Replacing the complete detector
If the operator needs to replace the complete detector, the easiest way is to take off the main
housing from the base of the detector (for more details, refer to § 4.2.1).
As the base of the detector remains in place, cable glands do not need to be dismantled. If
the detector is not replaced immediately, the “open” base must be protected against
humidity, dust and shocks
No intervention should be carried out when the detector is powered.