background image

- 6 -

6.  TROUBLESHOOTING

6.1  Room temperature varies significantly from its 

setting

•  Unit may have been incorrectly sized for the load, 

or the external water system is limiting the unit's 

performance.

•  Unit may be in a protection or diagnostic failure 

mode (refer 6.6 below).

6.2  Unit does not seem to deliver the heating when 

most needed

•  Heating capacity at design conditions may be 

incorrect. As the outside temperature falls, heat 

losses through the walls, floor and ceiling increase.

•  Check the unit’s brochure for information on the 

minimum/ maximum operating temperatures.

•  Check the supply water temperature is appropriate 

for the installation (refer MWH Applications Manual)

6.3  In a new building, why does it take some days 

before the heat pump unit seems to work properly?

•  Many new buildings have a large amount of 

concrete and other structural materials that are 

generally cold and full of moisture. This is most 

evident in the winter when trying to heat the building 

from scratch.

•  Allow sufficient amount of time for unit to heat the 

floor. This could be up to 60 hours. Start heating well 

before you need the warmth most.

•  Units need to be checked regularly to ensure proper 

operation and that they are not exceeding operating 

limits for any length of time.

6.4  Unit runs excessively – the temperature remains 

too cold in winter. 

•  Windows or doors may be opened to non-heated 

areas.

•  Keep doors to unheated areas (eg laundries, 

bathrooms etc.) closed. 

•  Location of wall controller or remote temperature 

sensor is wrong.

• Check top air discharge is unblocked and air flow to 

the coil face is clear and not restricted or blocked.

• Check no ice is forming on the coil between de-ice 

cycles (Refer 7.10).

6.5  Unit stopped and displaying 'HP' fault code 

The most likely reason is insufficient purging of air 

through the system. Repeat the above steps to purge 

air from the system (Refer 4.1). Should this unit again 

result in a HP fault, then keep the hose connected on 

unit start-up, and open the purge port with the internal 

passage closed (filling port) / partially disconnect the 

return water pipe, and close the return side ball valve. 

The unit should operate. Once the unit is operating 

normally, then close the internal passage and purge port.

  Note: Cold water in the system is more likely to result 

in air-locks than warm water. Once the water heats 

the air will tend to be naturally removed through the 

automatic air-bleed. Cooler water absorbs air, and 

heating water will release it. Installing the air-bleed on 

the supply water side of the manifold allows the air 

to be removed prior to the water entering the plastic 

tubing. It is normal for the system pressure to reduce 

over several days as the remaining air is eliminated 

from the system. Return to site, and re-pressurize, 

ensuring that the water hose is free of air prior to 

connecting to the filling port. 

6.6  Unit displays an error code: 

  Refer to UC8 Controller label on the unit for 

operation & fault diagnostics information; or 

visit www.temperzone.biz and model search 

'UC8 Controller'. Here you will also find a 'UC8 

Troubleshooting Guide'.

6.7  Unit Does Not Start

• Circuit breaker may have been tripped. Reset circuit 

breaker.

• Unit may be off or in wall thermostat mode. Check 

unit is switched on at the unit, and external 

temperature controller is in Heating mode.

• Unit may be in a protection or diagnostic failure 

mode. Check for fault code display on unit's 

controller board (refer also 6.5).

6.8  Water Dripping Outside

Condensation released during unit operation is normal. 

The unit should have been drain connected at the time 

of installation (refer 2.3)

• Check drain line is unblocked.

• If a condensate drain has been installed and is 

connected to a drain system, check gaskets and 

fittings around drain for leaks and plugs.

6.9  Ice or Frost Forms On Unit's Coil

  Under normal operation in cold conditions the coil 

will at times change to a white appearance as a 

frost forms. The unit is programmed to de-ice no 

more frequently than once every 50 min. At the end 

of each de-ice cycle, the coil should be completely 

clear of ice. Should a layer of clear ice form on 

the coil, then contact your Installer or Temperzone 

Customer Service (www.temperzone.biz).

8  WARRANTY

Please refer to the separate warranty document supplied with the unit, or visit 

www.temperzone.biz

 for details.

 

Australia: 

New Zealand:

[email protected] 

nztechnical [email protected]

[email protected] 

Telephone: 0800 TZWARRANTY (899 2777)

Telephone: 1800 21 1800

NOTE  Specifications are subject to change without notice due to the manufacturer's ongoing research and development programme.

W

A

R

R

A

N

T

Y

T

R

O

UB

L

E

S

H

OO

T

IN

G

Содержание MWH 2000

Страница 1: ...unit or connections will not result in damage to the area adjacent to the appliance or to lower floors of the structure When such locations cannot be avoided it is recommended that a suitable drain pa...

Страница 2: ...heat the joints and cause restricted flow Restricted flow rates may result in over pressure HP faults occurring Use water treatment when connecting to steel piping one that prevents internal corrosion...

Страница 3: ...es it eg long pipe systems and or multiple small fan coil units or radiators Note Higher LWT will reduce the efficiency of the unit To adjust the supply water temperature refer Commissioning 4 3 MWR o...

Страница 4: ...s On and the entering water temperature EWT is greater than 5 C below the target set temperature default 45 C and the outdoor ambient temperature is above 15 C Stop Mode The remote On Off switch is Of...

Страница 5: ...e on holiday The labels should be fixed adjacent to the heat pump outdoor power point and on the main fuse switchboard of the building Advise the building occupier Note The addition of glycol to the w...

Страница 6: ...ort Note Cold water in the system is more likely to result in air locks than warm water Once the water heats the air will tend to be naturally removed through the automatic air bleed Cooler water abso...

Страница 7: ...e each connected UC8 controller has a unique Modbus device address Refer to section 5 4 for the procedure Example For detailed information about monitoring and control via Modbus RTU refer to document...

Страница 8: ...ndensing temperature 42 C Compressor discharge line temperature C dLt Discharge line temperature 70 C Compressor discharge side superheat K dSH Discharge side superheat 28K De ice sensor temperature l...

Страница 9: ...e display shows the message Hi dSH when protection is active 6 Low discharge superheat protection Discharge superheat is defined as the difference between the compressor discharge gas temperature and...

Страница 10: ...trol then the controller will no longer allow the unit to be unlocked by the method described The controller display will show the message Lockout If this has happened the following steps must be take...

Страница 11: ...l through list Heat Cycle Low Pressure SLP kPa Entering Water temperature in C Evaporating temperature Et C Leaving Water temperature 35 55 max default 45 out C Suction Line temperature SLt C Water Fl...

Страница 12: ...ydney Australian Head Office and Manufacturing Wellington Christchurch Brisbane Melbourne Adelaide Singapore Shanghai Perth Hobart Newcastle Singapore Shanghai Beijing Jakarta Hong Kong Sri Lanka Maur...

Отзывы: