background image

DSAFM

62

HT : U

s

i

ng

 boo

s

ter cable

H : At 

s

hipme

n

t

5

Air Flow (m

3

/mi

nu

te)

Exter

n

al 

S

tatic Pre

ssu

re

0

50

100

0

5

10

15

150

10

(mmAq)

(P

a)

Limit li

n

e

Limit li

n

e

HT

H

M

L

20

Air Flow (m

3

/mi

nu

te)

Exter

n

al 

S

tatic Pre

ssu

re

0

50

0

5

10

15

150

10

Limit li

n

e

Limit li

n

e

HT

H

L

100

M

(mmAq)

(P

a)

3

0

40

Air Flow (m

3

/mi

nu

te)

Exter

n

al 

S

tatic Pre

ssu

re

0

50

0

5

10

15

150

20

Limit li

n

e

Limit li

n

e

L

100

M

H

(mmAq)

(P

a)

HT

3

0

Air Flow (m

3

/mi

nu

te)

Exter

n

al 

S

tatic Pre

ssu

re

0

50

0

5

10

15

150

20

Limit li

n

e

HT

L

100

M

H

Limit li

n

e

(mmAq)

(P

a)

15

Air Flow (m

3

/mi

nu

te)

Exter

n

al 

S

tatic Pre

ssu

re

0

50

0

5

10

15

150

10

Limit li

n

e

Limit li

n

e

HT

M

L

100

H

(mmAq)

(P

a)

1

8

 Ty

p

e

7, 9, 12 Ty

p

e

Indoor Fan Performance

25 Ty

p

e

3

6 Ty

p

e

4

8

 Ty

p

e

NOTE

3-34.  Increasing the Fan Speed

If external static pressure is too great (due to long

extension of ducts, for example), the air flow volume

may drop too low at each air outlet. This problem may

be solved by increasing the fan speed using the fol-

lowing procedure:

(1) Remove 4 screws on the electrical component box

and remove the cover plate.

(2) Disconnect the fan motor sockets in the box.

(3) Take out the booster cable (sockets at both ends)

clamped in the box.

(4) Securely connect the booster cable sockets

between the disconnected fan motor sockets in

step 2 as shown in Fig. 3-111.

(5) Place the cable neatly in the box and reinstall the

cover plate.

Fig. 3-111

Fig. 3-112

Booster cable

Booster cable

Electrical component box

(At shipment)

(Booster cable installed)

Fan motor socket

Fan 

motor

How to read the diagram

The vertical axis is the external static pressure (Pa) while the horizontal axis represents the air flow (m

3

/minute).

The characteristic curves for “HT,” “H,” “M” and “L” fan speed control are shown. The nameplate values are shown

based on the “H” air flow. For the 25 type, the air flow is 18 m

3

/minute, while the external static pressure is 49 Pa at

“H” position. If external static pressure is too great (due to long extension of ducts, for example), the air flow volume

may drop too low at each air outlet. This problem may be solved by increasing the fan speed as explained above.

06-062 Mini ECO-i II for Technibel  2/8/06  4:32 PM  Page 62

Содержание CAFM

Страница 1: ...485 R DSAFM Concealed Duct DSAFM DSAFM DSAFM DSAFM DSAFM DSAFM DSAFM 74 R 94 R 124 R 184 R 255 R 365 R 485 R DSAFMHP Concealed Duct DSAFMHP DSAFMHP DSAFMHP High Static Pressure 254 R 364 R 484 R KFM F...

Страница 2: ...re hazard When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin...

Страница 3: ...g power etc Most importantly the multi air conditioner system is able to replenish a large amount of refrigerant com pared to conventional individual air conditioners If a single unit of the multi air...

Страница 4: ...a conventional vacuum pump if it is equipped with a check valve If it has no check valve purchase and attach a vacuum pump adapter Leak detector Yes No Leak detectors for CFC and HCFC that react to c...

Страница 5: ...3 2 Use R410A exclusive cylinder only Single outlet valve with siphon tube Liquid refrigerant should be recharged with the cylinder standing on end as shown 06 062 Mini ECO i II for Technibel 2 8 06...

Страница 6: ...rge Semi Concealed Type CAFM2V Type 39 3 9 Suspending the Indoor Unit 3 10 Placing the Unit Inside the Ceiling 3 11 Installing the Drain Piping 3 12 Checking the Drainage 4 Way Air Discharge Semi Conc...

Страница 7: ...djusting the Auto Flap 10 TEST RUN 98 10 1 Preparing for Test Run 10 2 Test Run Procedure 10 3 Outdoor Unit PCB Setting 10 4 Auto Address Setting 10 5 Caution for Pump Down 10 6 Meaning of Alarm Messa...

Страница 8: ...ene insulation for copper tubes as required to precise length of tubing Wall thickness of the insulation should be not less than 8 mm 3 Use insulated copper wire for field wiring Wire size varies with...

Страница 9: ...suspension bolts 1 For securing drain hose Black White White Part Name Figure Q ty Remarks Full scale installation diagram 1 Special washer 8 Flare insulator 2 Insulating tape 2 2 Vinyl clamp 8 Hose...

Страница 10: ...stall on opposite side of tubing For fastening installation gauges Table 1 4 4 Way Air Discharge Semi Concealed Part Name Figure Q ty Remarks Full scale installation diagram 1 Flare insulator 2 Insula...

Страница 11: ...oints Printed on container box Table 1 7 Concealed Duct Part Name Figure Q ty Remarks 8 Flare insulator 2 Insulating tape 2 Drain insulator 1 Hose band 1 Packing 1 Drain hose 1 Sealing putty 1 Vinyl c...

Страница 12: ...ame Figure Q ty Remarks Connection pipe 1 Flare insulator 2 Insulating tape 2 Insulating tape 2 Vinyl clamp 7 Insulating tape black and long 1 Drain insulator 1 For connecting gas tubes For gas and li...

Страница 13: ...bend R60 100 mm Trap bend 12 7 0 30 0 23 0 90 2 30 15 88 0 35 0 26 1 05 2 80 19 05 0 42 0 32 1 26 3 20 Y branch distribution joint Equivalent length conversion not needed Ball valve for service Equiva...

Страница 14: ...stribution joint K70A056Z for indoor unit Note Do not use commercially available T joints for the liquid tubing H2 LD L1 L2 LC LB LA Be sure to use special R410A distribution joints K70A056Z purchased...

Страница 15: ...added to that distribution joint When adding the ball valve locate it within 40 cm of the distribution joint Consult with Technibel separately concerning the ball valve If a trap or ball valve is not...

Страница 16: ...able 1 22 1 Because the diameter of this ball valve is approximately the same as the inner diameter of the connecting cop per tube correction for pressure loss is not necessary 2 Airtightness must be...

Страница 17: ...r 29 mm respectively Be sure to use only the supplied flare nuts Be careful to use the correct tools and materials 2 Flare nut tightening The flare nut on the service port side is fully tightened Reco...

Страница 18: ...valve is used for any other purpose use a box cut ter or similar tool to cut away the part shown in the figure at right The insulation is divided into 2 parts After per forming the leak test use viny...

Страница 19: ...with R410A refrigerant in liquid form With R410A refrigerant charge while adjusting the amount being fed a little at a time in order to prevent liquid refrigerant from backing up After charging is co...

Страница 20: ...per 1 meter are different for each liquid tubing size 9 52 LA LB LC LD 65 m 0 056 kg m 3 64 kg 6 35 1 2 3 4 5 23 m 0 026 kg m 0 598 kg Total 4 238 kg Additional refrigerant charge amount is 4 238 kg B...

Страница 21: ...he maximum elevation differ ence above or below the outdoor unit and within a total tubing length L from the outdoor unit as detailed in Table 1 19 allow room for mounting the remote controller about...

Страница 22: ...ble water damage and decreased ser vice life Fig 2 9 use lug bolts or equal to bolt down unit reducing vibration and noise 4 1 2 3 1 More than 1 cm More than 100 cm More than 1 cm Inlet side C Inlet s...

Страница 23: ...the unit may occur b There may be no air flow c The tubing may freeze and burst d The condenser pressure may drop because of strong wind and the indoor unit may freeze 2 5 Precautions for Installatio...

Страница 24: ...t air discharge chamber 2 Unit left side air discharge chamber 3 Unit light side air discharge chamber 4 Reinforcement brackets 4 locations 110 660 170 13 13 340 405 380 10 15 20 20 13 68 544 300 Wind...

Страница 25: ...oth sides must remain open If there are obstacles to the front and rear of the outdoor unit the obstacle at either the front or rear must be no taller than the height of the outdoor unit 1 Single unit...

Страница 26: ...or snow proof vents field supply For GRFMI306 406 506R5I Unit mm 1 Unit top snow proof vent 2 Unit left side 3 Unit right side 4 Unit reverse side 5 Unit reverse side 6 Unit sides reinforcement bracke...

Страница 27: ...acle to the front of unit Outdoor unit GRFMI306 406 506R5I A B D C E F G 150 150 Outdoor unit K L GRFMI306 406 506R5I 500 150 200 300 300 150 200 Min C Min E Min F Min E Min E Min L Min B Min A Min D...

Страница 28: ...remain open Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit Dimension Q If a snow protection duct is attached after the unit is inst...

Страница 29: ...t pitch 20 20 Flared refrigerant connection outlet gas tube Flared refrigerant connection outlet liquid tube Power wiring outlet Suspension lug Drain outlet 560 268 15 15 100 115 40 287 20 60 30 65 Dr...

Страница 30: ...nit If the ceiling is already constructed lay the tubing into position for connection to the unit before placing the unit inside the ceiling 2 Thread the 3 hexagonal nuts and 2 washers field supply on...

Страница 31: ...PVC pipe must be purchased separately The unit s transparent drain port allows you to check drainage Fig 3 10 Fig 3 9 Fig 3 10 Fig 3 11 37 70 5 Installation gauge 15 Vinyl clamps Drain insulator suppl...

Страница 32: ...s will cause the drain water to flow backward and leak when the unit is not operating Fig 3 14 Do not apply force to the piping on the unit side when connecting the drain pipe The pipe should not be a...

Страница 33: ...utlet grille Fig 3 16 3 Short the check pin CHK on the indoor control board and operate the drain pump Check the water flow through the transparent drain pipe and see if there is any leakage 4 When th...

Страница 34: ...ion bolts as shown in Fig 3 20 or Use existing ceiling supports or construct a suitable support as shown in Fig 3 21 WARNING 4 Cut the ceiling material if necessary Refer to Figs 3 18 and 3 19 It is i...

Страница 35: ...e unit will not fall off the suspension lugs 3 The indoor unit should be suspended from the suspension bolts Fig 3 23 so that the distance between the bottom of the suspension lug and the bottom surfa...

Страница 36: ...VP 25 Hard PVC pipe PVC adhesive Bead Vinyl clamps Drain insulator supplied 2 After checking the drainage wrap the supplied packing and drain pipe insulator around the pipe then secure it with the su...

Страница 37: ...vide insulation for any pipes that are run indoors 3 8 Checking the Drainage After wiring and drain piping are completed use the following procedure to check that the water will drain smoothly For thi...

Страница 38: ...p installation screws the drain hose and the wiring Removing the side panel 1 Push the tab on both sides of the side panel inward a to disengage the tab first stage and move the panel horizontally b 2...

Страница 39: ...in the ceiling Table 3 2 2 Depending on the ceiling type Insert suspension bolts as shown in Fig 3 36 or Use existing ceiling supports or construct a suitable support as shown in Fig 3 37 WARNING It i...

Страница 40: ...ge to check 3 11 Installing the Drain Piping 1 Prepare a standard hard PVC pipe O D 32 mm for the drain and use the supplied drain hose and hose band to prevent water leaks The PVC pipe must be purcha...

Страница 41: ...ting the drain pipe The pipe should not be allowed to hang unsupported from its connection to the unit Fasten the pipe to a wall frame or other support as close to the unit as possible Fig 3 46 Provid...

Страница 42: ...pin CHK on the indoor control board and operate the drain pump Check the water flow through the transparent drain port and see if there is any leakage 4 When the check of drainage is complete open th...

Страница 43: ...e supplied full scale installation diagram The diagram and table Fig 3 50 and Table 3 4 show the relationship between the positions of the sus pension fitting unit and panel Table 3 4 Unit mm Fig 3 48...

Страница 44: ...15 mm as shown in Fig 3 51 3 Thread the 3 hexagonal nuts and 2 washers field supply onto each of the 4 suspension bolts as shown in Fig 3 52 Use 1 nut and 1 washer for the upper side and 2 nuts and 1...

Страница 45: ...hose may slip off Align the hose bands with the end of the hose Tighten the hose band firmly Please make sure that the bead is not covered by the hose band Fig 3 53 2 After checking the drainage wrap...

Страница 46: ...connection to the unit Fasten the pipe to a wall frame or other support as close to the unit as possi ble Fig 3 58 Provide insulation for any pipes that are run indoors 3 17 Checking the Drainage Afte...

Страница 47: ...ove precautions are also applicable if tub ing goes through the wall in any other location 4 Using a sabre saw key hole saw or hole cutting drill attachment make a hole dia 80 mm in the wall Fig 3 63...

Страница 48: ...o Install the Indoor Unit In principle with this model wiring can be completed without removing the grille However if it is necessary to change the settings on the PCB follow the procedure below Remov...

Страница 49: ...74 Raising the clamp to lift up the indoor unit will facili tate this work Fig 3 75 To remove the indoor unit press up on the 2 loca tions marks on the lower part of the unit frame to disconnect the i...

Страница 50: ...Do not supply power to the unit or operate it until all tubing and wiring to the outdoor unit are completed Left or left rear tubing 1 Pass the tubing and drain hose into the rear of the indoor unit...

Страница 51: ...outlet port Remote controller wiring inlet port 30 knock out Power inlet port 40 knock out Power inlet port 40 knock out Knock out Side panel Position of plate inside side panel Side panel Left side...

Страница 52: ...le diagram 3 Depending on the ceiling type a Insert suspension bolts as shown in Fig 3 85 or b Use existing ceiling supports or construct a suit able support as shown in Fig 3 86 NOTE WARNING It is im...

Страница 53: ...pply 5 Before suspending the indoor unit remove the 2 or 3 screws on the latch of the air intake grilles open the grilles and remove them by pushing the claws of the hinges as shown in Fig 3 88a Then...

Страница 54: ...confirm that the indoor unit is evenly suspended For the installation to be correct leave a clearance of about 10 mm between the ceiling panel and the ceiling sur face and fill the gap with an approp...

Страница 55: ...drain hose is connected below the refrigerant tubing 2 Installing the drain hose To install the drain hose first place 1 of the 2 hose bands over the unit drain port and the other hose band over the h...

Страница 56: ...nit to the outside Fig 3 95 Never allow traps to occur in the course of the piping Insulate any piping inside the room to prevent drip ping After the drain piping pour water into the drain pan to chec...

Страница 57: ...r For details refer to Fig 3 94a For the method used to insert the wiring refer to the figure below Fig 3 97 2 How to carry out wiring Open the knock out hole on the rear or top of the main unit Attac...

Страница 58: ...0 780 290 262 680 715 180 340 8 12 200 3 962 900 1 000 1 080 290 272 980 1 015 130 245 250 12 16 180 5 245 1 1 442 1 380 1 480 1 560 335 310 1 460 1 495 130 490 240 16 18 230 6 245 2 No of holes L M C...

Страница 59: ...test the strength of each attached suspension bolt 1 When placing the unit inside the ceiling determine the pitch of the suspension bolts referring to the dimensional data on the previous page Fig 3 9...

Страница 60: ...pre vent water leaks The PVC pipe must be purchased separately The transparent drain part on the unit allows you to check drainage Fig 3 105a CAUTION Do not use adhesive at the drain connection port...

Страница 61: ...Fig 3 109 3 33 Checking the Drainage After wiring and drain piping are completed use the following procedure to check that the water will drain smoothly For this prepare a bucket and wiping cloth to...

Страница 62: ...the fol lowing procedure 1 Remove 4 screws on the electrical component box and remove the cover plate 2 Disconnect the fan motor sockets in the box 3 Take out the booster cable sockets at both ends c...

Страница 63: ...box Inspection access 600 600 25 Type Min 550 Min 580 36 48 Type or Suspension bolt pitch Suspension bolt pitch 980 940 130 290 500 Min 600 Space for service Drain pan Ceiling face A 310 100 100 300 B...

Страница 64: ...test the strength of each attached suspension bolt 1 When placing the unit inside the ceiling determine the pitch of the suspension bolts referring to the dimensional data on the previous page Fig 3 1...

Страница 65: ...port threads with sealing tape then connect the joint Fig 3 119a 3 After connecting the drain pipe securely wrap insulator field supply around the pipe 4 Ensure the drain pipe has a downward gradient...

Страница 66: ...ute The characteristic curve for the H Med and Lo fan speed control The nameplate values are shown based on the H air flow Therefore in the case of 25 Type the flow is 23 m3 minute while the External...

Страница 67: ...ws Air filter Refrigerant connection outlet liquid tube Refrigerant connection outlet gas tube Level adjusting bolt Drain outlet 20 A Power cord outlet downward rear Refrigerant tubing outlet downward...

Страница 68: ...7 6 5 4 3 2 1 Type Length A B C D Liquid Gas tube tube 7 9 12 858 692 672 665 9 52 12 7 18 25 1173 1007 1002 980 9 52 15 88 D 229 155 66 125 260 402 539 147 205 100 56 D A B C 166 374 147 30 30 70 616...

Страница 69: ...n heater 4 Remove the chain connecting the front panel of the unit by unhooking it from the fixture attached to the panel How to attach the front panel 1 Hook the chain to the fixture of the front pan...

Страница 70: ...between the union insulator and flare insulator with black insulating tape Fasten both ends of the flare insulator with the supplied vinyl clamps 167 1 7 7 Holes for fixing the unit to the floor Rear...

Страница 71: ...r into the drain pan to check if the water drains smoothly 5 Remove any dust or debris in the drain pan so that the pipe is not clogged 3 44 Installing the Remote Controller A remote controller option...

Страница 72: ...ocket For details refer to the instruction manual of the drain socket optional part STK DS25T 4 3 Routing the Tubing and Wiring The tubing and wiring can be extended out in 4 direc tions front rear ri...

Страница 73: ...isoperation that occurs as a result of such unauthorized changes 7 Regulations on wire diameters differ from locality to locality For field wiring rules please refer to your LOCAL ELECTRICAL CODES bef...

Страница 74: ...em for the explanation of A B C D and E in the above diagram 2 The basic connection diagram of the indoor unit shows the 7P terminal board so the terminal boards in your equipment may differ from the...

Страница 75: ...oor units When shipping In shorted condition Otherwise the communication of S net link system is not performed For a system without link no con nection wiring between outdoor units do not remove the s...

Страница 76: ...htly connected When connecting each power wire to the terminal fol low the instructions on How to connect wiring to the terminal and fasten the wire securely with the fixing screw of the terminal plat...

Страница 77: ...all box for flush mounting 2 Attach the back case with the 2 small screws pro vided Using a screwdriver push open the cut outs on the back case These holes are for screws Use the spacers and take care...

Страница 78: ...unit In this case a remote controller can be connected at any indoor unit Wiring procedure Wire according to the right diagram Each successive unit will respond at 1 second intervals following the or...

Страница 79: ...ress CODE NO with SET TEMP buttons Select the UNIT NO that you want to call with button Press the button to finish service mode To display the trouble history Press both and buttons on the remote cont...

Страница 80: ...ntroller When group control is used the remote controller sensor will not function unless the group address is set to the address of the master indoor unit If both the remote sensor and remote control...

Страница 81: ...nnector and connect the remote controller cord optional to the connector on the remote controller unit Insert the remote controller cord optional into the groove and bend it into the correct shape the...

Страница 82: ...t the end of the copper tube with a tube reamer or file This process is important and should be done carefully to make a good flare Fig 7 1 When reaming hold the tube end downward and be sure that no...

Страница 83: ...tdoor side tub ing 2 To fasten the flare nuts apply specified torque as at right When removing the flare nuts from the tubing con nections or when tightening them after connecting the tubing be sure t...

Страница 84: ...aracteristics be easy to use be age resis tant and must not easily absorb moisture After a tube has been insu lated never try to bend it into a narrow curve because it can cause the tube to break or c...

Страница 85: ...erlap half of each previous tape turn 3 Clamp the tubing bundle to the wall using 1 clamp approx each meter Fig 7 10 Do not wind the armoring tape too tightly since this will decrease the heat insulat...

Страница 86: ...lves on the outdoor unit are kept closed at this stage Leak test 1 Attach a manifold valve with pressure gauges and dry nitrogen gas cylinder to this service port with charge hoses 2 Pressurize the sy...

Страница 87: ...for evacuation varies with the tubing length and capacity of the pump The following table shows the amount of time for evacuation The required time in the above table is calculated based on the assump...

Страница 88: ...ected to the gas tube service port for 7 94 mm tube slightly to release the pressure then remove the hose 4 Replace the service port cap on the gas tube ser vice port and fasten the cap securely with...

Страница 89: ...eiling panel and finely adjust the suspension position of the unit 4 Once the joining edges are properly aligned with each other install the supplied stoppers into the key hole shaped openings then in...

Страница 90: ...d into 4 points as shown in Fig 9 3 3 Install the wiring connector from the ceiling panel to the connector from the indoor unit If the connector is not connected a misoperation sig nal P9 on the remot...

Страница 91: ...ng the side panels see Fig 9 5 Attaching the side panels Put the center claw of the side panel into the center recess of the indoor unit Pressing 2 claws of the both sides of the side panel toward the...

Страница 92: ...e air intake panel from either side Fig 9 8 1 Push in 2 Slide 3 Pull 4 Remove Fig 9 6 Indoor unit Ceiling 60 60 Fig 9 7 Fig 9 8 Electrical component box Ceiling panel Indoor unit M4 25 screw 2 pcs Onl...

Страница 93: ...anel to the connector in the electrical component box of the indoor unit 8P connector if heat pump model After installing the connector use the clamp on the body of the indoor unit to secure the wirin...

Страница 94: ...in this range malfunction or other trouble may result A Ceiling side Main unit Ceiling opening dimension A Fig 9 11 Wing Fig 9 12a Fig 9 12b 2 Fig 9 14 9 7 Before Installing the Ceiling Panel 1 Remove...

Страница 95: ...re hole in unit Temporary fastener Push when you remove Temporary fastener Fig 9 16 Drain tubing corner Refrigerant tubing corner Panel installation hole 4 locations Ceiling panel Washer head screws D...

Страница 96: ...does not become caught Be sure to attach the safety cord that prevents the air intake grille from dropping off to the ceiling panel unit as shown in the figure at right Direction that the unit faces...

Страница 97: ...anel for servicing remove the air intake grille and air filter disconnect the wiring connector inside the electrical component box and then remove the 4 mounting screws 9 13 Adjusting the Auto Flap Th...

Страница 98: ...compressor should be hot to the touch Fig 10 1 5 Both the gas and liquid tube service valves are open If not open them now Fig 10 2 6 Request that the customer be present for the trial run Explain the...

Страница 99: ...address Set the No of outdoor units Set the No of indoor units Set the system address When multiple outdoor units exist disconnect the terminals extended from the shorted plugs CN33 at all outdoor ma...

Страница 100: ...100 10 3 Outdoor Unit PCB Setting CN51 CN50 D043 LED2 D042 LED1 S003 CN33 S002 S004 Fig 10 4 06 062 Mini ECO i II for Technibel 2 8 06 4 32 PM Page 100...

Страница 101: ...o of indoor units System address No Indoor unit setting S004 Rotary switch red System address S003 2P DIP switch blue System address S002 Rotary switch black System 1 factory setting 1 unit factory se...

Страница 102: ...the outdoor unit to 8 on the outdoor unit control PCB set the No of indoor units rotary switch S004 to 8 3 Turn ON the power to the indoor and outdoor units 4 On the outdoor unit control PCB short ci...

Страница 103: ...to the instructions on the following pages Leave the socket that is used to open circuit the terminal plug CN33 6 S004 1 ON 1 2 ON OFF S003 S002 If link wiring is used No 1 unit settings Unit No 1 Ou...

Страница 104: ...or 1 second or longer then pull it out Communication for automatic address setting begins Automatic address setting is completed when LEDs 1 and 2 on the outdoor unit control PCB turn OFF 4 Next turn...

Страница 105: ...nication for automatic address setting begins the compressors turn ON and automatic address setting in heating mode begins All indoor units operate Automatic address setting is completed when the comp...

Страница 106: ...cuit the automatic address pin CN51 for 1 second or longer then pull it out Repeat the same steps to complete automatic address setting for all units 5 Operation from the remote controllers is now pos...

Страница 107: ...tic Functions and Description of Alarm Displays Note indicates that the solenoid is fused or that there is a CT current detection circuit failure current is detected when the compressor is OFF Display...

Страница 108: ...ted to the remote controller Check that the fan of that indoor unit starts and that air is discharged 5 Press the button again and check the address of each indoor unit in sequence 6 Press the button...

Страница 109: ...onnector RCU ADR is duplicated Duplication of main remote controller Starting auto address setting is prohibited Error in auto address setting Number of connected indoor units is less than the number...

Страница 110: ...m missing phase in the compressor wiring etc Start failure not caused by IPM or no gas IPM trip IPM current or temperature Compressor suction port temperature sensor TS Possible cause of malfunction I...

Страница 111: ...on the next page twist the wires together and use a cable fastener to fasten them leaving a length of wiring that is long enough to permit removal of the adjustable corner cap Fig 11 3 5 Install the r...

Страница 112: ...mote control unit Remote control holder Parts Q ty Parts Q ty AAA alkaline battery Receiver unit Tapping screw 4 16 Clamp No No 2 2 1 1 2PWHT CN001 WHT BLK Indoor unit Receiver PCB Remote controller T...

Страница 113: ...ea of at least 0 5mm2 to 2mm2 The maximum total length of crossover cables must be no longer than 200m Ground Ground Ground Ground Fig 11 6 Fig 11 5 1 To assign the wired remote controller as the sub...

Страница 114: ...he fastener that holds the louver motor wiring Fig 11 9 5 Reattach the side panel 6 Route the lead wire from the receiver unit along the louver motor wiring and other wiring and fas ten them with a fa...

Страница 115: ...when wiring the remote controller The remote con troller will be damaged if high voltage such as 200 VAC is applied The wireless receiver unit components cannot be used for more than 1 indoor unit at...

Страница 116: ...ain or sub unit can operate with any indoor unit Use field wiring cables with a cross sectional area of at least 0 5mm2 to 2mm2 The maximum total length of crossover cables must be no longer than 200m...

Страница 117: ...ing because this may cause malfunction Install a noise filter or take other appropriate action if electrical noise affects the power supply circuit of the unit 1 Use the 2 supplied screws 4 10 to atta...

Страница 118: ...rm the lead wire as shown in the figure At the position of the cover fastening bracket part fastened by rivets extend the lead wire parallel to the ceiling panel side surface then use tape to fasten i...

Страница 119: ...er unit can permit dual remote control operation at the same time Up to 2 units of remote controllers a wireless remote controller and a wired remote controller can be installed Dual remote control op...

Страница 120: ...400m 1 2 2 1 2 1 2 1 2 1 2 1 Indoor unit No 3 Ground Ground sub Wired remote controller main Wireless remote controller kit Remote control wiring among the control groups field supply Remote controlle...

Страница 121: ...After the test run be sure to reset DIP switch No 1 back to the OFF position and check that no indi cator lamps are blinking Be aware that test run is not possible if the ceiling panel is not attache...

Страница 122: ...om fluorescent lamps leave a minimum of 2 meters between the receiver unit and the fluores cent lamps and install the receiver unit in a loca tion where it can receive the wireless remote con troller...

Страница 123: ...driver and remove the lower case Fig 11 23 2 In order to later pass the receiver wiring out through the upper case thin part at the top cen ter use nippers or a similar tool to cut a notch in the same...

Страница 124: ...nd be sure not to wire incorrectly The unit will be damaged if high voltage such as 200 VAC is applied 6 Adjust the provided spacers so that they are sev eral millimeters larger than the thickness of...

Страница 125: ...ler and be sure not to wire incorrectly The unit will be damaged if high voltage such as 200 VAC is applied to it Wire of receiver unit field supply Power wire from receiver unit Separate receiver uni...

Страница 126: ...eiver units to control 1 indoor unit Using 2 separate receiver units to control a group of multiple indoor units The main and sub receiver units will operate regardless of the indoor unit in which the...

Страница 127: ...al strain on the air conditioner do not use this mode except for conducting a test run 3 Select any one of the operation modes HEAT COOL or FAN for the test run The outdoor unit will not start running...

Страница 128: ...TP3 2P yellow on the indoor unit control PCB 3 Setting b Open the cover of the electrical component box Short the short circuit pin TP6 2P white on the indoor unit control PCB TP6 TP3 TP1 TP6 TP3 TP1...

Страница 129: ...abulation of Var i ou s data A B C D E F G C K W A Various A Model Name Various D A Various B V PH Various 50 Hz Operating Spec Area Various Not for the PED E bar Various F bar Various G kg Various Va...

Страница 130: ...R D 28 Reyrieux BP 131 01601 Tr voux CEDEX France Tel 33 04 74 00 92 92 Fax 33 04 74 00 42 00 http www technibel com 06 062 Mini ECO i II for Technibel 2 8 06 4 32 PM Page 130...

Отзывы: