CAFM1VS
34
Fig. 3-17
Fig. 3-18
Fig. 3-20
Fig. 3-21
1-Way Air Discharge Semi-Concealed Slim
Type (CAFM1VS Type)
3-5. Suspending the Indoor Unit
(1) Place the full-scale diagram (supplied) on the ceil-
ing at the spot where you want to install the indoor
unit. Use a pencil to mark the drill holes. Refer to
Table 3-1 and Figs. 3-17 and 3-19.
Since the diagram is made of paper, it may shrink or
stretch due to high temperature or humidity. For this
reason, before drilling the holes maintain the correct
dimensions between the markings.
(2) Follow the diagrams to make the holes in the ceil-
ing. (Figs. 3-18 and 3-19)
Table 3-1
NOTE
Type
Length
A
B
9, 12, 18
1,193
1,089
25
1,390
1,286
The distance between the
bottom of the suspension
bolts and the bottom surface
of the ceiling should be 30 to
100 mm. (Fig. 3-24)
(3) Depending on the ceiling type:
Insert suspension bolts as shown in Fig. 3-20.
or
Use existing ceiling supports or construct a suitable
support as shown in Fig. 3-21.
WARNING
(4) Cut the ceiling material, if necessary.
(Refer to Figs. 3-18 and 3-19)
It is important that you
use extreme care in sup-
porting the indoor unit
from the ceiling. Ensure
that the ceiling is strong
enough to support the
weight of the unit. Before
hanging the unit, test the
strength of each attached
suspension bolt.
Rear
Full-scale diagram
Front face
A
(Ceiling opening dimension)
B
(Suspension bolt pitch)
690(Ceiling
opening dimension)
Air discharge side
Drain hose
Refrigerant tube
(Suspension bolt pitch)
405
197
40
18
39
192
221
52
(52)
Air-di
s
char
g
e
s
ide
Refri
g
era
n
t t
u
bi
ng
joi
n
t
(liq
u
id t
u
be
s
ide)
Refri
g
era
n
t t
u
bi
ng
joi
n
t
(
g
a
s
t
u
be
s
ide)
Drai
n
co
nn
ectio
n
port
157
2
8
Sus
pe
ns
io
n
l
ug
88
3
5
140
157
19
8
15
221
40
52
Hole-in-anchor
Hole-in-plug
Concrete
Insert
Suspension bolt (M10 or 3/8")
(field supply)
Ceiling tiles
Ceiling support
Fig. 3-19
Unit: mm
Unit: mm
Unit: mm