4
Technical data
4.1
Supply circuit
Terminals
A1 (L or +); A2 (N or -)
Supply voltage
DC: 24V
AC: 110 - 230V
Tolerance of the supply voltage
DC: ± 10%
AC: ± 30%
Nominal consumption
max. 1,25W / 4VA @ 230V AC
Nominal frequency
50 / 60Hz
Tolerance of the nominal frequency
48 - 63Hz
Duration of operation
100%
Recovery time
6 s set turn-on delay
Drop-out voltage
7V
Overvoltage category
III
Rated surge voltage
6 kV
Internal fusing
250V / 500mA slow blow
To ensure the device's functionality during a power failure, the device is to be supplied via an external UPS
system!