Parallel Setting
7.7.2.1
Parallel Board for UPS 1
The Parallel Board is positioned at the bottom on the back side.
Please set SW2 on the parallel board of the UPS 1 to the right side as shown in figure 7.2.
Figure 7.2 - SW2 position on UPS 1
7.7.2.2
Power Stage/Module ID of UPS 2
There are
three DIP switches
(see #2- figure 6.1) for
power stage/module ID address setting
. In the same
cabinet, each power stage/module ID address MUST be exclusive. Please refer to table 7-1. where the ID
addresses assigned to the power stages/modules of UPS 2 are indicated