![Technoware EVO DSP PLUS TT 100 KVA Скачать руководство пользователя страница 64](http://html1.mh-extra.com/html/technoware/evo-dsp-plus-tt-100-kva/evo-dsp-plus-tt-100-kva_user-manual_1070751064.webp)
ENGLISH
User’s manual
58
UPS EVO DSP PLUS TT
Figure 7-4 - UPS 1 Parallel Board
Figure 7-5 - UPS 2 Parallel Board
The parallel cables of each UPS must to be connected correctly.
Incorrect connection will result in abnormal operations.
7.7.5
Parallel System Turn On Procedure
1.
Please be sure the
Input Breakers (Q1)
and
Output Breakers (Q3)
of each UPS have been turned
“ON”.
2.
Turn on the Battery Breaker
of Battery Boxes.
3.
Turn on the external AC Source Breaker to apply AC Input Source to both UPS.
4.
Watch for any abnormal event message on the LCD display.
5.
Switch on each UPS by pressing
the Power On/Off Button for 2 seconds
(or
by using the Menu-Control-
System Turn On
).