EV Inverter Operating Manual
___________________________________________________________________________
TECO
– Westinghouse Motor Company 55
Section 13
-
Error Codes and Troubleshooting
The following
Tables
13.1 - 13.5
describe the error codes that are displayed under fault
conditions. They are broken down into five categories:
Unresettable / Unrecoverable errors
Errors recoverable both manually and automatically
Manually recoverable errors Only
(no auto-restart)
Set-up configuration and interface errors
Keypad errors
Some of the faults can be reset manually via the
Reset
key, or by an
external reset
command. Certain faults can also be reset by setting parameter
F41=000
(Enable Auto
Restart). Other faults are
not resettable
. In this case, the inverter may need a total
replacement or a
part
replaced.
SAFETY FIRST!
Use extreme caution when trouble shooting.
Table 13.1
Unresettable / Unrecoverable Errors
Display
Error
Cause
Remedy
EEPROM problem
EEPROM problem
Replace EEPROM
Overvoltage during
stop
Voltage detection circuit
malfunction
Repair or replace unit
Undervoltage during
stop
1. Input voltage too low
2. Power resistor or fuse burned
out.
3. Detection circuit malfunctions
1. Check that the input voltage is
correct.
2. Replace the power resistor or the
fuse
3. Repair or replace inverter
The inverter is
overheating during stop
1. Thermal detection circuit
malfunction
2. Ambient temperature too high
or poor ventilation
1. Repair or replace unit
2. Improve ventilation conditions or
relocate inverter
Current transducer
detection error
Current transducer or circuit
error.
Repair or replace unit
* The Fault relay contact does not operate with these error indications.
EPR
CTR
*
OV
*
LV
*
OH