background image

LZS-A500-3 Power Supply

Operating Modes

Table  5

 Series Operation 

Yes (see Fig. 7)

 Parallel Operation 

Two or more identical units (see Fig. 6).  (Use of D. con. terminal 5 will

 (with current sharing) 

provide current sharing to within 10% nominal of rated 60°C current.)

DC Output Controls and Indicators

Table  6

 Output Voltage Adjust 

Screwdriver adjustment over entire range. Output voltage range is from  

18-29.4V. (Multi-turn potentiometer accessible from terminal end of chassis.)

 Overvoltage Protection Adjust  Screwdriver adjustment over entire range. Overvoltage trip range is from  

20-34V. Factory setpoint is 31.0V. (Multi-turn potentiometer accessible

from terminal end of chassis.)

 Output Good Indicator 

Green colored LED illuminates when output is within specified operating range

 Fault Indicator 

Red colored LED illuminates if overvoltage, overtemperature, or overcurrent

shutdown occurs. The LED is also illuminated if the output is less than approximately

95% of its adjusted output or if the output is inhibited (stand-by mode).

Remote Control Features

Table  7

 Remote Voltage Sensing 

Provides precise regulation directly at load (see Fig. 3).  Maximum total

DC voltage drop between output terminals and load must be limited to

<1.0 V.  In addition, the voltage at the output terminals must be limited to

29.4V.

 Remote Voltage Programming  1000 ohms per volt for resistor connected between pins 1 and 2

 external resistor. 

on TB201 (see Figs. 4 and 5).

 Remote Voltage Programming  Volt per volt for voltage source connected between pins 1 and 2

 external voltage source. 

on TB201 (see Figs. 4 and 5).

 Remote On/Off Control 

Enable/Disable output via TTL compatible signal connected between

pins 6 and 7 of “D” connector (see Fig. 9).

 Signals Isolation 

Pins 6 and 7 are fully isolated from all other power supply terminals.

 Signal Logic 

Logic zero (below 0.7 V), short circuit or open circuit disables power

supply output.  Logic one (above 2.5 V) enables power supply output.

 Signal Current Draw 

Current draw from Logic 1 input is less than 4mA.

 Output Response Time 

Output will be within specified limits within 100 ms. of application of

logic “1” signal.

 Signal Enable 

Remote on/off function must be enabled by moving “OUTPUT ENABLE”

switch at terminal end of chassis from “LOCAL” to “REMOTE” position (see Fig. 9).

Auxiliary Monitoring and Alarm Signals

Table  8

 Optically coupled, conductance outputs.  (Conduct up to 1mA at a voltage of <0.4 V, when active.)
 Input Power Good Signal 

Conductance signal which indicates adequate input capacitor voltage to

provide 10 ms holdup time when operating -3 model at full output power.

Signal will be asserted when the unit is remotely disabled (AC still present)

or when unit shuts down due to overtemperature (see Fig. 10).

 Output Good Alarm Signal 

Conductance signal which indicates that delivered output voltage, as measured at  

the +V and -V terminals, is above its minimum specified value (see Fig. 10).

 Inverter Good Signal 

Conductance signal which indicates that the power supply’s inverter is

functional.  At very light loads, this signal may be indeterminate (see Fig. 10).

 Signal Isolation 

Input power good, output UV/OV alarms, inverter good and remote on/off

signals are isolated from power supply output and each other for voltages up

to 500 volts, minimum.  3000 VAC isolation from AC input to all auxiliary signals.

 Synchronization (Sync) 

Auxiliary signal at approximately 200khz (switching frequency of unit) used for

synchronizing with other equipment.

FEATURES

* Not backward compatible with the LZS-500-3 power supply.

Revision N : January 2022

Page. 5

1-800-LAMBDA-4

Содержание LZS-A500-3

Страница 1: ...a office Environmental These products are IPX0 and therefore chemicals solvents cleaning agents and other liquids must not be used Environment This power supply is a switch mode power supply for use i...

Страница 2: ...nt for mechanical electric shock and fire hazard protection Energy Hazards The main output of this product is capable of providing hazardous energy 240VA Final equipment manufacturers must provide pro...

Страница 3: ...Konformit t mit der EMV Richtlinie muss in der finalen Gesamtinstallation betrachtet werden Bitte kontaktieren Sie Ihr regionales TDK Lambda Vertriebsb ro im Falle von R ckfragen Umwelt Diese Produkt...

Страница 4: ...vor der Gefahr von mechanischen Risiken Stromschl gen und Brandschutz in dem Endger t vorgesehen werden Gefahren durch elektrische Energie Von bestimmten Modulen kann je nach Einstellung der Ausgangs...

Страница 5: ...ntacter votre bureau TDK Lambda le plus proche Environnement Ces produits sont IPX0 et donc on ne doit pas utiliser des produits chimiques solvants des produits de nettoyage et d autres liquides Envir...

Страница 6: ...l pour assurer la protection contre les chocs m caniques les chocs lectriques et l incendie Energies dangereuses Certains modules peuvent g n rer une nergie dangereuse 240 VA selon le r glage de tensi...

Страница 7: ...ana sono a vostra disposizione per ulteriori ragguagli Condizioni ambientali Questi prodotti sono classificati come IPX0 dunque non devono essere utilizzati sostanze chimiche solventi prodotti per la...

Страница 8: ...sse elettriche e dai pericoli di incendio Pericoli energetici Alcuni moduli sono in grado di erogare energia pericolosa 240 VA a seconda della tensione in uscita impostata I produttori delle apparecch...

Страница 9: ...contacto con su oficina local de TDK Lambda Medioambiental Estos productos son IPX0 y por tanto no pueden utilizarse sustancias qu micas disolventes agentes de limpieza ni otros l quidos Medio ambient...

Страница 10: ...ra incendios de protecci n mec nica contra descargas el ctricas y contra el peligro de incendios Peligros de energ a Algunos m dulos pueden generar energ a peligrosa 240VA dependiendo de la configurac...

Страница 11: ...tre em contacto com seu escrit rio TDK Lambda mais pr ximo Ambiental Estes produtos s o IPX0 e como tal n o se devem utilizar qu micos solventes agentes de limpeza e outros l quidos Ambiente Esta font...

Страница 12: ...cer energia perigosa 240 VA de acordo com a configura o da tens o de sa da O equipamento final do fabricante deve garantir que o pessoal de assist ncia est protegido contra contactos inadvertidos com...

Страница 13: ...LZS A500 3 POWER SUPPLY Installation Operation and Maintenance Manual IM LZSA500 3 January 2022 Revision N...

Страница 14: ...rovals 2 2 RATINGS AND SPECIFICATIONS 4 3 FEATURES 5 4 GUIDE TO APPLICATION 7 4 1 Safety Notice 7 4 2 Input Voltage 7 4 3 Output Voltage 7 4 4 Overvoltage Protection Circuit Adjustment 7 4 5 Overtempe...

Страница 15: ...he rating stated on the power supply label 8 Openings in the product case are designed for ventilation and must not be obstructed when the product is installed and or operated 9 Never push objects of...

Страница 16: ...ine 3m Criteria A Lightning Surge IEC61000 4 5 2 kV line to GND CM Criteria A 1 kV line to line DM Criteria A Conducted RF Common Mode IEC61000 4 6 10 V m RMS 150 kHz 80 MHz 80 AM at 1kHz Power Freque...

Страница 17: ...ower 84 typical 110VAC line Output Performance Specifications Units LZS A500 3 Table 4 Voltage Line Regulation 0 1 Voltage Load Regulation 0 1 Ripple and Noise 20 MHz measurement Bandwidth PARD mVP P...

Страница 18: ...7 of D connector see Fig 9 Signals Isolation Pins 6 and 7 are fully isolated from all other power supply terminals Signal Logic Logic zero below 0 7 V short circuit or open circuit disables power supp...

Страница 19: ...to power supply is 1 4 Requires No M4 metric hardware supplied with unit Input and Output Connections Table 11 Input Heavy duty terminal block Chassis Ground Tapped hole and screw provided in chassis...

Страница 20: ...here is sufficient OVP margin with respect to the output voltage to avoid nuisance tripping 4 4 OVERVOLTAGE PROTECTION CIRCUIT ADJUSTMENT The overvoltage protection circuit provides an adjustable mean...

Страница 21: ...LZS A500 3 Power Supply Figure 1 PIN Assignments for TB201 and chassis mounted D connector 5 Figures 1 800 LAMBDA 4 Revision N January 2022 Page 8...

Страница 22: ...500 3 Power Supply Figure 3 Typical Remote Sense Connection Figure 2 Typical Local Sense Connection LS Local Sense S Remote Sense LS Local Sense S Remote Sense Revision N January 2022 Page 9 1 800 LAM...

Страница 23: ...rnal Programming Resistor or Voltage Source Remote Sensing Figure 4 Remote Voltage Control with an External Programming Resistor or Voltage Source Local Sensing LS Local Sense S Remote Sense LS Local...

Страница 24: ...LZS A500 3 Power Supply Figure 6 Parallel Operation Revision N January 2022 Page 11 1 800 LAMBDA 4...

Страница 25: ...LZS A500 3 Power Supply Figure 7 Series Operation 1 800 LAMBDA 4 Revision N January 2022 Page 12...

Страница 26: ...LZS A500 3 Power Supply Figure 8 Outline Drawing Revision N January 2022 Page 13 1 800 LAMBDA 4...

Страница 27: ...LZS A500 3 Power Supply Figure 9 Remote Output On Off Control Figure 10 Input Good Inverter Good Output Good Signals 1 800 LAMBDA 4 Revision N January 2022 Page 14...

Отзывы: