EV Inverter Operating Manual
___________________________________________________________________________
TECO
– Westinghouse Motor Company 25
C46
Multi-function output T+, T-
(Photocoupler)
Note: This function is
provided by an SIF-IO option
card
000 Run
005
001
Frequency reached
(Set frequency ±
F23
)
002
Frequency is within the
range set by (
F22±F23
)
003
Frequency detection
(
>F22
)
004
Frequency detection
(
<F22
)
005 Fault terminal
006 Auto reset and restart
007 Momentary power loss
008 Emergency stop(E.S.)
009 Base block (b.b.)
010 Motor overload protection
011 Inverter overload protection
012
Not used
013 Power on
014 Communication error
015
Output current detection
(>F24
)
C47
Remote keypad control
selection
Note: The remote keypad is
an option
000
Disable (no signal loss
detection)
000
Note 4
Stop
inverter then
connect
remote
keypad for
proper
operation
001
Enable. On signal loss stop
according to
F09
002
Enable. Runs at the last set
frequency. On signal loss
stop according to
F04
setting or Stop key on
keypad.
C48
Copy module
Note: This function is
provided by the Copy
Module option card
000 Copy module disable
000
Note 3
001
Copy to module from
inverter
002
Copy to inverter from
module
003 Read / Write check
C49
Inverter communication
address
Note: SIF-232 or
SIF-485 required
-
001 - 254
001
Notes 3&4
C50
Baud rate (
bps
)
Note: SIF-232 or SIF-485
required
000 4800
003
Notes 3&4
001 9600
002 19200
003 38400
C51
Stop bit
Note: SIF-232 or
SIF-485 required
000 1 Stop bit
000
Notes 3&4
001 2 Stop bits
C52
Parity bit
Note: SIF-232 or
SIF-485 required
000 No parity
000
Notes 3&4
001 Even parity
002 Odd parity