background image

Technology Solutions

T

CD  7801C

EK-

L

Instruction Manual

NEMA 4X Panel Mount Multi-Channel Controller  

Document Number: IM-7801C

www.tek-trol.com

Содержание TEK-LCD 7801C Series

Страница 1: ...Technology Solutions T CD 7801C EK L Instruction Manual NEMA 4X Panel Mount Multi Channel Controller Document Number IM 7801C www tek trol com...

Страница 2: ...contact Customer Support 796 Tek Drive Crystal Lake IL 60014 USA Tel 1 847 857 6076 www tek trol com No part of this publication may be copied or distributed transmitted transcribed stored in a retri...

Страница 3: ...Momentary Pushbutton 15 2 5 3 7801C SH Sun Hood 16 2 5 4 7801C 2360 Control Stations 16 2 5 5 Signal Splitter Conditioner Accessories 16 2 5 6 Split Core AC Current Transducer 16 2 5 7 Panel Mount Bu...

Страница 4: ...11 Delete Channel 42 6 12 2 Point Linear Scaling 42 6 13 Square Root Scaling 43 6 14 Scale Exponent 43 6 15 Round Horizontal Tank 44 6 16 Open Channel Flow Application 44 6 16 1 Programmable Exponent...

Страница 5: ...t 69 6 53 Setup Modbus Output Spoofer 70 6 54 Setup Screens 71 6 54 1 Screens Settings 71 6 55 Setup Function Keys 72 6 56 Setup System 72 6 56 1 Setup Display 73 6 56 2 Setup Colours 73 6 57 General...

Страница 6: ...9 1 View Alert Messages 94 8 10 View Digital Outputs 95 8 11 View Modbus Outputs 95 8 12 View Screens 95 9 Operation 97 9 1 Viewing Screens 97 9 1 1 Individual Channel View 97 10 Modbus RTU ASCII Ser...

Страница 7: ...r the consequences of misuse by the operator Wrong installation or operation of the devices systems will cause the warranty to be void The respective Terms and Conditions of Sale which forms the basis...

Страница 8: ...ts against the packing list provided 1 5 2 Transportation Avoid impact shocks to the device and prevent it from getting wet during transportation Verify local safety regulations directives and company...

Страница 9: ...digital outputs Modbus RTU ASCII Modbus Enron and Ethernet Modbus TCP IP protocol communication capabilities Additionally the controller is equipped with up to 32 timers that can be used to control m...

Страница 10: ...Rate User selectable 0 1 to 0 5 sec 10 updates sec to 2 updates sec Programming Method Front panel buttons external buttons Number of Alarms Up to 64 high or low logic AND OR Automatic non latching or...

Страница 11: ...LCD turns on at 0 C delivering the minimum power If the temperature drops below 10 C the heater delivers its maximum power Connections Removable screw terminal blocks Inputs Outputs 12 to 24 AWG wire...

Страница 12: ...xpected maximum total Date Format Month day year Time Format 24 hour 00 Midnight hh mm ss Battery 3 V P N CR2032 included Display Date Time Displayed on the top line of Setup and View menus including...

Страница 13: ...Flow Scale Factor Round Horizontal Tank Volume Units Conversion mA Input Reading Percent bar graph Text Percent Channel Input Live Calibration Each channel can be calibrated using live calibration si...

Страница 14: ...tek trol com Technology Solutions 12 2 3 Dimensional Drawings Fig 2 Front Panel Mount Fig 3 Panel Cutout Fig 4 Mounting Panel 10 3 4 276mm 10 3 4 276mm 6 1 4 157mm 61 4 157mm 10 1 4 254mm 10 1 4 254m...

Страница 15: ...20RY 0 12 0 20 7801C GP 12AI 10AO 10RY 0 12 10 10 7801C GP 16AI 0 16 0 0 7801C GP 16AI 15RY 0 16 0 15 7801C GP 16AI 15AO 0 16 15 0 7801C GP 20AI 0 20 0 0 7801C GP 20AI 10RY 0 20 0 10 7801C GP 20AI 10A...

Страница 16: ...troller Calibration and Certificate for up to 36 Inputs and Outputs 7801C 12 DATA NEMA 4X Panel Mount Multi Channel Controller Calibration and Certificate with data for up to 12 Inputs and Outputs 780...

Страница 17: ...Drilled in Enclosure 1 7801C LH5CB1 Light Horn with User Choice of Red Green Yellow Blue or White Light Button and Holes Drilled in Enclosure 1 7801C LH3LCB1 RYG Light Horn with Red Yellow Green Ligh...

Страница 18: ...op Button 7801C2361 A 1 Black Ack Button 7801C2361 Q 1 Black Silence Button Model Description 7801C 1MA 1MA Signal Isolator with One 4 20 mA Input and One 4 20 mA Output 7801C 1MA 2MA Signal Splitter...

Страница 19: ...available in painted steel and plastic and come pre cut with one cutout to mount the Tek LCD 7801C The enclosures are available in various sizes with the larger enclosures capable of housing other pie...

Страница 20: ...ts authorized to perform such works CAUTION When removing the instrument from hazardous processes avoid direct contact with the fluid and the meter All installation must comply with local installation...

Страница 21: ...ll line voltage connections Observe all safety regulations Electrical wiring should be performed in accordance with all applicable national state and local codes to prevent damage to the meter and ens...

Страница 22: ...e controller will run on DC power Note 1 Each 4 20mA input has its own isolated 24VDC power supply to power the transmitter 2 Each 4 20mA output has its own isolated 24VDC power supply to power the ou...

Страница 23: ...mA Analog Input Connections Analog 4 20 Input connections are made to screw terminal connectors two inputs per connector The following figures show examples for typical applications Each of the 4 20m...

Страница 24: ...the digital inputs Normally open switch contacts can be used as shown in Figure 12 The diagram also shows a Digital Input using an NPN open collector transistor output from a live signal Logic LO or...

Страница 25: ...cting the positive voltage to the Ex terminal Fig 13 Active 4 20 mA Output Powered by Controller Fig 14 Passive 4 20 mA Output Powered by External Supply 4 2 8 Digital Output Connections The digital o...

Страница 26: ...rnal suppressors snubbers is strongly recommended when switching inductive loads to prevent disrupting the microprocessor s operation The suppressors also prolong the life of the relay contacts Suppre...

Страница 27: ...nces up to 4000 feet can be reached with RS 485 Up to 32 Modbus devices can be connected to a single RS 485 bus Fig 21 Serial Connections 4 2 14 Ethernet Option The Ethernet port is available on the R...

Страница 28: ...t version of the Tek LCD 7801C configuration software from our website predig com software or from the included CD 2 Extract the contents of the Tek LCD 7801C_Installer zip file into a folder in your...

Страница 29: ...rol com Technology Solutions 27 5 The User Account Control message is displayed Click Yes to proceed with the installation 6 The installation progress is displayed 7 Read and accept the End User Licen...

Страница 30: ...ek LCD 7801C icon will be placed on your desktop 10 You are now ready to start using the software to configure your TEK LCD 7801C Controller WARNING Only one controller can be connected at a time Atta...

Страница 31: ...sh creating a new configuration 6 Click on File to save files open existing files or to create a new configuration even without a controller connected 6 Setup and Programming 6 1 Navigation and Editin...

Страница 32: ...ic scan Scan Scan screens automatically Ack Acknowledge alarms relays Reset Reset total max min Setup Enter the Setup menu Edit Modify selection Enter Execute keypad entry Ok Accept setting change Sav...

Страница 33: ...ignal connections have been completed and verified apply power to the instrument Inputs outputs channels and relays are configured individually It is recommended that all inputs be configured before c...

Страница 34: ...menu is the starting point during the programming process Setup menu setting up Channels Totals Timers Alarms Inputs Outputs Screens and System settings The number of channels shown on this screen is...

Страница 35: ...nge Filter Window Average IIR First Order Cutoff Limits Round Hysteresis Delay Pulse Filter See Channel Math Functions on page 15 for details Control Sampler On Off Control w Randomizer Select A or B...

Страница 36: ...n background indicates the field to be edited Press Edit key again to change the channel s tag this opens the data entry keypad Use the Down Arrow key to navigate to the keypad Use the and keys to mov...

Страница 37: ...ons 35 To enter symbols press the three dots and select the desired symbol When done typing the characters in the selected field press the Enter key To enter numbers select the numeric keypad move the...

Страница 38: ...tup Channels menu is used to configure each channel enter a tag select the input source scale the input and program other settings that will determine the channel s processing capabilities Use the Arr...

Страница 39: ...nology Solutions 37 Press the Edit key to edit the channel tag and other settings Press the Up and Down arrow keys to select setting to be edited Select the function to be applied to the input and pre...

Страница 40: ...the engineering units decimal point enter scale points and press the Ok key Select number of decimals scale the input enter the cut off value select colours for bar graph and text confirm the bar grap...

Страница 41: ...s 39 Select a color pattern or press the Edit key to make changes to the colours tag text background and bar graph Use the arrow keys to navigate the settings and press Edit to make changes Press Edit...

Страница 42: ...hannel The Manage button is used to move or delete colours 6 9 Live Calibration The Live Calibration feature is used to calibrate a channel by applying a live calibration signal From the Setup menu na...

Страница 43: ...additional inputs to be calibrated Adjust the output values according to the calibrated inputs Press Save 6 10 Edit Channel To edit a channel press the Edit key and navigate to the setting you want t...

Страница 44: ...delete the channel or the Cancel key to cancel delete action 6 12 2 Point Linear Scaling Linear mode refers to basic 2 point scaling of a 4 20mA signal in engineering units The graph in figure 25 show...

Страница 45: ...eadings below a programmed value Below the cut off value the controller will display 0 Fig 26 Square Root Response Graph 6 14 Scale Exponent Exponent mode refers to 2 point scaling with programmable e...

Страница 46: ...z Tank from Function options Fig 28 Round Horizontal Tank Volume Graph 6 16 Open Channel Flow Application The Tek LCD 7801C in combination with a level transmitter makes for a practical way to measure...

Страница 47: ...ecific Weir or Flume Function In this method the user selects one of the following functions to be applied to the input from a menu in the Tek LCD 7801C Parshall Flumes V Notch Weirs Cipolletti Weirs...

Страница 48: ...ration 6 17 Setup Math Function There are many math functions that can be applied to any channel which allows the execution of simple or complex math functions Math channels can be the source for othe...

Страница 49: ...Flow Compare Measure Filter Control Relays and Modbus 6 18 Random Varying On Off Control The On Off Control with the Randomizer function is used to prevent grease build up in tank level control appli...

Страница 50: ...and the formula for calculating the flow rate using the head height The first thing to do is to create a channel for measuring the head height of the weir or flume This example shows the setup for a 3...

Страница 51: ...Instruction Manual Tek LCD 7801C www tek trol com Technology Solutions 49 6 20 Setup Totalizer Based on Flow Rate 6 21 Setup Screen to Monitor Open Channel Flow...

Страница 52: ...t available for it The pulse inputs can be either integrated from a rate channel or they can be directly totalized based on the pulse count and K Factor value this is the most accurate method because...

Страница 53: ...uts can be totalized directly without the need to create a rate channel Select the units and enter the K Factor provided by the flow meter manufacturer 6 25 Setup Accumulated Total Triggered Selecting...

Страница 54: ...ated The trigger can be a digital input a Modbus input or any event selected 6 26 Setup Previous Total The previous total is saved just before the input total is reset The date time when the total was...

Страница 55: ...every day at midnight The daily total can be the input to a previous total to save the previous day total Link previous daily totals to maintain a history of daily totals 6 28 Setup Grand Total The gr...

Страница 56: ...ng above a certain threshold or a digital input going from low to high Additional Inputs to control the timer mA Input Relay Output Pulse Input Digital Output Modbus Output 6 30 Timer Automatic Action...

Страница 57: ...rms they can be driven by a single channel multiple channels digital inputs time interval or a combination of other alarms into logic AND logic OR alarms Set and reset point values determine if it is...

Страница 58: ...Instruction Manual Tek LCD 7801C www tek trol com Technology Solutions 56 Automatic only Alarm resets automatically at the reset point...

Страница 59: ...m can be used as a summary alarm 6 33 Logic AND Alarm The inputs for the logic AND alarm are any existing alarm regardless of the source or type All alarms in the group must be active to trigger the A...

Страница 60: ...me Choose how long the alarm should stay on and if manual acknowledge is allowed 6 36 Setup Inputs The Setup Inputs screen is used to configure the hardware inputs assigning a user defined tag and set...

Страница 61: ...on unused inputs Note For more filtering If you need a more stable reading select IIR 16 sec or IIR32 sec setting 6 38 Setup Pulse Inputs The top line for each input shows the slot and input location...

Страница 62: ...input 6 39 1 Digital Input Functions A digital input can be used to execute one of the listed functions and at the same time it can be used to trigger an alarm or to totalize count how many times the...

Страница 63: ...n be written to other server devices using the Modbus output functions The Snooper mode can listen and read the process variables being transmitted on the RS 485 bus without causing any disruptions to...

Страница 64: ...nter Modbus Input tag o Mode Select Client o Server ID Enter the device ID to read from o Address Enter the register address to be read the register number is displayed next to the data type o Enron C...

Страница 65: ...her Modbus devices being polled by a Modbus Client The inputs can be used as the source for channels math functions alarms relay control etc o Enter Modbus Input tag o Mode Select Snooper o Server ID...

Страница 66: ...digital outputs Modbus Output Configure Modbus outputs 6 45 Setup 4 20 mA Outputs The mA output can be assigned to any analog input channel alarm or digital input It can be scaled to any input and ou...

Страница 67: ...when set is active o Break The relay state when break is detected o Fail Safe Relay energized under normal conditions o Relay Status Runtime hh mm ss Select the input source to drive the relay and en...

Страница 68: ...Select the input for alternation e g Ch 1 3 Enable alternation 4 Enable alternate on time and enter time 5 Enter the On Off alternation points according to the number of relays to alternate 6 Select r...

Страница 69: ...made up of a primary relay and any number of relays selected to alternate with it Multiple alternation groups can be setup using different sources for each group A relay should NOT be assigned to mor...

Страница 70: ...stem e g PV channels Totals Relay Runtime etc and selecting the desired data type from bit logic to float 64 The function code is 0x03 and the registers are base 1 e g Reg Address 4400 Reg Number 4440...

Страница 71: ...scaled combined with other variables using the math functions and the results can be written to another Tek LCD 7801C or any other Modbus server such as a digital panel meter The Modbus Output menu a...

Страница 72: ...ntroller must be configured as a Modbus Server Snooper in the System Modbus menu See page 67 for instructions on how to enable the Add On Features The Spoofer Modbus output is used to replace Modbus d...

Страница 73: ...screens that will be displayed during operation and to setup the actions assigned to the function keys F1 F4 6 54 1 Screens Settings Up to eight PVs and or alarms can be displayed per screen The scre...

Страница 74: ...Note The function keys F1 F4 can be customized according to the screen in view 6 55 Setup Function Keys The function keys are setup independently for each screen this allows the customization of the...

Страница 75: ...Settings menu is used to adjust the backlight brightness refresh rate and to enable or disable the display of commas for all numeric values 6 56 2 Setup Colours The Colours menu is used to select the...

Страница 76: ...Options Beeping Alarm Solid Warble Carousel 6 57 1 Add On Features The Add On Features can be enabled at the factory or they can be purchased and enabled by the user at any time A unique key code is...

Страница 77: ...user may enter a 4 digit password to protect the system from unintentional changes Password Protected Controller o The correct 4 digit password is required to make changes to the system o If the pass...

Страница 78: ...nu 6 60 System Build The Build menu provides the model number and it shows the I O cards installed with their location in the seven available slots If an I O card is removed permanently pressing the R...

Страница 79: ...e Rx Timeout is used for devices that are slow to respond such as wireless Modbus servers Modbus Write Protection Select Passcode and enter a Modbus passcode between 0 and 9999 to prevent unauthorized...

Страница 80: ...rnet Port Setup Dynamic Host Configuration Protocol DHCP is a network management protocol used to automate the process of configuring devices on IP networks thus allowing them to use any communication...

Страница 81: ...Go to the System menu Custom Units o Select New o Enter a label for the unit 8 characters max o Select the unit type or None o Select the base unit o Enter the conversion factor 6 66 1 Delete Custom U...

Страница 82: ...e Tek Trol DeviceInstaller it will search for XPort devices on the Local Area Network LAN and display their status 3 If no controller is found click on Options and select the type of connection being...

Страница 83: ...k trol com Technology Solutions 81 6 Click on Configuration Records to find these settings see the example above IP Address 192 168 5 32 Local TCP Port 10001 0x2711 7 Click on Web Configuration 8 Clic...

Страница 84: ...ection Below are some screenshot examples for Modbus TCP IP connection Note You may download a free trial copy of Modbus Poll from https www modbustools com 8 View Menu The View menu is used to view i...

Страница 85: ...o simulate the selected parameter o Channel number and tag o PV and units o View the channel input source o View alarms associated with channel o View analog outputs assigned to channel o Simulate the...

Страница 86: ...simulate an alarm condition 8 4 View Totals The View Totals menu displays the value of all the totals and allows resetting each total individually o Total number and tag o Accumulated total and units...

Страница 87: ...l 1 Press the 3 Bar key to enter a new total reset the total or simulate a value for the total Totals not associated with a rate channel have additional features Add to or remove from the total Press...

Страница 88: ...menu displays the value of the existing timers Press the Right Arrow key to step into the details of the selected timer and view the associated inputs and outputs Press the Right Arrow key to step int...

Страница 89: ...ue using the keypad Press the Timer Control key shown in the timer details screen to access all timer control buttons 8 6 View Alarms The View Alarms menu displays the status of all the alarms and the...

Страница 90: ...ow key to view the alarm details Press the 3 Bar key to select Ack Alarm Reset Alarm change Set Points or Simulate Alarm condition Press the Set Point key to change the Set Points This re initializes...

Страница 91: ...ation states are not saved on power cycle On power up the controller initializes to the actual process conditions The View Inputs menu displays the values and status of all the inputs and the details...

Страница 92: ...2 details and the associated channels 8 7 1 Simulate mA Input Use the keys to ramp up and down or use the keypad to jump to any value within the range Press the Ok key to maintain the input in simulat...

Страница 93: ...ializes to the actual process conditions The View Outputs menu displays the values and status of all the outputs and the details of the associated channels o Output and tag o mA output value o Relay o...

Страница 94: ...ails Press the 3 Bar key to access Analog Output controls Manual control hold current value return to automatic 8 8 2 Manual Control of 4 20 mA Output Select Manual to control the analog output manual...

Страница 95: ...he F4 key can be used to turn on and off the selected relay momentarily Press the Right Arrow key to view the relay details o Relay and tag o Status o Runtime o Number of Cycles o Reset relay runtime...

Страница 96: ...1 View Alert Messages If Alerts are enabled for alarms the Menu key displays a flashing Alert message on red background Simulated parameters and manual control outputs automatically generate alert me...

Страница 97: ...1 View Modbus Outputs The View Modbus Outputs screen displays the Modbus outputs set up by the user it shows the register number and the parameter used to generate each output 8 12 View Screens With t...

Страница 98: ...l Tek LCD 7801C www tek trol com Technology Solutions 96 Press the Scan key to have all available screens continue to scan Press the Stop key to have all available screens stop scanning and stay on th...

Страница 99: ...rrow key to view the channels Select the channel of interest Navigate through the different items using the navigation keys A green bar indicates the selected item press the Right Arrow key to step in...

Страница 100: ...aph Indication The bar graph can be configured to show different colours depending on the value of the process variable The following example illustrates the use of colours Process Variable Bar Graph...

Страница 101: ...graph shows green below the first set point The bar graph changes to yellow above set point 1 The bar graph changes to orange above set point 2 The bar graph changes to red above set point 3 The pane...

Страница 102: ...le value into specified holding register 16 Write Multiple Registers Set multiple values into specified holding registers The multi channel controller can also work as a Modbus Display Controller by w...

Страница 103: ...40041 40056 40 55 Device Tag String 32 char 03 04 R Null terminating string Write 00 for the last char RTC Date Time 40061 60 Year Short 03 04 R 20 2020 40062 61 Month Short 03 04 R 40063 62 Day Shor...

Страница 104: ...ing with the software If you have programmed the controller with the front panel buttons and it is not working as intended try re programming it with the Tek LCD 7801C configuration software 11 1 Trou...

Страница 105: ...instrument does not respond at all Cycle the power to reboot the microprocessor Settings reprogrammed but instrument behavior remains as previously programmed Cycle the power to reboot the microproces...

Страница 106: ...s and solutions for process power and oil gas industries Tek Trol provides process measurement and control products for Flow Level Temperature Pressure Measurement ControlValves Analyzer systems We ar...