![Technoware EVO DSP PLUS TT 100 KVA Скачать руководство пользователя страница 47](http://html1.mh-extra.com/html/technoware/evo-dsp-plus-tt-100-kva/evo-dsp-plus-tt-100-kva_user-manual_1070751047.webp)
ENGLISH
UPS EVO DSP PLUS TT
41
User’s manual
6.3
Output/input Terminal Blocks
To access the Output/Input Terminal Blocks, remove the cover panels.
100KVA/120KVA
160KVA/200KVA
Figure 6.6 –Terminal Blocks
No.
Item
Function
Description
Output Block (OUTPUT)
Connects to the critical loads
Includes: R(L1 phase), S(L2 phase), T(L3
phase) and N(Neutral) terminals.
Bypass Input Block (INPUT2)
Connects to Bypass AC Input
Line
Includes: R(L1 phase), S(L2 phase), T(L3
phase) and N(Neutral) terminals.
Main Input Block (INPUT1)
Connects to Main AC Input
Line
Includes: R(L1 phase), S(L2 phase), T(L3
phase) and N(Neutral) terminals.
Screws for UPS Grounding
For UPS grounding
2 GND screws: one screw on the right
and the other on the left above the low
floor of case.
Battery Block (BAT)
Connects to an external
battery cabinet
Includes: Positive (+), Negative (-) and
Neutral (N) terminals.