EV Inverter Operating Manual
___________________________________________________________________________
TECO
– Westinghouse Motor Company 4
1.3 Installation and Pre-operation
Caution
The inverter should be installed in a dry and dust-free area.
The inverter should be installed on a nonflammable surface such as metal.
The inverter may be operated up to an altitude of 1000m. Above 1000m it must be
de-rated.
(Please consult factory)
If several inverters are to be placed in the same enclosure, additional cooling may be
needed to keep the surrounding temperature below 50°C to avoid overheating or
possible fire.
Do not
connect T1, T2, and T3 terminals of the inverter to the AC power supply.
CMOS ICs on the
inverter‘s main board are susceptible to static electricity.
Do not
touch the main circuit board without proper precautions.
Do not
perform dielectric tests on parts inside the inverter as the high voltage will
easily destroy semiconductor parts.
Wiring size and insulation type, as well as placement of the inverter, should conform
to applicable codes for a particular installation.
Control wiring should be kept separate from power wiring and cabling. In some
applications it may be necessary to use shielded cable for the control wiring and / or
the power cabling to avoid performance issues.
Danger
Do not
modify any internal wiring, circuits, or parts. Connect the ground terminal of
the inverter properly. For 200V class Rg =< 100Ω, 400V class Rg =< 10Ω.
1.4 During Power ON
Caution
The display will flash the input voltage for about 2 seconds when power is applied.
D
anger
To avoid damage to the control circuitry resulting from transient voltages,
do not
plug
or un-plug any connectors or connect or disconnect any wiring to or from the inverter
when power is present.
Do not
change out parts and or check signals on circuit boards during the inverter
operation.
When power interruption to the inverter is momentary, the inverter has sufficient
power storage to ride through and continue operation. However, when power loss
interruption is longer than 2 seconds (the larger the horsepower, the longer the time);
the inverter does not have enough stored power to maintain control. Therefore, when
power is restored, the inverter restart is controlled as follows:
1 -
Will
not
automatically run after restart if Run Command Source parameter
F04=000 keypad
(Factory Default
).
2 -
Will not
automatically run after restart if Run Command Source parameter
F04=001 external terminal (switch) is
off
.
3 -
Will
automatically
run
after restart if Run Command Source parameter
F04=001 external terminal (switch) is
on
and parameters F41=000. (Auto
Restart after power loss)
When removing or installing the keypad operator, turn
OFF
power first, and follow the
instruction diagram to avoid improper operation.