AccuLoad IV Installation & Maintenance Manual
Installation
32
3.5.6.2 A4I I/O Index Numbering
The following tables provide details about configuring the A41 board’s I/Os.
Table 15: A4I Switch Settings
Switch
Setting
S1-1
Factory Use
S1-2
OFF = Address 100
ON = Address 200
S1-3
OFF = Band 9600
ON = Band 38,400
S1-4
OFF = RS 232
ON = RS 485
S1-5
OFF = Address 100
ON = Address 200
S1-6
Reserved
S1-7
Model SA Board Set Selector - see section 6, Off for all other models
S1-8
Model SA Board Set Selector - see section 6, Off for all other models
Table 16: First Optional A4I I/O Index Numbering
Terminal
Block
Type of I/O
AccuLoad Configuration Index Number
TB3
Injector pulse
or digital input
Inj 11 in or DC In 30 – Pin 2 Inj 12 in or DC In 31 – Pin
5 Inj 13 in or DC In 32 – Pin 8 Inj 14 in or DC In 33 –
Pin 11
TB4
Serial communication port
RS232/485
Inj 8 in or DC In 27 – Pin 3 Inj 9 in or DC In 28 – Pin 6
Inj 10 in or DC In 29 – Pin 9