EV Inverter Operating Manual
___________________________________________________________________________
TECO
– Westinghouse Motor Company 29
S1
S2
S3
T
er
m
in
al
s
F06 = 2
Three wire mode
F06 = 0
Run/Stop/Reverse
F06 = 1
Run/Reverse/Stop
NOTE: If C00=001, the reverse command is disabled.
F07 Frequency upper limit (Hz) : 01.0 - 200
F08 Frequency lower limit (Hz) : 00.0 - 200
NOTE: If F07 = 0Hz and frequency command = 0Hz, the inverter will zero-speed stop.
If F08 > 0Hz and frequency command <F08, the inverter will run at the F08 set value.
F09 Stopping method
000: Decelerate to stop
001: Free run ( Coast) to stop
1.) F09 = 000: after receiving a stop command, the motor will decelerate to stop at the rate set
in F02, deceleration time 1.
2.) F09 = 001: after receiving a stop command, the motor will free-run (Coast) to stop.
O
utp
ut
fr
eq
u
en
c
y
F07 (Frequency upper limit)
F08 (Frequency lower limit)
(See note below)
Commanded frequency
Fig. 11.1d Control Method Sequences
Fig. 11.2 Frequency Limits
Содержание EV INVERTER Series
Страница 69: ......