PRMAN-0047 ORYX200 S21 Fire Panel Range Rev 02.00 220224.docx
E&OE
ORYX200 RANGE
Technoswitch Conventional
Fire Control Panels
ABS, Standard & Weatherproof Versions
Rev 02.00
Страница 1: ...PRMAN 0047 ORYX200 S21 Fire Panel Range Rev 02 00 220224 docx E OE ORYX200 RANGE Technoswitch Conventional Fire Control Panels ABS Standard Weatherproof Versions Rev 02 00 ...
Страница 2: ...__________________________________________________24 1 9 5 AUX DC Supply Output ____________________________________________________________25 1 9 6 L Bus Wiring_____________________________________________________________________26 1 9 7 USB Connection for SOLAR_________________________________________________________26 1 10 Panel Loading __________________________________________________________...
Страница 3: ...________42 Short Circuit _______________________________________________________________43 Low Resistance Fault ________________________________________________________44 Incorrect EOL Resistor _______________________________________________________45 High Resistance Fault ________________________________________________________46 False Fire Alarms and Activations__________________________________...
Страница 4: ...50 x 139 Environmental 5 C to 40 C Humidity 95 RH Non condensing Weight ORYX202 ORYX204 ABS ORYX202 ORYX204 Weatherproof ORYX208 Standard ORYX208 Weatherproof 2 1 kg excl Batteries 7 4 kg excl Batteries 5 7 kg excl Batteries 10 7 kg excl Batteries Cable Entries ORYX202 ORYX204 ABS Top 6x 20 mm 5x 25 mm Back 4x 20 mm 2x 25 mm ORYX202 ORYX204 Weatherproof Bottom 5x 20 mm 2x 25 mm ORYX208 Standard To...
Страница 5: ...each Sounder EOL 3k3 Ω General Fire Relay 30 V AC DC 1 A maximum General Fault Relay 30 V AC DC 1 A maximum Programmable Relays ORYX202 ORYX204 ORYX208 2 rated 30 V AC DC 1 A maximum 4 rated 30 V AC DC 1 A maximum 8 rated 30 V AC DC 1 A maximum Programmable Inputs 2x fully monitored as per below Monitored Inputs EOL 3k3 Ω Monitored Inputs Alarm Threshold 220 to 900 Ω L Bus Topology and Distance RS...
Страница 6: ...cognise and Notify Supply Faults 5 4 Additional Functions Auxiliary Power Supply Output Auxiliary Relay Outputs 1 2 CAUTIONS AND WARNINGS STOP Before commencing with installation or operation of the panel please read this manual carefully If you are unclear on any point DO NOT proceed Contact the manufacturer or supplier for clarification and guidance Only trained service personnel should undertak...
Страница 7: ... Devices Output to Fault Routing Equipment Test Condition 7 8 8 9 10 PSE Functions EN54 4 Clause Operation from a Main Power Supply Operation from a Standby Battery Monitor and Charge the Standby Battery Recognise and Notify Supply Faults 5 1 5 2 5 3 5 4 This FACP also supports the following additional functions that are not covered by EN54 Additional Function Refer to Paragraph Auxiliary Power Su...
Страница 8: ...ulations for example BS7671 appropriate to the country and location of the installation 1 6 IDENTIFICATION OF PARTS Figure 1 Identification of Major Panel Parts 1 7 INSTALLING THE ENCLOSURE The panel is heavy when the batteries are installed Use the appropriate fixing hardware to secure the panel to the wall Observe recommended lifting practices to guard against spinal injury See the table below f...
Страница 9: ...vent accidental damage NB Do not lift the chassis by holding onto any of the printed circuit cards Hold the chassis by the metal plate only NB Do not remove or tamper with the DO NOT REMOVE sticker to screw out the harness this will void the warranty Unplug the harness only from the Main PCB and leave it connected to the PSU Firstly remove the required knockouts for the installation wiring There a...
Страница 10: ...ctors of the Main PCB If the DIN Rail option was selected the harnesses between the pluggable connectors and DIN Rail modules will be pre installed Drill the required holes in the supporting wall using an 8 mm drill bit ABS and Standard Enclosures or a 10 mm drill bit Weatherproof Enclosure and plug with a suitable 40 mm or longer expansion plugs Affix the panel to the wall with M6 screws or No 10...
Страница 11: ... ORYX208 Conventional Fire Panels INSTALLATION OPERATION MANUAL PRMAN 0047 ORYX200 S21 Fire Panel Range Rev 02 00 220224 docx E OE 11 Figure 4 ORYX208 Standard Enclosure Figure 5 ORYX202 ORYX204 Weatherproof Enclosure ...
Страница 12: ...with a cross sectional area suitable for the loading conditions In areas where cabling may come into contact with high frequency interference such as portable radio transceivers etc the data wiring cable should be of a twisted pair construction within an overall screen Care should be taken to correctly terminate this screen refer to the relevant sections of this manual for further information for ...
Страница 13: ...TION OPERATION MANUAL PRMAN 0047 ORYX200 S21 Fire Panel Range Rev 02 00 220224 docx E OE 13 Figure 7 Internal Arrangement Showing Recommended Cable Routing for the ORYX202 ORYX204 Figure 8 Internal Arrangement Showing Recommended Cable Routing for the ORYX208 ...
Страница 14: ... with DIN Rail mounted modules External wiring as indicated in section 1 8 3 Battery Positioning Wiring on page 17 should be terminated to the DIN Rail modules A layout of the DIN Rail terminal connections is shown in Figure 11 and is also available on the inside of the panel s door Figure 9 Internal Arrangement Showing Recommended Cable Routing in the DIN Rail Mounted ORYX202 ORYX204 Weatherproof...
Страница 15: ...roof Panel with DIN Rail ORYX208 1 8 1 2 Weatherproof Panel Without DIN Rail Option The routing arrangement shown in Figure 13 is recommended for the Weatherproof Enclosure without DIN Rail mounted modules External wiring indicated in section 1 8 3 Battery Positioning Wiring on page 17 should be terminated to the pluggable connectors on the chassis plate PCB Figure 13 Internal Arrangement Showing ...
Страница 16: ...and live terminal connections These are clearly marked on the label next to the PCB connector The connector block contains an integral fuse holder Secure the Mains Input wiring by tie wrap as close to the terminal block as possible Connect the power supply to the Mains Supply via a readily accessible disconnect device Isolation Switch and suitable earth fault protection incorporated in the buildin...
Страница 17: ...YX204 Weatherproof Panel The panel requires 2x two 12 V DC batteries connected in series for standby operation The battery harness is already pre fitted Use the Red Black leads of the provided harness to connect the batteries to the BATT VCC and BATTGND terminals on the PSU The short Blue lead provided is used to connect the batteries as shown in Figure 18 Refer to the Specifications section of th...
Страница 18: ...ssist if no AC mains supply is present on site The batteries will need to be fully charged before using this function Remove the load from the output Press and hold the Start from Batteries button until CPU running LED flashes Do not continuously run your power supply in this mode Do not make the final battery connections until the installation wiring is completed and the system is to be powered u...
Страница 19: ...The internal power supply is a high efficiency switch mode power supply with an input AC voltage range of 100 240 V AC The power supply provides the following 27 5 V DC to the fire control panel electronic circuits Battery charging and monitoring LED fault indication Two relay outputs one for common PSU fault and the other for an AC Input Fault Figure 19 PSU Configuration ...
Страница 20: ...are provided to protect the output or to provide additional current depending on the amount of current draw Boost Mode Should the current draw exceed 1 2 A the 27 5 V DC output Fault LED will flash and the battery charger circuit will be shut down If the 27 5 V DC output current draw exceeds 1 2 A but is less than 1 8 A for more than 10 minutes the General Fault Relay and the 27 5 V DC output LED ...
Страница 21: ...ll illuminate and the General Fault relay will activate The output will attempt to reset itself every four seconds until the fault is cleared 1 8 4 3 PSU INFORMATION INDICATIONS Load Test The Load Test LED is on for 15 seconds whilst test is conducted battery charger is switched off successful test Normal failed test Battery Fault First load test takes place 10 minutes after start up and every 4 h...
Страница 22: ...ally monitored for Short Circuit Low Resistance Active Double End of Line Normal and Open Circuit Conditions The 3k3 resistor provided must be connected across the ve and ve output terminal of the last device installed on that sounder circuit see Figure 23 below NB The Zener diodes indicated in Figure 23 below are only required when the warning device type has an internal resistance that affects t...
Страница 23: ... ORYX204 The panel monitors this resistance and will react with a Fault condition if an open or short circuit is detected A resistance between 220 900 Ω across the circuit will produce a fire alarm Up to 32 devices may be wired per zone as per EN54 Standards For specific device allocations per zone refer to the applicable local standard For intrinsically safe applications use a MTL 5561 Galvanic I...
Страница 24: ...e Flyback from an unprotected relay can be high enough to spark over the panel s relay contacts onto its coil and then damaging the CPU Flyback voltage is not created when the external relay is energised but created as soon as the relay is de energised Using the TEC031 range of relay solutions may help prevent this 1 9 4 INPUT CIRCUITS Two inputs are provided which have been pre programmed as show...
Страница 25: ...ORYX200 S21 Fire Panel Range Rev 02 00 220224 docx E OE 25 Figure 26 Input Circuits 1 9 5 AUX DC SUPPLY OUTPUT A 24 V DC auxiliary output limited to 500 mA is provided to power peripheral equipment The Auxiliary output has short circuit and overload protection Figure 27 AUX DC Supply Output ...
Страница 26: ... for the ORYX fire panels with standard enclosure or weatherproof enclosure It is the installer s responsibility to ensure a clean earthing screening point For detailed information on the ORYX Repeater range wiring instructions and configuration please refer to PRMAN 0048 ORYX Repeater Installation and Operation Manual Figure 28 Repeater Wiring 1 9 7 USB CONNECTION FOR SOLAR The USB B port on the ...
Страница 27: ... A x Total ORYX202 0 70 1 0 0 70 0 265 1 0 0 265 ORYX204 0 90 1 0 0 90 0 385 1 0 0 385 ORYX208 0 108 0 108 0 410 0 410 AUX 24 V DC 1 0 1 0 Sounder Output 1 1 0 Sounder Output 2 1 0 Total Quiescent Load Alarm Load x 24 hr A hr x 48 hr A hr A h x 72 hr A hr 21 x 0 5 hr Ahr carry forward Ahr Total Load Quiescent Alarm Ahr x 1 251 Battery De rating factor Ahr 1 The alarm load should be doubled to allo...
Страница 28: ...els are as follows Level 1 Untrained User An Untrained User will only be able to silence the buzzer Level 2 Authorised User Enable Controls key switch An Authorised User will be able to use all control buttons on the panel membrane Level 3 Commissioning Service and Maintenance Opening the panel and connecting via USB port for programming Event Log retrieval or Enabling the Service Switch 2 1 2 FRO...
Страница 29: ...its into Test mode 3 second press Also used to perform a LED test press release Scroll Used to in conjunction with either the Disable or Test button to select the zone or sounder circuits to be disabled or put into Test mode Enable Controls Key Switch Key switch for enable disabling of controls key switch must only be able to be removed in the controls disabled position 2 1 2 2 PANEL INDICATIONS T...
Страница 30: ... Flashing Yellow The service commission switch is active and the panel is in commissioning mode All outputs are disabled in this mode Power On Steady Green The panel is supplied with Mains power Silence Buzzer Steady Yellow Internal buzzer has been silenced Silence Alarm Steady Yellow Sounders have been silenced Sound Alarm Steady Yellow Sounders have been activated NB Refer to PRBOI 0007 ORYX200 ...
Страница 31: ...ble LED and the selected zone s Fault In Test Disable LED will now be on steady Yellow The rapid flashing LED will automatically advance the selection onto the next zone To exit the enablement or disablement selection mode wait for 10 seconds or press reset The same procedure is used to enable a zone 2 1 6 ENABLING DISABLING OF SOUNDER CIRCUITS The following procedure is used to disable sounder ci...
Страница 32: ...from Test Mode Alternatively for a quick exit from Test Mode push the Reset button When a zone is in test the Fire LED for that zone the General Fire LED Buzzer and all Sounders will go on for eight seconds before automatically clearing the condition if the device in the field has been reset No relays will activate if a zone is in test except those relays programmed to switch when Sounders are Act...
Страница 33: ...ORYX202 ORYX204 ORYX208 Conventional Fire Panels INSTALLATION OPERATION MANUAL PRMAN 0047 ORYX200 S21 Fire Panel Range Rev 02 00 220224 docx E OE 33 Figure 31 Bootloader Jumper Position ...
Страница 34: ...delays are cancelled Normal Normal Zone indications are activated immediately Sounder will only be activated after the set sounder delay period has lapsed Verified Determines the minimum time that the circuit must be in the alarm condition before an alarm condition is registered Confirmed 1st alarm from a zone is inhibited zone is reset and checked every 30 seconds If the alarm is still present af...
Страница 35: ...aracters Enabled YES NO Test YES NO Sounder Disabled The output is activated when a sounder is disabled Output Text 0 21 Characters Enabled YES NO Test YES NO Disablement The output is activated when an FACP device is disabled Output Text 0 21 Characters Enabled YES NO Test YES NO Test The output is activated when an FACP device is put into test mode Output Text 0 21 Characters Enabled YES NO Test...
Страница 36: ... sounder is activated Output Text 0 21 Characters Zone No 1 8 Enabled YES NO Test YES NO 3 1 3 SOUNDERS The Sounders have the following programmable features Programming Group Programming Function Comments Options None None Sounder circuit is not used and will not activate None General Fire SND Sounder circuit will activate when any fire alarm is detected Output Text 0 21 Characters Type NORMAL IS...
Страница 37: ...nders on the panel to be activated Input Text 0 21 Characters Enabled YES NO Test YES NO Inverted YES NO Silence Buzzer Activating an input with this setting will cause the buzzer to be silenced Input Text 0 21 Characters Enabled YES NO Test YES NO Inverted YES NO Mute Activating an input with this setting will cause the buzzer and all sounders on the panel to be silenced Input 2 default to this s...
Страница 38: ...D Test LCD Test Keypad Test GENERAL LVL Time out Screen 1 Silence Buzzer Silence Sndrs Reset Level Fault Latching Earth Monitor EVENT LOG All Screen 1 Fire Fault Disable Condition Action PANEL INFORMATION Panel No Screen 1 Panel Name Date Time Event Reminder SERVICE DUE Date Screen 1 Time Company Contact Reminder ACCESS CODES Access Level Screen 1 Access Level Name Access Code TOOLS Default Contro...
Страница 39: ...reen Items Page 2 MODULES Module Screen 1 Enabled Product Id Revision Hardware Firmware Date Protocol Screen 2 Module Input Voltage ZONES Zone Screen 1 Zone Text Status Type Latch Zone Screen 2 Enabled Test Mode Zone Screen 3 Voltage Counts SOUNDERS Sounder Screen 1 Output Text Status Group Func Sounder Screen 2 Enabled Test Delay Action Type Sounder Screen 3 Voltage ...
Страница 40: ...02 00 220224 docx E OE 40 Main Menu Option Screen Items Page 2 continued PROG INPUTS Input Screen 1 Input Text Status Group Function Input Screen 2 Enabled Test Inverted Input Screen 3 Voltage RELAYS Relay Screen 1 Output Text Group Function Relay Screen 2 Enabled Test Page 3 L BUS SETUP Setup Screen 1 Inputs Relays Status ...
Страница 41: ... responsibly and in accordance with any local regulations Expected Life 3 to 5 years at an ambient temperature of 20 C Replacement Schedule As above Note however that the expected battery life is shortened by increase in ambient temperature The life reduces by 50 for every 10 C rise above ambient Refer to battery manufacturer for further information For optimum performance and charge retention it ...
Страница 42: ...nel Controls disabled Ensure controls are enabled Power Supply Faults Description Measurement Possible Cause Action Required Resistance Voltage AUX 24 V DC Fault N A 0 V Load exceeds maximum current rating 500 mA Remove load check for short circuits and consult load technical information Battery Fault 20 V DC Batteries unplugged or internal resistance high Check battery circuit connections or repl...
Страница 43: ...e Ensure correct value EOL is in place Zone 4 Short Circuit Check field device termination and polarity Zone 5 Short Circuit To confirm the panels indications the resistance should be measured with the circuit cabling removed from the Main PCB disconnect terminal block If short persist after completing above checks break zone cabling at the field devices in smaller sections to reduce the search ar...
Страница 44: ...e Zone 4 Low Resistance Fault Check field device termination and polarity Zone 5 Low Resistance Fault In addition the resistance should be measured with the input or output cabling removed from the Main PCB disconnect terminal block If low resistance fault persists after completing above checks break zone cabling at the field devices in smaller sections to reduce the search area Zone 6 Low Resista...
Страница 45: ...CB If double EOL fault persist after completing above checks break zone cabling at the field devices in smaller sections to reduce the search area Zone 4 Double EOL Fault Zone 5 Double EOL Fault In addition the resistance should be measured with the input or output cabling removed from the Main PCB disconnect terminal block If the problem persists please contact your supplier Zone 6 Double EOL Fau...
Страница 46: ...ination and polarity Zone 4 Open Circuit Fault If open circuit fault persists after completing above checks break zone cabling at the field devices in smaller sections to reduce the search area Zone 5 Open Circuit Fault In addition the resistance should be measured with the input or output cabling removed from the Main PCB disconnect terminal block Zone 6 Open Circuit Fault If the problem persists...
Страница 47: ...S Zone Ensure correct value EOL is in place Z3 Fire To confirm the panel s indications Voltage should be measured across the input or output whilst the field cabling is connected to the Main PCB Check field devices for activations Z4 Fire If the problem persists please contact your supplier Z5 Fire In addition the resistance should be measured with the input or output cabling removed from the Main...
Страница 48: ...6 WARRANTY General Terms and Conditions are available from the Technoswitch website www technoswitch co za Alternatively please contact your local Sales Office for further information 7 DISCLAIMER Although the contents of our product literature have been prepared with the greatest care Technoswitch can accept no liability whatsoever for any direct or indirect damages of any kind that may arise due...
Страница 49: ...9144 E info technoswitch co za Cussonia Park 3 Ridge Road Laser Park Johannesburg PO Box 1752 Randpark Ridge South Africa 2156 CAPE TOWN T 27 0 21 948 4575 Tyger Terraces II Block 2B DJ Wood Street Bellville Business Park Cnr Mike Pienaar Blvd Voortrekker Road Bellville 7530 DURBAN T 27 0 31 266 8843 Colchester Building Essex Gardens 1 Nelson Road Westville 3629 www technoswitch co za ...