Heat meter
32
Heat meter
Standard diagram
Function description
Calculation of thermal output and metering of thermal energy via the temperature differential
T.flow - T.return and the flow rate, and allowing for the antifreeze component in the heat transfer
medium.
Input variables
Enable
General enabling of the function (digital value ON/OFF)
Flow temperature
Analogue input signal for the flow temperature
Return temperature
Analogue input signal for the return temperature
Flow rate
Analogue input signal for the flow rate
Meter reset
Digital
pulse
input signal, ON/OFF, to reset the meter
Specific heat capacity
Optional
: Analogue value specifying the heat capacity of the fluid in
the measured system
Price / unit
A price per kWh for yield calculations
• The
BFPT1000 5x60MM
sensors fitted in the
KH ball valve
from Technische Alternative are
particularly suitable for temperature measurement. The sensors can be removed with little
effort for the calibration process.
• With a solar thermal system, the collector sensor can also be used as the flow sensor. For that
to be possible, it must be installed in a sensor well at the flow outlet of the collector header.
However, the captured amount of heat will then also include the losses in the solar flow line.
• Entering
User
as the source in the
Flow rate
input variable allows a fixed value to be entered as
the flow rate instead the flow rate captured by a flow sensor.
• The
meter reset
is carried out by a digital ON pulse or manually in the parameter menu. It will
delete
all
meter readings, in other words also those from previous periods. The meter will be
blocked as long as this input variable is set to ON. The meter reset also works when Enable =
Off.
•
Specific heat capacity:
This optional specification must be entered as a multiple of the unit
0.01 kJ/l*K
as a
dimensionless
number.
Example:
Pure water has a heat capacity of 4.18 kJ/
l*K at 20 °C, so a dimensionless value of 418 must be entered for this heat capacity (at 20 °C).
N.B.:
The heat capacity of fluids is temperature-dependent. The value entered should there
-
fore be a variable value dependent on the temperature (e.g. from the Curve function).
Содержание CAN-EZ3
Страница 5: ......
Страница 27: ...Energy manager 27 Example of a standard diagram Energy manager with output control CAN EZ3 and EHS R...
Страница 61: ...61 Messages This menu item displays activated messages Example Message 21 is active...
Страница 94: ......
Страница 95: ......