TFP-40x Series Conventional Fire Alarm Panels
TFP-40X INSTALLATION & OPERATION MANUAL
11
6
User Levels
Some features of the panel are restricted with user levels and the panel has 4 user levels.
6.1
Level 1
Level 1 is defined as the predefined user level with the most basic features. When the key lock is off (key in
vertical position), Level-1 is entered. The authorizations of the Level 1 user are shown in the following list:
•
Indicators and Buzzer Test;
•
Buzzer muting,
•
Displaying disabled zones or sirens,
•
Displaying the zones being tested,
•
Detail fault display,
6.2
Level 2
Level 2 is the level that the authorized person with the system control authorization may enter using the key
provided with the panel. When the key lock is on (key in horizontal position), Level-2 is entered. The
authorizations of the Level 2 user are shown in the following list:
•
Level-1 authorizations,
•
Deactivating and activating zones/sirens,
•
Zone test,
•
Evacuation status creation,
•
Muting or reactivating sirens in an alarm situation,
•
Resetting alarm or fault statuses
To leave Level-2, turn the key into vertical position and remove it.
6.3
Level 3
All the authorizations and functions of the system can be performed at this level. The users of this system are
authorized persons who have received training on system installation and maintenance. To enter Level-3, first the
front cover of the panel should be removed and "Access Level-1 Activation Switch" shown in "9.3 Appendix-Level
/Figure 9 Level-3" should be brought to "ON" position.
The authorizations of the Level 3 user are shown in the following list:
To leave Level-3, turn the switch into the original position.
•
Level-2 authorizations,
•
Option to reactivate the sirens for every new fire situation,
•
Computer connection (to monitor panel data),
•
Hard Reset,
6.4
Level 4
Level-4 can be entered via a special apparatus provided by the manufacturer. At this level the user can change
the memory where the user program is located and the working data of the site.