ADR-7000 / SAVER-7000 / GUARD-7
© 2017
– Telefire Fire & Gas Detectors Ltd
Revision 0.98 October 2017
– Page 58 of 87 –
8.9.12 Remote Displays
This menu configures the RM-7000 remote anunciators. You can select whether each of
the 16 RM-7000 is active or not; Class A or Class B wiring; and assign a 19 character
description to each RM-7000.
Screen 57 System configuration
– remote displays
8.9.13 COM Ports
This menu allows you to select the operation mode of COM1, COM2, and COM5 as
inactive, active an PC communication or NET-7000 TCP/IP interface; whether the
communication is supervised or not; and Baud rate.
COM3 and COM4 are used as RM-7000 connections and can't be configured other than
Class B or Class A operation (see above).
Screen 58 System configuration
– com ports
8.9.14 LON Card
This menu allows the configuration of the LON-7000 port.
Screen 59 System configuration
– LON cards
8.9.15 Loop Expansion Card
This menu allows you to configure whether an ADR-7022 SLC Expansion Module (for
loops 5
– 8) is installed.