K
81
6-6. Wiring the Remote Controller
<Flush Mounting>
Connection diagram
Use 0.5 mm
2
– 2 mm
2
wires.
(1) Strip the insulation to approximately 14 mm from
the ends of the wires that will be connected.
(2) Twist together the 2 wires and create a crimp con-
nection at the wire joint.
(3) If a special crimping tool is not used, or if the con-
nection is soldered, insulate the wires using insu-
lation tape.
Use the remote controller cord (optional) for remote
controller wiring.
(1) Disconnect the lead wire that is wound around the
lead wire anchor on the remote controller unit. Dis-
connect the connector and connect the remote
controller cord (optional) to the connector on the
remote controller unit. Insert the remote controller
cord (optional) into the groove and bend it into the
correct shape, then wind it around the lead wire
anchor.
(2) If the remote controller cord (optional) is used,
refer to the installation manual that is provided
with the cord.
Terminal board for
indoor unit remote
controller wiring
1
2
1
2
W
BK
Remote controller wiring
(field supply)
Connector
Remote
controller
unit
Power wire from remote
controller unit
Approx.
200 mm
Remote controller wiring
Power wire from
remote controller
unit
Provided wire joint
(white)
Wire joint
CE-1, white
Remote controller cord (optional)
Connector
Lead wire anchor
06-062 Mini ECO-i II for Technibel 2/8/06 4:32 PM Page 81