DHW MODE 2 OPERATION

On a call for DHW, the control provides DHW priority by shutting off the primary pump (

Prim

 

P1

) for a period of time. This time 

is based on the outdoor air temperature as described in the DHW Priority Override section. However, if the 

DHW

 

Demand

 is not 

satisfied within the allotted time, the boiler shuts off and the heat of the boiler is purged into the DHW tank.

Once the boiler supply temperature is sufficiently reduced, the 

DHW Pmp / Vlv

 contact shuts off. The heating system is turned on 

for a period of time to prevent the building from cooling off. After a period of heating, and if the 

DHW

 

Demand

 is still present, the 

control shuts off the heating system and provides heat to the DHW tank once again.

For correct operation, close attention must be paid to the mechanical layout of the system. When the control turns off the primary 
pump (

Prim

 

P1

), flow to the heating system must stop. If flow is not stopped, the temperature in the heating system can exceed the 

maximum desired temperature and can result in damage to the heating system.

DHW

Pump

Primary

Pump

Boiler

Pump

CONDITIONAL DHW PRIORITY

The Conditional DHW Priority Override applies to 

DHW MODE 2 

and Boiler Minimum is not set to OFF. If the boiler supply 

temperature is maintained at or above the required temperature during DHW generation, this indicates that the boiler has enough 
capacity for DHW and possibly heating as well. As long as the boiler supply temperature is maintained near its target, DHW and 
heating occurs simultaneously.

DHW POST PURGE

After the 

DHW Demand

 is removed, the control performs a purge on the boiler. The control shuts off the boiler and continues 

to operate either the DHW pump or the DHW valve and the system and boiler pump if applicable. This purges the residual heat 
from the boiler into the DHW tank. The control continues this purge for a maximum of four minutes or until the boiler supply water 
temperature drops 20°F (11°C) below the boiler target temperature during the DHW operation. The control also stops the purge if 
the boiler supply temperature drops below the current boiler target temperature.

DHW MIXING PURGE

After DHW operation, the boiler is extremely hot. At the same time, 
the heating zones may have cooled off considerably after being off for 
a period of time. To avoid thermally shocking the boiler after DHW in 
parallel with priority (

DHW MODE 2

), the control shuts off the boiler, but 

continues to operate the DHW pump while restarting the heating system. 
This allows some of the DHW return water to mix with the cool return 
water from the zones and temper the boiler return water.

DHW DURING UNOCCUPIED

When an external 

DHW Demand 

is present, the control can either continue operation of the DHW system as it would during the 

occupied period or the control can ignore a call for DHW as long as the control is in an unoccupied mode.

Section E2: DHW with Low Temperature Boilers

If DHW is to be incorporated into a low temperature system such as a 
radiant heating system, a mixing device is often installed to isolate the high 
DHW supply temperature from the lower system temperature. If a mixing 
device is not installed, high temperature water could be supplied to the 
low temperature system while trying to satisfy the DHW demand. This may 
result in damage to the low temperature heating system. The control is 
capable of providing DHW in such a system while maximizing the chance 
that the temperature in the heating system does not exceed its allowed 

Boiler Maximum 

setting.

To prevent high temperature water from being introduced into the heating 
system, the primary pump (

Prim

 

P1)

 must be turned off during a call for 

DHW. To do this, the control must be set to 

DHW MODE

 

2 or DHW

 

MODE

 

4

 

and 

Boil

 

MIN

 must be set to 

OFF

.

DHW

Pump

Primary

Pump

Boiler

Pump

Содержание D 270

Страница 1: ...Indr UnO Boil Com Sw Boiler Control 270 One Modulating Boiler DHW Boiler Pmp P2 DHW Pmp Vlv H2039A Menu Item Boiler Demand DHW Demand Modulation DHW Priority Override Test o not testing red testing r...

Страница 2: ...sh buttons Menu Item for selecting and adjusting settings As you program your control record your settings in the ADJUST menu table which is found in the second half of this brochure Menu All of the i...

Страница 3: ...gs Burner Displays when Relay 1 is turned on Warning Displays when an error exists or when a limit has been reached Pump Displays when the primary or boiler pump is operating Lock Unlock Displays when...

Страница 4: ...m The supply water temperature is based on outdoor reset or a fixed temperature for DHW Outdoor Reset When a boiler demand signal from the heating system is present the control operates the boiler s t...

Страница 5: ...calculates a boiler target temperature that is below the Boiler Minimum setting the boiler target temperature is adjusted to at least the Boiler Minimum setting During this condition if the boiler is...

Страница 6: ...ut signal range of the 270 control The Minimum Modulation setting limits the control output range in order to match the boiler s input range To calculate the Minimum Modulation use the following formu...

Страница 7: ...residential cast iron boilers or steel tube boilers The Med Mass setting provides a moderate response to the heating system Hi 3 The Hi setting is selected if the boiler that is used has a high therm...

Страница 8: ...of time that the primary pump continues to run is adjustable using the Primary Pump Purge setting The primary pump continues to run until either the purging time has elapsed or the boiler supply temp...

Страница 9: ...ight periods INDOOR SENSOR With the indoor sensor connected the control is able to sense the actual room temperature Indoor temperature feedback fine tunes the supply water temperature in the heating...

Страница 10: ...on the WWSD pointer in the display When the control is in WWSD the Boiler Demand pointer is displayed if there is a boiler demand However the control does not operate the heating system to satisfy thi...

Страница 11: ...contact is opened until the heating system has recovered before returning to DHW operation This mode can be used if a DHW tank is piped in direct return and a DHW valve is installed DHW MODE 4 Extern...

Страница 12: ...heat from the boiler into the DHW tank The control continues this purge for a maximum of four minutes or until the boiler supply water temperature drops 20 F 11 C below the boiler target temperature d...

Страница 13: ...or Sensor 070 One Universal Sensor 082 Data Brochures D 270 D 070 D 001 Application Brochure A 270 Note Carefully read the details of the Sequence of Operation to ensure that you have chosen the prope...

Страница 14: ...power supply must be used to power both the DHW Demand and the Boiler Demand circuits since they both share the Com Dem terminal Output Connections Primary Pump Contact Prim P1 The Prim P1 output term...

Страница 15: ...When these two terminals are shorted together the control registers an unoccupied UNOCC signal Connection to Operate Modulating Boiler 11 12 Mod V dc V dc STEP FIVE TESTING THE WIRING General Each ter...

Страница 16: ...e wiring between the terminal block and pump and refer to any installation or troubleshooting information supplied with the pump If the pump operates properly disconnect the power and remove the jumpe...

Страница 17: ...oth with water and wring out prior to wiping control Do not use solvents or cleaning solutions DIP Switch Settings GENERAL The DIP switch settings on the control are very important and should be set t...

Страница 18: ...measured by the boiler supply sensor 22 to 266 F 30 to 130 C Boiler Target Boiler target temperature is the temperature the control is currently trying to maintain at the boiler supply sensor of the...

Страница 19: ...F 82 C B1 Boiler Minimum The minimum allowed boiler target temperature Check the boiler manufacturer s manual for a recommended setting OFF 80 to 180 F OFF 27 to 82 C Default 140 F 60 C B1 Boiler Maxi...

Страница 20: ...C Default 180 F 82 C DHW Exchange Unoccupied Selects whether or not a DHW demand will be responded to during the UnOccupied period OFF On Default OFF WWSD Occupied The system s warm weather shut down...

Страница 21: ...essed again to advance to the next step This can also be used to rapidly advance through the test sequence To reach the desired step repeatedly press and release the Test button until the appropriate...

Страница 22: ...ystem start up in order to purge air from the piping To enable the Max Heat feature use the following procedure 1 Press and hold the Test button for more than 3 seconds At this point the control flash...

Страница 23: ...to read the boiler supply sensor due to a short circuit The control will not operate the boiler until the sensor is repaired Locate and repair the problem as described in the Data Brochure D 070 To cl...

Страница 24: ...AND FITNESS FOR A PARTICULAR PURPOSE DURA BILITY OR DESCRIPTION OF THE PRODUCT ITS NON INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS AND ITS COMPLIANCE WITH OR NON VIOLATION OF ANY APPLICABLE EN...

Отзывы: