Protection against over currents, short circuits and earth faults an additional two-pole
disconnect device shall be provided as a part of building installation. This protection device shall have
adequate breaking capacity to interrupt the maximum fault current, which can flow and shall have a
contact separation of at least 3 mm.
Turn off two-pole automatic disconnect device in order to simultaneously disconnect the
equipment and all with it associated equipment.