Electrical connection
Electrical and magnetic fields often generate interfering voltage in the
measuring circuit. This interference essentially emanates from high
voltage current running parallel to the measuring lines, but can also
be caused by contactors or electric motors operating in the
vicinity. Interfering voltage can also be introduced galvanically. This
particularly occurs in cases where the measuring chain is earthed at
various points that do not have the same potential.
To avoid the coupling in of interference, please note the following:
•
Always use shielded, low-capacity measuring cables (all tecsis
cables meet these requirements).
•
The shielded measuring cable should be grounded on both sides.
•
Do not route the measuring cable parallel to high-voltage current
and control cables.
•
Avoid leakage fields from transformers, motors and contactors.
•
The load pin, the amplifier and the display unit must not have multi-
ple earths. Attach all equipment to the same protective conductor.
The plug or cable connection assignments can be found on the name
plate (Fig. 1 to 3, p. 33-34). Unless otherwise agreed, the
following assignments are used as standard.
Abbreviations for connection Abbreviations for colors
UB+
power
BN
brown
0V/UB-
power supply -
WH
white
UR+
power for Relay
(SIL-Shift)
BU
blue
UR-
power supply - for Relay
(SIL-Shift)
BK
black
Содержание F5308
Страница 26: ...Betriebsanleitung Operating manual F5308 F53C8 F53S8 26 BD_BE 991 d www tecsis de 12 Konformitätserklärung ...
Страница 27: ...Betriebsanleitung Operating manual F5308 F53C8 F53S8 www tecsis de BD_BE 991 d 27 ...
Страница 49: ...Betriebsanleitung Operating manual F5308 F53C8 F53S8 www tecsis de BD_BE 991 d 49 12 Declaration of Conformity ...
Страница 50: ...Betriebsanleitung Operating manual F5308 F53C8 F53S8 50 BD_BE 991 d www tecsis de ...
Страница 51: ...Betriebsanleitung Operating manual F5308 F53C8 F53S8 www tecsis de BD_BE 991 d 51 ...