UPS EVO DSP PLUS TT
4.
ONLY 100KVA/120KVA models: switch OFF the Main AC Input breaker Q1 and the Bypass Input breaker Q2.
ONLY 160KVA/200KVA models: switch OFF the Main AC Input breaker Q1, the Bypass Input breaker Q2 and
the Output Breaker Q3.
5.
It is possible to change the power stage/module now.
7.4.2
Transfer to UPS Protection
Please follow below steps to transfer from Maintenance Bypass to UPS protection.
1.
Make sure the maintenance is complete. All power stages/modules have been installed well
2.
ONLY 100KVA/120KVA models: switch ON the Main AC Input breaker Q1 and the Bypass Input breaker Q2.
ONLY 160KVA/200KVA models: switch ON the Main AC Input breaker Q1, the Bypass Input breaker Q2 and
the Output Breaker Q3.
3.
Check if the UPS operates in Bypass Mode, as show below.
4.
Switch OFF the Maintenance Bypass Breaker
.
5.
Lock back the mechanical lock plate
as shown below
.
100KVA/120KVA models
160KVA/200KVA models