Subject to modifications and errors
Page 56 of 71
2019-06-26 edition
ID
Default
Min
Max
Min
Max
.090
RoCoF
Enable Function
off
on / off
on / off
.091
RoCoF OFF
RoCoF
THR
OFF
mHz/s
1000
10
9990
10
9990
.092
RoCoF ON
RoCoF
THR
ON
mHz/s
950
10
9990
100
9990
.093
RoCoF T
Time OFF
ms
500
50
60000
50
60000
Comment:
Fixed window length 225ms
Phase Shift (PShift)
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.094
PShift
Enable Function
off
on / off
on / off
.095
PShift OFF
PShift
THR
OFF
°
7
2
20
2
20
.096
PShift ON
PShift
THR
ON
°
5
2
20
2
20
.097
PShift T
Time OFF
ms
0
0
60000
0
60000
Comment:
Fixed window length 200ms
Auxiliary Contact type
Conformity Range
Possible Range
ID
Default
.099
Contact
n.c. (normally closed)
n.o. (normally opened)
n.c. (normally closed)
n.o. (normally opened)
n.c. (normally closed)
dis. (disabled)
Turn on Delay
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.102
Ton delay
s
60
60
600
0
600
Random Turn on delay
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.103
Ton random
Enable function
off
on … off
on … off
.104
Ton random
Turn on time
s
60
600
60
600
Comment:
The random time value is shown in .104 and cannot be edited
Device Information
ID
.105
ID: xxxxxx
SW: dd.aa.cc
xxxxx = Device ID
dd: Software version of Display Software
aa: Software version of Measuring Software
cc: Version of the Configuration set
Password
ID
Default
Min
Max
.106
PW1
1
st
digit of Password
0
0
9
.107
PW2
2
nd
digit of Password
0
0
9
.108
PW3
3
rd
digit of Password
0
0
9
.109
PW4
4
th
digit of Password
0
0
9
Remark:
If all 4 digits of the Password are 0 (default setting) the Password request is skipped