background image

- 3 -

3. WIRING

3.1 General

Electrical power wiring must be fitted and certified by 

persons with appropriate qualifications and certification.
A signed 'Certificate of Compliance' must be left with the 

unit for insurance purposes.

3.2 Power to unit

All power wiring is to be done to the appropriate electrical 

standard of the country in which the unit is being installed.
The person installing the wiring is responsible for the 

correct selection of wiring size and auxiliary components.
See the Specification Sheet for supply voltage range, 

frequency, phase and maximum operating current .
Wire the unit directly from the Electrical Distribution 

Board.
The unit should have its own dedicated circuit breaker 

on the Distribution Board. 

Route the power supply cord 

through the entry hole provided. 

MWH/R 900: Use the mounting track provided, which 

includes cable ties.
DO NOT install wiring in contact with refrigeration piping.

Refer Figure 3 for client wiring.

3.3 Power to optional Room AC Units – ducted type

Single phase mains power wiring to each zoned unit (if 

applicable) shall be taken from the distribution board.

3.4 Control 

Simply connect power (and water) and switch the unit ON 

and the unit's built-in UC8 Controller works to maintain 

the default leaving water temperature (LWT) of 45°C.
The maximum LWT can be raised to a maximum of 55°C 

if the application requires it, eg long pipe systems and/or 

multiple small fan coil units or radiators.

Note: Higher LWT will reduce the efficiency of the unit.
To adjust the supply water temperature, refer 

Commissioning 4.3.

MWR only:

In cooling mode, the UC8 works to maintain the default 

leaving water temperature (LWT) of 7°C. The minimum 

LWT can be lowered to a minimum of 3°C if the 

application requires it.

Note: Lower LWT will reduce the efficiency of the unit.

Adding glycol to the water loop is recommended for low 

LWT applications. 

A single load Leaving Air Temperature (LAT) control 

application requires a Programmed Logic Controller 

(PLC) to be installed. Refer Temperzone for 

'LAT Control 

User Guide' for set-up.

MWH 900/2000 models include a PLC for stage control 

of more than one compressor, and de-ice control 

management.

3.5 BMS Control 

MWH/R external control options are limited to Remote 

On/Off and Modbus/RTU control using the on-board UC8 

(refer Appendix I).
MWH/R 250, 450 Single Compressor models:  

An optional PLC is available to enable more options 

including BACnet and scheduling. Refer to Temperzone 

for more information.
MWH 900/2000 Multiple Compressor models:  

PLC supplied as standard and includes BACnet and 

scheduling. Refer to Temperzone for more information.

WIRING

Figure 3  Client Wiring

MWH/R Unit

UC8

UC8

E

N

L1
L2
L3

Power Supply

1Ø (2 core+E) 

or 

3Ø (4 core+E)

depending on unit

External

Protection

Isolator

On

0V

Optional

Remote On/Off

(remove link if used)

Optional

Communicating

BMS Controller

Modbus RTU

B1
A1
0V

B
A

REF

Control

- shielded

twisted pair

2 core + screen

link

Содержание MWH 2000

Страница 1: ...unit or connections will not result in damage to the area adjacent to the appliance or to lower floors of the structure When such locations cannot be avoided it is recommended that a suitable drain pa...

Страница 2: ...heat the joints and cause restricted flow Restricted flow rates may result in over pressure HP faults occurring Use water treatment when connecting to steel piping one that prevents internal corrosion...

Страница 3: ...es it eg long pipe systems and or multiple small fan coil units or radiators Note Higher LWT will reduce the efficiency of the unit To adjust the supply water temperature refer Commissioning 4 3 MWR o...

Страница 4: ...s On and the entering water temperature EWT is greater than 5 C below the target set temperature default 45 C and the outdoor ambient temperature is above 15 C Stop Mode The remote On Off switch is Of...

Страница 5: ...e on holiday The labels should be fixed adjacent to the heat pump outdoor power point and on the main fuse switchboard of the building Advise the building occupier Note The addition of glycol to the w...

Страница 6: ...ort Note Cold water in the system is more likely to result in air locks than warm water Once the water heats the air will tend to be naturally removed through the automatic air bleed Cooler water abso...

Страница 7: ...e each connected UC8 controller has a unique Modbus device address Refer to section 5 4 for the procedure Example For detailed information about monitoring and control via Modbus RTU refer to document...

Страница 8: ...ndensing temperature 42 C Compressor discharge line temperature C dLt Discharge line temperature 70 C Compressor discharge side superheat K dSH Discharge side superheat 28K De ice sensor temperature l...

Страница 9: ...e display shows the message Hi dSH when protection is active 6 Low discharge superheat protection Discharge superheat is defined as the difference between the compressor discharge gas temperature and...

Страница 10: ...trol then the controller will no longer allow the unit to be unlocked by the method described The controller display will show the message Lockout If this has happened the following steps must be take...

Страница 11: ...l through list Heat Cycle Low Pressure SLP kPa Entering Water temperature in C Evaporating temperature Et C Leaving Water temperature 35 55 max default 45 out C Suction Line temperature SLt C Water Fl...

Страница 12: ...ydney Australian Head Office and Manufacturing Wellington Christchurch Brisbane Melbourne Adelaide Singapore Shanghai Perth Hobart Newcastle Singapore Shanghai Beijing Jakarta Hong Kong Sri Lanka Maur...

Отзывы: