Tekmar D 270 Скачать руководство пользователя страница 20

© 2010          D 270 - 08/10 

20 of 24 

Adjust 

Menu (2 of 2)

Display

Description

Range

Section

Installer

Ad

vanced

Actual

Setting

B3

Boiler Modulation 

Selects either a 2 to 10 V (dc) or a 

0 to 10 V (dc) output signal.

2:10, 0:10
Default = 0:10

B3

Minimum Modulation 

The minimum percent modulation 

of the burner.

0 to 50%
Default = 0%

B3

Maximum Modulation

 The maximum percent modulation 

of the burner.

50 to 100%
Default = 100%

E1
E2

DHW Mode

 Selects the DHW mode of operation.

1

 (parallel, no priority),

2

 (parallel, priority), 

3

 (pri-sec, no priority),

4

 (pri-sec, priority)

Default = 

1

DHW Exchange Occupied

 The minimum boiler supply 

temperature to the DHW heat exchanger during the 
Occupied period.

OFF, 100 to 220°F
(OFF, 38 to 104°C)
Default = 180°F (82°C)

DHW Exchange Unoccupied

 Selects whether or not a 

DHW demand will be responded to during the UnOccupied 
period.

OFF, On
Default = OFF

WWSD Occupied

 The system’s warm weather shut down 

temperature during the Occupied period.

35 to 100°F, OFF
(2 to 38°C, OFF)
Default = 70°F (21°C)

WWSD Unoccupied

 The system’s warm weather shut 

down temperature during the Unoccupied period.

35 to 100°F, OFF
(2 to 38°C, OFF)
Default = 60°F (16°C)

C1

Primary Pump Purge

 The maximum length of time that 

the primary pump will continue to operate after the boiler 
demand has been removed.

OFF, 0:10 to 19:55 min.
(5 second increments)

Default = 0:20 min 

C1

Boiler Pump Purge

 The length of time that the boiler 

pump will continue to run after the boiler demand is 
removed.

OFF, 0:10 to 19:55 min.
(5 second increments)

Default = 0:20 min 

The units of measure that all of the temperatures are to be 
displayed in by the control.

°F,°C
Default = °F

Содержание D 270

Страница 1: ...Indr UnO Boil Com Sw Boiler Control 270 One Modulating Boiler DHW Boiler Pmp P2 DHW Pmp Vlv H2039A Menu Item Boiler Demand DHW Demand Modulation DHW Priority Override Test o not testing red testing r...

Страница 2: ...sh buttons Menu Item for selecting and adjusting settings As you program your control record your settings in the ADJUST menu table which is found in the second half of this brochure Menu All of the i...

Страница 3: ...gs Burner Displays when Relay 1 is turned on Warning Displays when an error exists or when a limit has been reached Pump Displays when the primary or boiler pump is operating Lock Unlock Displays when...

Страница 4: ...m The supply water temperature is based on outdoor reset or a fixed temperature for DHW Outdoor Reset When a boiler demand signal from the heating system is present the control operates the boiler s t...

Страница 5: ...calculates a boiler target temperature that is below the Boiler Minimum setting the boiler target temperature is adjusted to at least the Boiler Minimum setting During this condition if the boiler is...

Страница 6: ...ut signal range of the 270 control The Minimum Modulation setting limits the control output range in order to match the boiler s input range To calculate the Minimum Modulation use the following formu...

Страница 7: ...residential cast iron boilers or steel tube boilers The Med Mass setting provides a moderate response to the heating system Hi 3 The Hi setting is selected if the boiler that is used has a high therm...

Страница 8: ...of time that the primary pump continues to run is adjustable using the Primary Pump Purge setting The primary pump continues to run until either the purging time has elapsed or the boiler supply temp...

Страница 9: ...ight periods INDOOR SENSOR With the indoor sensor connected the control is able to sense the actual room temperature Indoor temperature feedback fine tunes the supply water temperature in the heating...

Страница 10: ...on the WWSD pointer in the display When the control is in WWSD the Boiler Demand pointer is displayed if there is a boiler demand However the control does not operate the heating system to satisfy thi...

Страница 11: ...contact is opened until the heating system has recovered before returning to DHW operation This mode can be used if a DHW tank is piped in direct return and a DHW valve is installed DHW MODE 4 Extern...

Страница 12: ...heat from the boiler into the DHW tank The control continues this purge for a maximum of four minutes or until the boiler supply water temperature drops 20 F 11 C below the boiler target temperature d...

Страница 13: ...or Sensor 070 One Universal Sensor 082 Data Brochures D 270 D 070 D 001 Application Brochure A 270 Note Carefully read the details of the Sequence of Operation to ensure that you have chosen the prope...

Страница 14: ...power supply must be used to power both the DHW Demand and the Boiler Demand circuits since they both share the Com Dem terminal Output Connections Primary Pump Contact Prim P1 The Prim P1 output term...

Страница 15: ...When these two terminals are shorted together the control registers an unoccupied UNOCC signal Connection to Operate Modulating Boiler 11 12 Mod V dc V dc STEP FIVE TESTING THE WIRING General Each ter...

Страница 16: ...e wiring between the terminal block and pump and refer to any installation or troubleshooting information supplied with the pump If the pump operates properly disconnect the power and remove the jumpe...

Страница 17: ...oth with water and wring out prior to wiping control Do not use solvents or cleaning solutions DIP Switch Settings GENERAL The DIP switch settings on the control are very important and should be set t...

Страница 18: ...measured by the boiler supply sensor 22 to 266 F 30 to 130 C Boiler Target Boiler target temperature is the temperature the control is currently trying to maintain at the boiler supply sensor of the...

Страница 19: ...F 82 C B1 Boiler Minimum The minimum allowed boiler target temperature Check the boiler manufacturer s manual for a recommended setting OFF 80 to 180 F OFF 27 to 82 C Default 140 F 60 C B1 Boiler Maxi...

Страница 20: ...C Default 180 F 82 C DHW Exchange Unoccupied Selects whether or not a DHW demand will be responded to during the UnOccupied period OFF On Default OFF WWSD Occupied The system s warm weather shut down...

Страница 21: ...essed again to advance to the next step This can also be used to rapidly advance through the test sequence To reach the desired step repeatedly press and release the Test button until the appropriate...

Страница 22: ...ystem start up in order to purge air from the piping To enable the Max Heat feature use the following procedure 1 Press and hold the Test button for more than 3 seconds At this point the control flash...

Страница 23: ...to read the boiler supply sensor due to a short circuit The control will not operate the boiler until the sensor is repaired Locate and repair the problem as described in the Data Brochure D 070 To cl...

Страница 24: ...AND FITNESS FOR A PARTICULAR PURPOSE DURA BILITY OR DESCRIPTION OF THE PRODUCT ITS NON INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS AND ITS COMPLIANCE WITH OR NON VIOLATION OF ANY APPLICABLE EN...

Отзывы: