Subject to modifications and errors
Page 25 of 71
2019-06-26 edition
10 minutes average overvoltage
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.043
V 59.S1
U
THR
OFF
%Unom
110
100
120
100
135
.045
T 59.S1
Time OFF
Ms
0
0
0
0
10.000
U
THR
ON
% Unom
Fixed Hysteresis (4% U
THR
)
Overfrequency 1
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.055
F 81>S2 ws
f
THR
OFF
Hz
51,50
50,0
52,0
50,0
55,0
.057
T 81>S2 ws
Time OFF
Ms
1000
50
5.000
50
10.000
f
THR
ON
Hz
Fixed Hysteresis (0,2% f
THR
)
Only active for:
Operational Mode 0 (definitive mode) when DigIn4 is inactive (contact open)
Voltage > 20% Unom
Underfrequency1
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.059
F 81<S2 ws
f
THR
OFF
Hz
47,50
47,0
50,0
45,0
50,0
.061
T 81<S2 ws
Time OFF
Ms
4000
50
5.000
50
10.000
f
THR
ON
Hz
Fixed Hysteresis (0,2% f
THR
)
Only ctive for:
Operational Mode 0 (definitive mode) when DigIn4 is inactive (contact open)
Voltage > 20% Unom
Overfrequency2
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.063
F 81>S1 nf
f
THR
OFF
Hz
50,50
50,0
52,0
50,0
55,0
.065
T 81>S1 nf
Time OFF
Ms
100
50
5.000
50
10.000
f
THR
ON
Hz
Fixed Hysteresis (0,2% f
THR
)
Only active for:
Operational Mode 0 (definitive mode) when DigIn 4 is active
Operational Mode 1 (transitoty mode) when DigIn 5 is active
Voltage > 20% Unom
Underfrequency2
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.067
F 81<S1 nf
f
THR
OFF
Hz
49,50
47,0
50,0
45,0
50,0
.069
T 81<S1 nf
Time OFF
Ms
100
50
5.000
50
10.000
f
THR
ON
Hz
Fixed Hysteresis (0,2% f
THR
)
Only active for:
Operational Mode 0 (definitive mode) when DigIn 4 is active
Operational Mode 1 (transitoty mode) when DigIn 5 is active
Voltage > 20% Unom
Overfrequency3
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.071
F 81>S2 wf
f
THR
OFF
Hz
51,50
50,0
52,0
50,0
55,0
.073
T 81>S2 wf
Time OFF
Ms
100
50
5.000
50
10.000
f
THR
ON
Hz
Fixed Hysteresis (0,2% f
THR
)
Only active for:
Operational Mode 1 (transitory mode) when DigIn 5 is inactive
Voltage > 20% Unom
Underfrequency3
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.075
F 81<S2 wf
f
THR
OFF
Hz
47,50
47,0
50,0
45,0
50,0
.077
T 81<S2 wf
Time OFF
Ms
100
50
5.000
50
10.000
f
THR
ON
Hz
Fixed Hysteresis (0,2% f
THR
)
Only active for:
Operational Mode 1 (transitory mode) when DigIn 5 is inactive
Voltage > 20% Unom