Subject to modifications and errors
Page 57 of 71
2019-06-26 edition
3.7.16
OPEN SETUP
Connection Mode
Conformity Range
Possible Range
ID
Default
.003
Connection
4-wire (LN)
2-wire, 3-wire, 4-wire (LN),
4-wire (LN+LL))
2-wire, 3-wire, 4-wire (LN),
4-wire (LN+LL)
Nominal Voltage
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.005
ULN/LL nom
Unom Y
Unom Δ
V
V
230.0
400.0
28.8
50.0
250.0
434.8
28.8
50.0
250.0
434.8
Functional Safety
Conformity Range
Possible Range
ID
Default
.007
Errtol
2ch
1ch, 2ch
1ch, 2ch
Remark:
2ch means: 2 channel with functional safety and 2 auxiliary contacts necessary
1ch means: 1 channel without functional safety and 1 auxiliary contact1 necessary
Overvoltage1 Line to Line
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.010
ULL>1
Enable function
on
on / off
on /off
.011
ULL>1 OFF
U
THR
OFF
%Unom
110
0
180
0
180
.012
ULL>1 ON
U
THR
ON
%Unom
109
0
180
0
180
.013
ULL>1 T
Time OFF
ms
200
50
300000
50
300000
Only active for:
Connection Modes: 3-wire, 4-wire (LN+LL)
Undervoltage1 Line to Line
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.014
ULL<1
Enable function
on
on / off
on /off
.015
ULL<1 OFF
U
THR
OFF
%Unom
90
0
180
0
180
.016
ULL<1 ON
U
THR
ON
%Unom
91
0
180
0
180
.017
ULL<1 T
Time OFF
ms
200
50
300000
50
300000
Only active for:
Connection Modes: 3-wire, 4-wire (LN+LL)
Overvoltage1 Line to Neutral
Conformity Range
Possible Range