Installation and connection – CAN bus
18
Cable selection and network topology
Screened twisted pairs have proven useful in CANopen networks. These are cables with twisted
pairs of conductors and a shared external screen. Such cables are relatively resistant to EMC inter
-
ference and can still carry 50 kbit/s for up to 1000 m. The CANopen recommendations (CiA DR 303-
1) for cable cross-sections are given in the table below.
The maximum cable length also depends on the number of nodes [n] linked with the bus cable and
the cable cross-section [mm²].
Bus rate
In the CAN bus / CAN settings menu of the UVR16x2, the bus rate can be set to between 5 and 500
kbit/s, whereby lower bus rates enable longer cable networks. However, in this case, the cable cross-
section must be increased accordingly.
The standard bus rate of the CAN network is 50 kbit/s (50 kBaud), which is specified for many CAN
bus devices.
Important:
All
devices in the CAN bus network must have the same transfer rate in order to be able
to communicate with each other.
Recommendations
A 2x2-pole, screened twisted pair (twist CAN-L with CAN-H or +12 V with GND) with a cable cross
-
section of at least 0.5 mm² and a conductor-to-conductor capacity of no more than 60 pF/m and a
nominal impedance of 120 ohms. The standard bus speed of the UVR16x2 is 50 kbit/s. This recom
-
mendation corresponds, for example, to cable type
Unitronic®-BUS CAN 2x2x0.5
supplied by
Lapp
Kabel
for permanent installation
in buildings or conduits.
Theoretically this would enable a bus
length of approx. 500 m to guarantee reliable transmission.
For
direct
routing
underground,
earth cable
2x2x0.5
mm² supplied by
HELUKABEL,
part no. 804269,
or earth cable
2x2x0.75
mm² supplied by
Faber Kabel,
part no. 101465, would be suitable.
Bus length
[m]
Resistance in terms
of length [mΩ/m]
Cross-section
[mm
2
]
0...40
70
0,25...0,34
40...300
< 60
0,34...0,60
300...600
< 40
0,50...0,60
600...1000
< 26
0,75...0,80
Cable cross-section
[mm
2
]
Maximum length [m]
n=32
n=63
0,25
200
170
0,50
360
310
0,75
550
470
Bus rate [kbit/s] Maximum permissible total bus length [m]
5
10.000
10
5.000
20
2.500
50 (standard)
1.000
125
400
250
200
500
100