INSTALLATION INSTRUCTIONS

G1N80BU, GIN80BR, GIN80BT, CG80UB, CG80RB, & CG80TB

80% Gas-Fired Furnace

Manufactured By

A.A.C.

A Lennox International Company

421 Monroe Street

Bellevue, OH  44811

TABLE OF CONTENTS

SAFETY ................................................. 2

INSTALLATION ...................................... 2

START-UP ............................................ 14

OPERATION ........................................ 15

MAINTENANCE................................... 16

CONTROL SYSTEM DIAGNOSTICS .. 18

REPAIR PARTS ................................... 18

WIRING DIAGRAMS ............................ 19

Do not store combustible materials, including

gasoline and other flammable vapors and

liquids, near the furnace, vent pipe, or warm

air ducts. The homeowner should be cau-

tioned that the furnace area must not be

used as a broom closet or for any other

storage purposes. Such uses may result in

actions that could cause property damage,

personal injury, or death.

  WARNING

This furnace is not approved for installation in

a mobile home. Do not install this furnace in a

mobile home. Installation in a mobile home

could result in actions that could cause prop-

erty damage, personal injury, or death.

  WARNING

Improper installation, adjustment, alteration, service or maintenance can cause injury

or property damage. Refer to this manual. For assistance or additional information,

consult a qualified installer, service agency, or the gas supplier.

 

WARNING

The installation of the furnace, wiring, warm air ducts, venting, etc. must conform to the requirements of the

National Fire Protection Association; the National Fuel Gas Code, ANSI Z223.1/NFPA No. 54 (latest edition)

and the National Electrical Code, ANSI/NFPA No. 70 (latest edition) in the United States; CSA B149.1

(latest edition) Natural Gas and Propane Installation Codes and the Canadian Electrical Code Part 1, CSA

22.1 (latest edition) in Canada; and any state or provincial laws, local ordinances (including plumbing or

wastewater codes), or local gas utility requirements. Local authorities having jurisdiction should be con-

sulted before installation is made. Such applicable regulations or requirements take precedence over the

general instructions in this manual.

 IMPORTANT

®

®

Содержание CG80RB

Страница 1: ...s that could cause prop erty damage personal injury or death WARNING Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual For ass...

Страница 2: ...ons 4 Combustion products must be discharged outdoors Connect this furnace to an approved vent system only as specified in Venting beginning on page 6 of these instructions 5 Never test for gas leaks...

Страница 3: ...in respect to the heat distribution system as much as practicable When installed in a utility room the door should be wide enough to allow the largest part of the furnace to enter or permit the replac...

Страница 4: ...opening shall have a free area of 1 square inch per 4000 BTU HR of the total input rating of all appliances within the enclosure Do not use the furnace as a heater in a building under construction The...

Страница 5: ...nother option is to use horizontal combustion ducts see Figure 6 If horizontal combustion ducts are run 1 square inch per 2000 BTU HR is required Contaminated Combustion Air Excessive exposure to cont...

Страница 6: ...venting are permitted when done in accordance with applicable codes such as local and national codes The venting system should be designed in accordance with the FAN columns in the venting tables in t...

Страница 7: ...es 8 and 9 13 All unused chimney openings should be closed 14 All vent pipe run through unconditioned areas or outside shall be constructed of factory built chimney sections see Figure 8 15 Multistory...

Страница 8: ...ting system are not in operation 1 Seal any unused openings in the common venting system 2 Visually inspect the venting system for proper size and horizontal pitch as required in the National Fuel Gas...

Страница 9: ...v o b a d e t a c o l t i f f o s d e t a l i t n e v o t e c n a r a e l c l a c i t r e V e h t m o r f m c 1 6 t e e f 2 f o e c n a t s i d l a t n o z i r o h a n i h t i w l a n i m r e t l a n...

Страница 10: ...connect a return air duct to the bottom or to enclose the bottom when side return is desired may result in combustion products being drawn into the circulating air stream which could result in asphyxi...

Страница 11: ...B G1N80BR and CG80RB Models Filters are not supplied with G1N80BT CG80TB G1N80BR or CG80RB series furnaces since filters are commonly located behind a return grille for ease of servicing It is the Fig...

Страница 12: ...ne by qualified person nel using a conversion kit available from the manufacturer following the instructions in the conversion kit If done improperly overfiring of the burners and improper burner oper...

Страница 13: ...r the thermostat the wiring to be done and any replacement of wire shall conform with the temperature limitation for Type T wire 63 F 35 C rise Connect a sufficiently sized wire with ground to the fur...

Страница 14: ...connection of a 120 volt electronic air cleaner The EAC terminal is energized whenever the thermostat calls for heat cooling or continuous blower Refer to the furnace wiring diagram for specific conne...

Страница 15: ...second cooling fan on delay OPERATION Should overheating occur or the gas supply fail to shut off shut off the manual gas valve to the appliance before shutting off the elec trical supply WARNING The...

Страница 16: ...g plate To use the same speed tap for both heating and cooling install a piggyback terminal on the speed tap using a short jumper Wire 1 4 quick connect termi nals on both ends to jumper the HEAT and...

Страница 17: ...ment is present Flame should be predominantly blue in color and strong in appear ance Check that all burners are lit and that the flame does not impinge on the sides of the heat exchanger Distorted fl...

Страница 18: ...Return Filter Kit Upflow Models AFILT525 Return Filter Kit Counterflow Models AFILT529 Bottom Return Filter Kit ATWIN579 Twinning Kit ABASE511 Combustible Floor Base 14 5 cabinets ABASE512 Combustible...

Страница 19: ...45464K003 Page 19 Connection Diagram P N 45198 005 Figure 18...

Страница 20: ...45464K003 Page 20 Figure 19 Schematic Diagram P N 45198 005...