background image

Heat Pump Water/Space Heaters

MWH/MWR models (c/w UC8) R32

Installation & Maintenance

CONTENTS

 Page

1. General ................................................................ 1

2.  Installation............................................................ 1

3. Wiring.................................................................. 2

4. Commissioning................................................... 4

5. Controls............................................................... 4

6. Maintenance....................................................... 5

7. Troubleshooting.................................................. 6

8. Warranty............................................................  6

Table 1:  UC8 Display Information........................ 8

Appendix I :  BMS Control Option.......................  8

Appendix II :  Protection Functions....................... 9

Commissioning Sheet .......................................... 11
Other Relevant Documents:

- MWH/MWR Applications Manual

- Specifications Sheet (model specific)

- R32 Handling : Water Heating Units

- MWH 900 LAT Control User Guide. 

1. GENERAL

1.1  Introduction

Follow these instructions to ensure the optimum 

performance, reliability and durability.
Units must be installed in accordance with all national and 

regional regulations and bylaws.

National Health and Safety regulations must be followed 

to avoid personal injuries.
The appropriate permits must be acquired and adhered to.
Seismic restraints must be fitted if required (refer NZS 

4104:1994, AS 1170.4).
The accompanying 'R32 Handling' pamphlet forms part of 

these Installation & Maintenance instructions.

!

 WARNING. 

These units use R32 refrigerant (Class A2L) which is 

mildly flammable.
The unit shall be installed, operated and stored in a 

adequately ventilated space (eg outdoors) where there is 

no continuously operating open flames (eg an operating 

gas appliance) or other R32 ignition source. If the 

refrigerant gas comes into contact with fire, a poisonous 

gas may occur. Be aware that R32 does not contain an 

odour.

1.2  Site Preparation

System designers and installers must first familiarise 

themselves with the contents of the MWH/MWR 

Applications Manual prior to installing any unit. This 

contains important information about site requirements 

that will ensure the unit performs effectively and to 

its design capabilities, eg expansion tank, water loop 

pressure system. 

2. INSTALLATION

2.1 Positioning

WARNING

The appliance should be located in an area where 

leakage of the unit or connections will not result in 

damage to the area adjacent to the appliance or to lower 

floors of the structure. When such locations cannot be 

avoided, it is recommended that a suitable drain pan, 

adequately drained, be installed under the appliance.

WARNING

Keep appliance area clear and free from combustible 

materials, gasoline and other flammable vapours and 

liquids. 
MWH/MWR units are designed to be located outdoors* 

and as close to the space heating area as acoustic 

criteria allows.

If the unit is located indoors, ensure adequate ventilation is 

provided to maintain the internal air temperature no lower 

than 5°C below the external ambient air temperature. It is 

possible to duct the discharge air from the unit, however the 

max. external static pressure is limited (refer Spec. Sheet). 

It is recommended that an additional in-line fan be installed to 

maintain airflow through the unit.

Refer to diagram (Figure 1) and supplied Specifications 

sheet for minimum clearances. If multiple units are to be 

placed side-by-side then allow at least 1m between coil 

faces.

When determining the position of the unit, allow adequate 

space around the unit to facilitate water pipe connections, 

future servicing and maintenance. Ensure there is enough 

working space in front of the electrical access panel. 
Note: The discharge air from the unit is very cold when 

the unit operates at full capacity, and may be well below 

the freezing temperature. Take care in selecting the 

installation position that the discharge air from the unit is 

not under a window or plants that are cold sensitive. It is 

also possible to get increased condensation on surfaces 

above the unit discharge air which may deteriorate some 

surfaces. Avoid installations where ponding of chilled air 

is likely to occur. Choose a well-ventilated location.

Consideration should be given to the piping route to the 

Room fan coil unit/s as well as power and control cabling.

Refer Specification Sheet for maximum separation limits 

between MWH units and connected heat exchangers. 

003-000-172  

06

/22

GENERAL

INST

ALLA

TION

PRELIMINAR

Y

Содержание MWH 2000

Страница 1: ...unit or connections will not result in damage to the area adjacent to the appliance or to lower floors of the structure When such locations cannot be avoided it is recommended that a suitable drain pa...

Страница 2: ...heat the joints and cause restricted flow Restricted flow rates may result in over pressure HP faults occurring Use water treatment when connecting to steel piping one that prevents internal corrosion...

Страница 3: ...es it eg long pipe systems and or multiple small fan coil units or radiators Note Higher LWT will reduce the efficiency of the unit To adjust the supply water temperature refer Commissioning 4 3 MWR o...

Страница 4: ...s On and the entering water temperature EWT is greater than 5 C below the target set temperature default 45 C and the outdoor ambient temperature is above 15 C Stop Mode The remote On Off switch is Of...

Страница 5: ...e on holiday The labels should be fixed adjacent to the heat pump outdoor power point and on the main fuse switchboard of the building Advise the building occupier Note The addition of glycol to the w...

Страница 6: ...ort Note Cold water in the system is more likely to result in air locks than warm water Once the water heats the air will tend to be naturally removed through the automatic air bleed Cooler water abso...

Страница 7: ...e each connected UC8 controller has a unique Modbus device address Refer to section 5 4 for the procedure Example For detailed information about monitoring and control via Modbus RTU refer to document...

Страница 8: ...ndensing temperature 42 C Compressor discharge line temperature C dLt Discharge line temperature 70 C Compressor discharge side superheat K dSH Discharge side superheat 28K De ice sensor temperature l...

Страница 9: ...e display shows the message Hi dSH when protection is active 6 Low discharge superheat protection Discharge superheat is defined as the difference between the compressor discharge gas temperature and...

Страница 10: ...trol then the controller will no longer allow the unit to be unlocked by the method described The controller display will show the message Lockout If this has happened the following steps must be take...

Страница 11: ...l through list Heat Cycle Low Pressure SLP kPa Entering Water temperature in C Evaporating temperature Et C Leaving Water temperature 35 55 max default 45 out C Suction Line temperature SLt C Water Fl...

Страница 12: ...ydney Australian Head Office and Manufacturing Wellington Christchurch Brisbane Melbourne Adelaide Singapore Shanghai Perth Hobart Newcastle Singapore Shanghai Beijing Jakarta Hong Kong Sri Lanka Maur...

Отзывы: