²

14

²

4.5

²

3.5

²

Propane

11

²

14

²

11

²

10

²

Natural Gas Input Rating Check

The gas meter can be used to measure input to furnace. Rating is

based on a natural gas BTU content of 1,000 BTU’s per cubic foot.

Check with gas supplier for actual BTU content.

1. Turn

OFF

gas supply to all appliances other than furnace and

start furnace.

2. Time how many seconds it takes the smallest dial on the gas

meter to make one complete revolution. Refer to

Example

.

Note:

If meter uses a 2 cubic foot dial, divide results (se-

conds) by two.

Example

Natural Gas

BTU Content

No. of Seconds

Per Hour

Time Per Cubic

Foot in Seconds

BTU Per

Hour

1,000

3,600

48

75,000

1,000 x 3,600

¸

48 = 75,000 BTUH

3.

Relight all appliances and ensure all pilots are operating.

Orifice Sizing

NOTE:

Factory sized orifices for natural and LP gas are listed in

the furnace Technical Support manual.

Ensure furnace is equipped with the correct main burner orifices.

Refer to

Table 3

for correct orifice size for a given heating value

and specific gravity for natural and propane gas. Note that this

chart is

ONLY

for installations

below

2000

¢

in altitude.

Table 3

Orifice Sizes (below 2000

¢

)

Gas

Type

Manifold

Pressure

Specific

Gravity

Heating Value

(BTU per

Cubic Ft.)

Orifice Size

(Drill #)

Natural

3 5

²

w c

800

40

3.5

²

w.c.

0 9kP

0 6

900

41

0.9kPa

w c

0.6

1000

42

w.c.

1100

43

Propane

10

²

w.c.

2.5kPa

w.c.

1.53

2500

54

Operation Above 2000

¢

Altitude

FIRE, EXPLOSION, CARBON MONOXIDE POISON-

ING HAZARD.
This conversion shall be done by a qualified ser-

vice agency in accordance with the Manufactur-

er’s instructions and all applicable codes and re-

quirements, or in the absence of local codes, the

applicable national codes.
Failure to follow these instructions exactly can re-

sult in death, personal injury and/or property dam-

age.

!

These units may be used at full input rating when installed at alti-

tudes up to 2000

¢

. When installed above 2000

¢

, the input must be

decreased 2%(natural) or 4%(LP) for each 1000

¢

above sea level.

This may be accomplished by a simple adjustment of manifold

pressure or an orifice change, or a combination of a pressure ad-

justment and an orifice change. The changes required depend on

the installation altitude and the heating value of the fuel.

Table 4

&

Table 5

show the proper furnace manifold pressure and gas ori-

fice size to achieve proper performance based on elevation above

sea level for both natural gas and propane.
To use the natural gas table, first consult your local gas utility for

the heating value of the gas supply. Select the heating value on the

vertical border and follow across the table until the appropriate

elevation for the installation is reached. The first value in the box at

the intersection of the heating value and elevation will be the man-

ifold pressure required. If a gas orifice change is also required, the

box is shaded. The required orifice size is shown at the bottom of

the table.

Sea Level

High Altitude Input Rate = Nameplate x (Multiplier)

Input Rate

Elevation

High Altitude Multiplier

Elevation

Natural

LP Gas

2000

¢

- 2999

¢

0.96

0.92

3000

¢

- 3999

¢

0.94

0.88

4000

¢

- 4999

¢

0.92

0.84

5000

¢

- 5999

¢

0.90

0.80

6000

¢

- 6999

¢

0.88

0.76

7000

¢

- 7999

¢

0.86

0.72

Содержание H8UH5050B12

Страница 1: ...nel can perform basic maintenance functions such as cleaning and replacing air filters All other operations must be performed by trained service personnel When working on heating equipment observe precautions in the literature on tags and on labels attached to or shipped with the unit and other safety precautions that may apply Follow all safety codes In the United States follow all safety codes i...

Страница 2: ...of Supply Air F or C Temperature of Return Air F or C Rise Supply Temp Return Temp F or C Filter Type and Size Fan Time ON Setting Fan Time OFF Setting Manual Gas Shut Off Upstream of Furnace Drip Leg YES NO Drip Leg Upstream of Gas Valve YES NO Blower Speed Checked YES NO All Electrical Connections Tight YES NO Gas Valve OK YES NO Measured Line Pressure When Firing Unit Calculated Firing Rate See...

Страница 3: ...lt to provide many years of safe and dependable service providing it is properly installed and maintained However abuse and or improper use can shorten the life of the unit and create hazards for you the owner A The U S Consumer Product Safety Commission recom mends that users of gas burning appliances install carbon monoxide detectors There can be various sources of carbon monoxide in a building ...

Страница 4: ...e necessary to resize the existing vent line and chimney to prevent oversizing problems for the other remaining appliances s See applicable codes and Venting and Combustion Air Check and Gas Vent Installation section Location and Clearances If furnace is a replacement it is usually best to install the furnace where the old one was Choose the location or evaluate the exist ing location based upon t...

Страница 5: ...RONT 3 Recommended For Service 30 ALL SIDES Of SUPPLY PLENUM 1 SIDES 0 VENT Single Wall Vent 6 Type B 1 Double Wall Vent 1 TOP OF FURNACE 1 Horizontal position Line contact is permissible only between lines formed by intersections of top and two sides of furnace jacket and building joists studs or framing DIMENSIONAL INFORMATION Unit Cabinet Top Bottom Unit Capacity A B F C D H8UH5050B12 H8UH5075B...

Страница 6: ...nd ventilation air can result in death and or personal injury Use methods described here to provide combus tion and ventilation air Furnaces require ventilation openings to provide sufficient air for proper combustion and ventilation of flue gases All duct or open ingsforsupplyingcombustion andventilation airmustcomplywith the gas codes or in the absence of local codes the applicable na tional cod...

Страница 7: ...re 1 square inch of free area per4 000 BTUHfor combined input of all gas appliances in area see Table 1 One permanent opening commencing within 12 of the top of the enclosure shall be permitted where the equipment has clear ances ofatleast1 fromthe sides and back and 6 fromthe frontof the appliance The opening shall directly communicate with the outdoors or shall communicate through a vertical or ...

Страница 8: ...this furnace can result in death personal injury and or property damage Install the vent in compliance with codes of the country having ju risdiction local codes or ordinances and these instructions These fan assisted combustion furnaces have been classified as Category I appliances which means that they MUST operate with a negative vent pressure Category I Safe Venting Requirements NOTE The follo...

Страница 9: ...icates sufficient infiltration air Venting to Existing Masonry Chimney NOTE The tables and notes referred to below are found in the most recent printing of the United States National Fuel Gas Code venting tables Use the United States National Fuel Gas Code or NFGC Tables to size the chimney orvent Dedicatedventing ofone fanassisted furnace into any masonry chimney is restricted The chimney must fi...

Страница 10: ...for installations below 2000 in altitude Table 3 Orifice Sizes below 2000 Gas Type Manifold Pressure Specific Gravity Heating Value BTU per Cubic Ft Orifice Size Drill Natural 3 5 w c 800 40 3 5 w c 0 9kP 0 6 900 41 0 9kPa w c 0 6 1000 42 w c 1100 43 Propane 10 w c 2 5kPa w c 1 53 2500 54 Operation Above 2000 Altitude FIRE EXPLOSION CARBON MONOXIDE POISON ING HAZARD This conversion shall be done b...

Страница 11: ...FERENT SPECIFIC GRAVITY CONSULT THE LATEST EDITION OF THE NATIONAL FUEL GAS CODE ANSI Z223 1 and CAN B149 NOTE The derating of these units at 2 Natural and 4 L P has been tested and approved by AGA High Altitude Air Pressure Switch Altitudes over 4 000 require a different air pressure switch than the one installed at thefactory Check parts list for pressure switch and consult your distributor for ...

Страница 12: ...vide a 1 8 inch plug for test gauge connection immediate ly up stream of gas supply connection to furnace 7 Use two pipe wrenches when making connections to prevent gas valve from turning Typical Gas Piping Figure 8 25 24 35a Union Manual Valve Drip leg pipe cap left side entry 8 Flexible corrugated metal gas connector may NOT be used inside the furnace or be secured or supported by the furnace or...

Страница 13: ...s Fieldwiringconnectionsmustbemadeinsidethefurnaceconnec tion box A suitable strain relief should be used at the point the wires exit the furnace casing Copper conductors shall be used Line voltage wires should be sized for the input amps stated on the rating plate Furnace must be connected to its own separate circuit Thermostat Thermostat location has an important effect on the operation of the u...

Страница 14: ...bjectionable when the unitis located very close to a living area Itis often advisable to route the return air ducts under the floor or through the attic Refer to furnace Technical Support Manual Blower Data for air flow information Size ductwork to handle air flow for heating and air condition ing if used Duct Installation Requirements When furnace supply ducts carry air outside furnace area seal ...

Страница 15: ...e high velocity filter providing they meet the minimum size areas Washable high velocity filters can be replaced ONLY with same type and size 2 5 2 0 3 1 Figure 12 Optional Duct Standoff 20 x 25 Optional Filter Rack Filter Installation using Optional Filter Rack When installing or removing a bottom mounted filter slide the two side filter clips to the back of the furnace BEFORE installing or re mo...

Страница 16: ...Blower Speed ELECTRICAL SHOCK HAZARD Failure to do so can result in death personal injury and or property damage Turn OFF power to furnace before changing speed taps NOTE The speed taps that the manufacture sets from the factory for this product are based on a nominal 400 CFM per ton cooling and the basic mid range on the temperature rise for heating Since the manufacturer cannot establish the sta...

Страница 17: ...s removed from EFT Cool motor speed de energized after 90 second Cool Fan Off Delay time Circulating Fan G Request 24 VAC signals applied to G terminals of EFT control Heat motor speed energized without delay G signal removed from EFT Heat motor speed de energized without delay NOTE 1 Furnaces with PSC blower motors de energize the Low Heat fan speed during the heat exchanger warm up period on a c...

Страница 18: ...ry count exceeded failed to light within 4 trials for ignition 6 Flashes 2 Notes 1 2 Soft Lockout Maximum recycle count exceeded Last failure was Flame Sense Lost During Run Cycling Pressure Switch or Blocked Condensate 6 Flashes 3 Notes 1 2 Soft Lockout Maximum recycle count exceeded Last failure was Airflow Proving Circuit Opened During Run 6 Flashes 4 Notes 1 2 Soft Lockout Maximum recycle coun...

Отзывы: