Lennox CG80RB Скачать руководство пользователя страница 10

# 45464K003

Page 10

When installing a CAM coil in a horizontal position with a

horizontal gas furnace, always keep the open end of the

A-coil 

facing the supply air outlet

 of the furnace (blow into

the open end of the A-coil). The A-coil should 

point away

from the supply air outlet

 of the furnace (see Figure 11).

If a cooling coil is not installed with the furnace, then a

removable access panel should be provided in the supply

plenum for purposes of inspecting the heat exchanger.

This opening shall be accessible when the furnace is

installed, and shall be of such size that the heat exchanger

can be viewed for possible openings using light assistance

or a probe can be inserted for sampling the air stream. The

cover for the opening shall be leaktight.

Upflow Installations

G1N80BU, G1N80BT, CG80UB, and CG80TB series

furnaces can be installed as upflow units with either a side

or bottom air return. For units that do not include a side

return filter rack, kit AFILT524 can be used. Bottom filter

kit AFILT529 can be used with all G1N80BU, G1N80BT,

CG80UB, and CG80TB series furnaces.

For side return installation, a full-size return air opening

must be cut in the side panel. A starter hole and corner

embossments are provided in each side (see Figure 13 in

the 

Filters

 section).

To provide sufficient filter area for installations requiring

more than 1600 CFM nominal air delivery, return air will

have to be brought through both sides of the furnace,

through one side and the bottom, or optional filter rack

AFILTHA7 may be used.

When side return is desired on a furnace with

an open bottom, the bottom must be sealed

with a piece of sheet metal large enough to

cover the entire opening. Failure to connect a

return air duct to the bottom, or to enclose

the bottom when side return is desired, may

result in combustion products being drawn

into the circulating air stream which could

result in asphyxiation.

  WARNING

Horizontal Installations

G1N80BR, G1N80BT, CG80RB, and CG80TB series

furnaces can be horizontally installed for airflow right to left

or left to right. These furnaces are to be installed so that

the burner and blower access panels are in a vertical

plane; they are 

NOT

 to be installed such that these panels

are in a horizontal plane (see Figure 1 on page 2). 

Never

install any furnace on its back.

Counterflow (Downflow) Installations

G1N80BR and CG80RB furnaces may be installed directly

on the supply plenum or coil cabinet if the furnace is

installed on a non-combustible floor.

For installations on combustible flooring, a special base

must be ordered and used. (See the 

Accessories

 section on

page 18 for more information.) To install the special base:

1. Cut a hole in the floor, sized to provide 1" clearance

between all four sides of the duct and the edge of the

flooring (see Figure 12). The four angles on the base

assembly should recess into the floor joists and the

base should rest on all four outside flanges.

2. Construct duct connections with 1" to 1-3/4" right

angle flanges, and long enough to extend below the

floor joists.

3. Drop the duct connections through the top of the base

assembly with the right angle flanges in good contact

with the glass tape on top of the base assembly.

4. Carefully position furnace over right angle duct flanges.

Filters

Filters are not supplied with CG80UB, CG80TB, or
CG80RB series furnaces.

G1N80BU Models

A filter rack and washable 16" x 25" x 1/2" filter are

supplied with each G1N80BU furnace. (Models designed

Figure 11

Correct Positioning of CAM Coil in the

Horizontal Position with a Gas Furnace

Return

Supply

Correct

Return

Supply

Incorrect

Содержание CG80RB

Страница 1: ...s that could cause prop erty damage personal injury or death WARNING Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual For ass...

Страница 2: ...ons 4 Combustion products must be discharged outdoors Connect this furnace to an approved vent system only as specified in Venting beginning on page 6 of these instructions 5 Never test for gas leaks...

Страница 3: ...in respect to the heat distribution system as much as practicable When installed in a utility room the door should be wide enough to allow the largest part of the furnace to enter or permit the replac...

Страница 4: ...opening shall have a free area of 1 square inch per 4000 BTU HR of the total input rating of all appliances within the enclosure Do not use the furnace as a heater in a building under construction The...

Страница 5: ...nother option is to use horizontal combustion ducts see Figure 6 If horizontal combustion ducts are run 1 square inch per 2000 BTU HR is required Contaminated Combustion Air Excessive exposure to cont...

Страница 6: ...venting are permitted when done in accordance with applicable codes such as local and national codes The venting system should be designed in accordance with the FAN columns in the venting tables in t...

Страница 7: ...es 8 and 9 13 All unused chimney openings should be closed 14 All vent pipe run through unconditioned areas or outside shall be constructed of factory built chimney sections see Figure 8 15 Multistory...

Страница 8: ...ting system are not in operation 1 Seal any unused openings in the common venting system 2 Visually inspect the venting system for proper size and horizontal pitch as required in the National Fuel Gas...

Страница 9: ...v o b a d e t a c o l t i f f o s d e t a l i t n e v o t e c n a r a e l c l a c i t r e V e h t m o r f m c 1 6 t e e f 2 f o e c n a t s i d l a t n o z i r o h a n i h t i w l a n i m r e t l a n...

Страница 10: ...connect a return air duct to the bottom or to enclose the bottom when side return is desired may result in combustion products being drawn into the circulating air stream which could result in asphyxi...

Страница 11: ...B G1N80BR and CG80RB Models Filters are not supplied with G1N80BT CG80TB G1N80BR or CG80RB series furnaces since filters are commonly located behind a return grille for ease of servicing It is the Fig...

Страница 12: ...ne by qualified person nel using a conversion kit available from the manufacturer following the instructions in the conversion kit If done improperly overfiring of the burners and improper burner oper...

Страница 13: ...r the thermostat the wiring to be done and any replacement of wire shall conform with the temperature limitation for Type T wire 63 F 35 C rise Connect a sufficiently sized wire with ground to the fur...

Страница 14: ...connection of a 120 volt electronic air cleaner The EAC terminal is energized whenever the thermostat calls for heat cooling or continuous blower Refer to the furnace wiring diagram for specific conne...

Страница 15: ...second cooling fan on delay OPERATION Should overheating occur or the gas supply fail to shut off shut off the manual gas valve to the appliance before shutting off the elec trical supply WARNING The...

Страница 16: ...g plate To use the same speed tap for both heating and cooling install a piggyback terminal on the speed tap using a short jumper Wire 1 4 quick connect termi nals on both ends to jumper the HEAT and...

Страница 17: ...ment is present Flame should be predominantly blue in color and strong in appear ance Check that all burners are lit and that the flame does not impinge on the sides of the heat exchanger Distorted fl...

Страница 18: ...Return Filter Kit Upflow Models AFILT525 Return Filter Kit Counterflow Models AFILT529 Bottom Return Filter Kit ATWIN579 Twinning Kit ABASE511 Combustible Floor Base 14 5 cabinets ABASE512 Combustible...

Страница 19: ...45464K003 Page 19 Connection Diagram P N 45198 005 Figure 18...

Страница 20: ...45464K003 Page 20 Figure 19 Schematic Diagram P N 45198 005...

Отзывы: