TFP-40x Series Conventional Fire Alarm Panels
TFP-40X INSTALLATION & OPERATION MANUAL
8
Table 4 LED Indicators
Label
LED name
Fixed LED
Blinking LED
Color
[V]
FIRE
NONE
Shows that the panel is in alarm
status (250 ms)
Red
[I]
General Error
Shows a system error
Shows there is a fault in the
system
Yellow
[J]
System Error
Shows a system error
NONE
Yellow
[K]
Supply Error
NONE
Shows there is a fault in the
power source or charging circuit
Yellow
[L]
Battery Error
NONE
Shows there is a fault in the
battery
Yellow
[M]
Earth Error
NONE
Shows there is a fault in the
earth connection
Yellow
[N]
Siren Status
Shows that the siren is
disabled
Shows there is a fault in the
siren
Yellow
[O]
Energy
Shows that the system is
supplied from any source
NONE
Green
[P]
System
Activated
Shows that there no problems
that can affect the full
operation of the system
NONE
Green
[R]
Test
Shows that one or more
zones are in test status
NONE
Yellow
[S]
Disable
Shows that the zones or the
siren are disabled
NONE
Yellow
[T]
Access Level
Level 3 active
Level 2 active
Yellow
[U]
Communication
NONE
Show that the system is
communicating with the
computer
Yellow
[A]
Zone fire
NONE
Shows that the zone is in fire
status
Red
[B]
Zone
Fault/Disable
/Test
Shows that the zone is
disabled or in test status
Shows there is a fault in the
zone
Yellow