background image

- 10 -

lock-out condition.
A unit that is locked out can be unlocked using any 

one of the following methods:

• Remove mains power from the unit for at least  

3 seconds, then restore power.

• Issue an ‘unlock’ command via Modbus RTU serial 

communications.

• Reset the controller via Modbus RTU serial 

communications.

If a unit has locked out and has been unlocked twice,

then locks out for a third time without having

managed at least once to stop once under normal

control, then the controller will no longer allow the

unit to be unlocked by the method described.

The controller display will show the message

"Lockout".

If this has happened the following steps must be

taken to unlock the unit:

i)  Remove power, then restore power.
ii)  Press push button SW3 on the controller.
iii)  Start the unit heating as normal.
iv)  Stop the unit by means of a normal off-command

    (e.g. via the thermostat, remote on/off signal or

    Modbus control).

Ensure the unit does not stop on yet another trip by 

identifying and remedying the cause of the fault.
Refer to Temperzone (page 6) if assistance is 

required.

A

P

P

E

ND

IX

 I

I –

 P

R

O

T

E

C

T

IO

N

 F

U

NC

T

IO

N

S

Содержание MWH 2000

Страница 1: ...unit or connections will not result in damage to the area adjacent to the appliance or to lower floors of the structure When such locations cannot be avoided it is recommended that a suitable drain pa...

Страница 2: ...heat the joints and cause restricted flow Restricted flow rates may result in over pressure HP faults occurring Use water treatment when connecting to steel piping one that prevents internal corrosion...

Страница 3: ...es it eg long pipe systems and or multiple small fan coil units or radiators Note Higher LWT will reduce the efficiency of the unit To adjust the supply water temperature refer Commissioning 4 3 MWR o...

Страница 4: ...s On and the entering water temperature EWT is greater than 5 C below the target set temperature default 45 C and the outdoor ambient temperature is above 15 C Stop Mode The remote On Off switch is Of...

Страница 5: ...e on holiday The labels should be fixed adjacent to the heat pump outdoor power point and on the main fuse switchboard of the building Advise the building occupier Note The addition of glycol to the w...

Страница 6: ...ort Note Cold water in the system is more likely to result in air locks than warm water Once the water heats the air will tend to be naturally removed through the automatic air bleed Cooler water abso...

Страница 7: ...e each connected UC8 controller has a unique Modbus device address Refer to section 5 4 for the procedure Example For detailed information about monitoring and control via Modbus RTU refer to document...

Страница 8: ...ndensing temperature 42 C Compressor discharge line temperature C dLt Discharge line temperature 70 C Compressor discharge side superheat K dSH Discharge side superheat 28K De ice sensor temperature l...

Страница 9: ...e display shows the message Hi dSH when protection is active 6 Low discharge superheat protection Discharge superheat is defined as the difference between the compressor discharge gas temperature and...

Страница 10: ...trol then the controller will no longer allow the unit to be unlocked by the method described The controller display will show the message Lockout If this has happened the following steps must be take...

Страница 11: ...l through list Heat Cycle Low Pressure SLP kPa Entering Water temperature in C Evaporating temperature Et C Leaving Water temperature 35 55 max default 45 out C Suction Line temperature SLt C Water Fl...

Страница 12: ...ydney Australian Head Office and Manufacturing Wellington Christchurch Brisbane Melbourne Adelaide Singapore Shanghai Perth Hobart Newcastle Singapore Shanghai Beijing Jakarta Hong Kong Sri Lanka Maur...

Отзывы: