Installation
This chapter describes the mechanical and electrical connection methods for TFP-40x series panels.
Caution: Do not start mounting before having read the entire manual!
5.1
Recommended Cables
It is recommended that cables with the properties described in "Table 5 Properties of the Recommended Cables"
are used with the cabling installations and in all the electrical connections.
Table 5 Properties of the Recommended Cables
Cable
Cable Property
Maximum
Supply
3 x 1,5mm²
N/A
Zone Lines
1x2x0,8+0,8JY(st)Y
1x2x1,5+1,5J-Y(st)Y
0
– 500 metre
500
– 1500 metre
Siren Lines
1x2x0,8+0,8JY(st)Y
1x2x1,5+1,5J-Y(st)Y
0
– 500 metre
500
– 1500 metre
5.2
Mounting
For mounting, one should select a clean and dry area, which is easily accessible by the user, where the panel is
not subjected to jolts and vibrations. The panel should be placed on a level surface at the eye level and it should
not be placed in another cabinet or someplace close to heat sources. There are cable inlets from the top and rear
for mounting convenience.
1
Loosen the A1 screws shown in "9.1 Appendix-Mechanical / Figure 2 Panel Front Cover Screws" with the
Allen key provided with the device.
2
Using the panel as the template, mark the wall from the A2 screw holes shown in "9.1 Appendix-Mechanical
/ Figure 3 Mounting Screw Holes".
3
Drill the holes marked on the wall and complete the fixing process with minimum 4-mm dowel and screws.
4
Then proceed to battery and cable connection processes.
5.3
Supply Input
The panel main supply input should be connected to the 195~250 VAC 50 Hz mains voltage and earth connection
must be made. It should be ensured that grounding resistance is less than 10 ohms. The main supply input fuse
of the panel must be 2A. Also, the panel supply cable must be of the type 3x1.5 NYM or 3x1.5 NYA. The electrical
connection should be made in accordance with the tag as shown in "9.1 Appendix-Mechanical / Figure 4 Electrical
Connections".
WARNING!
Do not remove or connect any connections when the system is energized.
WARNING!
This device should not be used without appropriate grounding
5.4
Battery Connection
The panel is supplied with 2 x 12V 7Ah sealed lead acid batteries and should be used with batteries of this kind.
For the battery mounting, the posts should be placed facing each other as shown in "9.1 Appendix-Mechanical /
Figure 5 Battery Connection" and the battery rails shown as B1 should be fixed tightly with screws.
For the battery mounting, the ends shown as B3 and B4 are connected to each other with battery jumper cable
as shown in "9.1 Appendix-Mechanical / Figure 5 Battery Connection" and the battery rails shown as B4 should be
fixed tightly with screws. Then the ends shown with B2 and B3 are connected to the battery supply socket with
battery supply cable.
System used the main supply as the primary power supply. Smart charging circuits are designed to keep batteries
always at full capacity.