Setup and Operation 

V6.x // 06-2016

 

 

secu4

 display with 3 or 4 tanks: 

 

Regular display: 

  

In case of a battery tank system with 3 or 4 tanks the display will switch over. 
Thereby the single tank display and the inventory and clearance display are shown alternately. 
 

 

 
 

Switch-over 

 

=>

 

 

 

 

If while refilling one of the tanks reaches 93% 

STAR

 as well as the warning 

STOP! Filllimit 

will appear. 

 

 
 

Switch-over 

 

=> 

 

 

 
 
 
 
 
 

ALARM and QUIT-button for 

secu4

 

 

Reference in this case is 95% filling limit, i.e. signaling at 93%

 

 

Filling level / 
action 

Status 

Red LED 
(Quit-button) 

Beeper 
(loud) 

Relay break 
contact  

Display 

all levels below 
limit 

OK 

off 

off 

closed 

OK 

level >= 93 % 
at refill or reserve 

warning 

flashes 

double  
beeping 

closed 
 

STOP 

Quit-button, shortly

 

(quit beeper) 

warning 
gets quitted 

turns off 

turns off 

closed 

STOP 

level reaches 95% 
(limit) 

alarm 

flashes 

fast double 
beeping 

disrupts 

STOP 

Quit-button, shortly

 

(quit beeper) 

alarm

 

gets quitted 

flashes 

turns off 

stays 
disrupted

 

STOP 

Quit-button, long

 

(quit beeper) 

hold for 3 sec.

 

Quit-status 

but level still 
exceeded

 

changes to 
continuous 
light 

off 

closes again 

STOP 

level drops under 
94%  
(thru consumption) 

warning 

turns off 

off 

closed 

full (stop) 

level drops under 
92% 

OK 

off 

off 

closed 

OK 

 

Содержание e-litro

Страница 1: ...sm SW Version V6 0x for tank sizes up to max 10 000 liters CONTENT Installation and mounting 4 Control elements and display 4 ALARM and QUIT button for secu4 6 Device setup and programming 7 Programmi...

Страница 2: ...e applicable for liquid level measurements of tanks operated unpressurized Maximum display value 10 000 liters per tank in case of secu4 The liquid level is indicated by the LCD display The instrument...

Страница 3: ...t the secu4 will sound the ALARM and an output relay will interrupt the current loop of the tanker The displaying device and the sensorbox both contain of an alarm sound Such an alarm can be switched...

Страница 4: ...skip to next menu step Language Select the operation language German English French in menu step 18 Select displaying mode for e litro and e litro net gsm After setting menu items 1 to 5b the favored...

Страница 5: ...assword The device settings can be protected by activating a password under menu item 8 A forgotten password can be requested by contacting TECSON Resetting the secu4 will cause the device to demote i...

Страница 6: ...evel action Status Red LED Quit button Beeper loud Relay break contact Display all levels below limit OK off off closed OK level 93 at refill or reserve warning flashes double beeping closed STOP Quit...

Страница 7: ...up the measuring range of the level sensor The LITRO Sensor is preset to 250mbar Measuring range max oil tank height water column 250 mbar 3 00 m 2 50 m If a different level sensor to the LITRO Sensor...

Страница 8: ...ank shape With excava tion Plastic tank with large cavity Excavation in the middle of the tank s body No ring bandages Cyl 50m 3 Not applicable with e litro displaying devices Bearing chart Value inpu...

Страница 9: ...g limit 95 190cm change of value with If e g a water tank may be filled to capacity the filling limit is to be set to a value of 99 all all 6 Display resp for secu4 without function The upper display...

Страница 10: ...for secu4 loss of password Menu item 9 24 see ff Steps 9 24 contain special settings which usually will not be needed all After entering setup of step 1 to 7 the standard programming is completed By...

Страница 11: ...Example 3 e litro secu4 device with 4 battery tanks 4 x 1250 liters steel tanks with hemicycles at top and bottom 155cm tank height display Fillspace Level for each single tank disable tank filling a...

Страница 12: ...displaying Default values Resets all values back to standard 0 For secu4 Exit all do not execute with e litro 10 Trim height Input option for the reference height for calibration of probe and measurem...

Страница 13: ...the registered tank numbers Return only for e litro gsm e litro net 17 Input Output Alarm In Choose the function of the alarm contact input Deactive Defines the alarm input to be not operating Opening...

Страница 14: ...Relay 1 Off On Enter Not for e litro 24 Reset Resetting the device software ESC Leaves this sub menu without execution Restart New initialization of the device software but parameter setup is left un...

Страница 15: ...Please blow through or replace the measurement line preferably with the blue bubbling through pipe of the e litro set As a TEST the bubbling through pipe can be disconnected from the LITRO Sensor E8 s...

Страница 16: ...estination In case of entering an individual dest IP no Error N2 message will be shown Important The destination address must be a fixed IP address Otherwise the device retries sending again and again...

Страница 17: ...on the prepaid account Error M 5 No mobile network available for the SIM card an external antenna could help Destination number set correctly please check Error M 6 Network or other failure during se...

Страница 18: ...us 2 green signal 3 brown minus Bottom right clamping block Power supply 230V AC N L Clamp contact number 1 LITRO sensor input red or white or blue 2 LITRO sensor input brown or black 3 4 Input for a...

Страница 19: ...number 1 LITRO Sensor input red white blue 2 ditto black brown 3 data input for additional e litro device 4 ditto 5 alarming contact input 6 ditto 7 8 relay output opening contact normal status is clo...

Страница 20: ...er maintenance This needs to be induced by the operator If the secu4 s tanker switch off function is used the password needs to be activated in menu item 8 The password is predefined Maintenance Manuf...

Отзывы: