CP030 Current Probe
14
922173-00 Rev A
Specifications
Nominal Characteristics
Nominal characteristics describe parameters and attributes which are guaranteed by design, but do not
have associated tolerances.
Maximum Continuous Input Current
30 A
rms
(Refer to Figure 3)
Maximum Peak Current
50 A
peak
, noncontinuous
Insertion Impedance
Refer to Figure 4
Intended Output Load
1 MΩ
Maximum Permitted Circuit Voltage
300 V, CAT I (Insulated conductor)
Warranted Characteristics
Warranted characteristics describe parameters which have guaranteed performance. Unless otherwise
noted, tests are provided in the Performance Verification Procedure for all warranted specifications.
Guaranteed at 23 °C ±5 °C (73 °F ±9 °F) after power has been applied for 30 minutes.
Amplitude Accuracy
±1.0% of reading ±10 mA; to 30 A
rms
±2.0% of reading; to 50 A
peak
(DC, 45 to 65 Hz)
Typical Characteristics
Typical characteristics describe parameters which do not have guaranteed performance; however are
representative of the average performance from a sample of several probes. Tests for typical
characteristics are not provided in the Performance Verification procedure.
Sensitivity*
20 mA/div* to 50 A/div.
Output voltage
0.1 V/A
Sensitivity Temperature
±2% or less. (from 0° to +40 °C,
Coefficient
32 °F to 104 °F).
Noise
Equivalent to 2.5 mA rms or less
(BW of measuring instrument: 20 MHz)
Bandwidth
DC to 50 MHz
Rise Time ≤ 7 ns
* Lower sensitivity may change with different oscilloscope models.
www.calcert.com
1.888.610.7664
0
5
10
15
20
25
30