CAFM1V
29
3. HOW TO INSTALL THE INDOOR UNIT
1-Way Air Discharge Semi-Concealed Type
(CAFM1V Type)
3-1. Suspending the Indoor Unit
(1) Follow the diagrams to make the holes in the
ceiling. (Figs. 3-1 and 3-2)
(2) Depending on the ceiling type:
Insert suspension bolts as shown in Fig. 3-3
or
Use existing ceiling supports or construct a suitable
support as shown in Fig. 3-4.
Fig. 3-1
Fig. 3-2
Fig. 3-4
Fig. 3-3
4 – 12
×
37 oblong holes
74
74
780 (Ceiling opening dimension)
590
(Ceiling opening dimension)
652
(Suspension bolt pitch)
483
(Suspension bolt pitch)
20
20
Flared refri
g
era
n
t co
nn
ectio
n
o
u
tlet (
g
a
s
t
u
be)
Flared refri
g
era
n
t co
nn
ectio
n
o
u
tlet (liq
u
id t
u
be)
Power wiri
ng
o
u
tlet
Sus
pe
ns
io
n
l
ug
Drai
n
o
u
tlet
560
26
8
15
15
100
115
40
2
8
7
20
60
3
0
65
Drai
n
i
ns
pectio
n
port
Ceiling tiles
Ceiling support
Hole-in-anchor
Hole-in-plug
Concrete
Insert
Suspension bolt (M10 or 3/8")
(field supply)
WARNING
It is important that you use
extreme care in supporting
the indoor unit from the ceil-
ing. Ensure that the ceiling
is strong enough to support
the weight of the unit.
Before hanging the unit, test
the strength of each
attached suspension bolt.
(3) Cut the ceiling material, if necessary.
(Refer to Figs. 3-1 and 3-2)
Unit: mm
Unit: mm
06-062 Mini ECO-i II for Technibel 2/8/06 4:32 PM Page 29