background image

IA979-04-01A

 

This Manual Covers Models: 

 

GSPS10-3000* 

GSPS100-300 

GBSPS10-3000* 

GBSPS100-300 

 

GSPS20-1500 

GSPS150-204 

GBSPS20-1500 

GBSPS150-204 

 

GSPS30-1020 

GSPS200-150 

GBSPS30-1020 

GBSPS200-150 

 

GSPS40-750 

GSPS300-102 

GBSPS40-750 

GBSPS300-102 

 

GSPS50-600 

GSPS400-78 

GBSPS50-600 

GBSPS400-78 

 

GSPS60-510 

GSPS500-60 

GBSPS60-510 

GBSPS500-60 

 

GSPS80-390 

GSPS600-51 

GBSPS80-390 

GBSPS600-51 

 

 

GSPS100-450 

 

GBSPS100-450 

 

GSPS20-2250 

GSPS150-306 

GBSPS20-2250 

GBSPS150-306 

 

GSPS30-1530 

GSPS200-225 

GBSPS30-1530 

GBSPS200-225 

 

GSPS40-1125 

GSPS300-153 

GBSPS40-1125 

GBSPS300-153 

 

GSPS50-900 

GSPS400-117 

GBSPS50-900 

GBSPS400-117 

 

GSPS60-765 

GSPS500-90 

GBSPS60-765 

GBSPS500-90 

 

GSPS80-585 

GSPS600-76.5 

GBSPS80-585 

GBSPS600-76.5 

 

GSPS10-4500** 

GSPS100-600 

GBSPS10-4500** 

GBSPS100-600 

 

GSPS20-3000 

GSPS150-408 

GBSPS20-3000 

GBSPS150-408 

 

GSPS30-2040 

GSPS200-300 

GBSPS30-2040 

GBSPS200-300 

 

GSPS40-1500 

GSPS300-204 

GBSPS40-1500 

GBSPS300-204 

 

GSPS50-1200 

GSPS400-158 

GBSPS50-1200 

GBSPS400-158 

 

GSPS60-1020 

GSPS500-120 

GBSPS60-1020 

GBSPS500-120 

 

GSPS80-780 

GSPS600-102 

GBSPS80-780 

GBSPS600-102 

 

 

 

 

 

*

Refer to GSPS30kW Specifications for de-rating. 

**Refer to GSPS60kW Specifications for de-rating.

 

 

30kW: 

45kW: 

60kW: 

Содержание GBSPS10-3000

Страница 1: ...r manual is available on TDK Lambda website or can be ordered refer to User manual IA761 04 02_ For units equipped with MODBUS TCP interface option refer to MODBUS TCP User manual IA761 04 04_ For units equipped with EtherCAT interface option refer to EtherCAT User manual IA761 04 05_ Modbus is a registered trademark of Schneider Electric licensed to the Modbus Organization Inc EtherCAT is a regis...

Страница 2: ...This page intentionally left blank ...

Страница 3: ...GBSPS30 1530 GBSPS200 225 GSPS40 1125 GSPS300 153 GBSPS40 1125 GBSPS300 153 GSPS50 900 GSPS400 117 GBSPS50 900 GBSPS400 117 GSPS60 765 GSPS500 90 GBSPS60 765 GBSPS500 90 GSPS80 585 GSPS600 76 5 GBSPS80 585 GBSPS600 76 5 GSPS10 4500 GSPS100 600 GBSPS10 4500 GBSPS100 600 GSPS20 3000 GSPS150 408 GBSPS20 3000 GBSPS150 408 GSPS30 2040 GSPS200 300 GBSPS30 2040 GBSPS200 300 GSPS40 1500 GSPS300 204 GBSPS4...

Страница 4: ...ption 27 1 2 2 Control via Communication Ports 27 1 2 3 Analog Voltage Programming and Monitoring 27 1 2 4 Parallel Operation 28 1 2 5 Output Connections 28 1 2 6 Cooling and Mechanical Construction 28 1 3 Accessories 28 1 3 1 Accessories Provided With Power System 28 1 3 1 1 Misc Hardware 28 1 3 1 2 Bus Bars Screws Kits 28 1 3 2 Optional Accessories 29 1 3 2 1 Printed User Manual 29 1 3 2 2 Seria...

Страница 5: ...tant Voltage Check Blank Panel Master Power Supply 53 4 8 5 Constant Current Check Standard Master Power Supply 53 4 8 6 Constant Current Check Blank Panel Master Power Supply 53 4 9 Connecting the Load 55 4 9 1 Load Wiring 55 4 9 2 Current Carrying Capacity 55 4 9 3 Wire Termination 57 4 9 4 Inductive Loads 57 4 9 5 Making the Load Connections 57 4 9 6 Grounding Outputs 61 4 10 Local and Remote S...

Страница 6: ...This page intentionally left blank ...

Страница 7: ...cuitry Furthermore TDK Lambda does not warrant any damage occurring as a result of the buyer s circuitry or the buyer s supplied products No other warranty is expressed or implied Warranty Service This product must be returned to an authorized TDK Lambda service facility for repairs or other warranty service For products returned to TDK Lambda for warranty service the buyer shall prepay shipping c...

Страница 8: ...cturer is not responsible for any of the damages caused LIFTING AND CARRYING This equipment is not intended for lifting or carrying as it is a heavy equipment and can weight up to 200Kg 440 pounds Please use the castors on the equipment for all mobility NORMAL POSITION USE The normal position use of the equipment is on a level steady floor The castors must be on lock position with the adjustable f...

Страница 9: ...torage period we recommend to use within 2 years after receiving the product There is tendency that the leakage current of an aluminum electrolytic capacitor may increase when stored without usage for a long time This phenomenon can be minimized by applying voltage to the aluminum electrolytic capacitor to reduce the increased leakage current through the self recovery effect of the electrolyte For...

Страница 10: ...CB Assembly X 机箱 如适用 Enclosure if applicable X 配件 Accessories 此表依照SJ T11634 2014规定制定 This table is prepared in accordance with the provisions of SJ T 11364 2014 o 指明产品所有均质材料包含的有害物质要低于GB T26572限定的要求 Indicates that said hazardous substance contained in all of the homogeneous materials for this part is below the limit requirement of GB T 26572 x 指明产品所用的至少一种均质材料包含的有害物质高于GB T26572限定的要求 Indicates that s...

Страница 11: ...gnetic Compatibility Regulations 2016 and Restriction of the Use of Certain Hazardous Substances in Electrical Electronic Equipment regulation 2012 UKCA Declaration of Conformity in accordance with the preceding directives and standards has been made and is available on a file at our UK representative TDK Lambda UK Limited Kingsley Avenue Ilfracombe Devon EX34 8ES Declarations may be accessed via ...

Страница 12: ...d for connection to an external conductor for protection against electric shock in case of a fault Switch ON position Powers ON the power system Switch OFF position Powers OFF the power system IMPORTANT This is NOT the main disconnect device of the equipment Refer to DISCONNECT DEVICE section to learn about the main disconnect device Direct current DC Indicates that the value next to this symbol i...

Страница 13: ...OSAL The product contains components that require special disposal Make sure that the unit is properly disposed of at the end of its service life and in accordance with local regulations EQUIPMENT OPERATION AND OPERATING CONTROLS Identification and description of operating controls and their use in all operating modes are stated in the user manual Operating of the equipment is explained in detail ...

Страница 14: ...ore touching components CLASS I WARNING The unit is Class I product To minimize electrical shock hazard the unit must be reliably earthed and professionally installed Any interruption of the protective ground conductor or disconnection of the protective earth terminal will cause a potential shock hazard that might cause personal injury Energy Hazards Warning The main output of the unit is hazardou...

Страница 15: ...estinato al collegamento a un conduttore esterno per protezione contro scossa elettrica in caso di guasto Posizione ON dell interruttore Accende l alimentatore Posizione OFF dell interruttore Spegne l alimentatore IMPORTANTE Questo NON è il dispositivo di disattivazione principale dell apparecchiatura Vedere la sezione DISPOSITIVO DI DISATTIVAZIONE per informazioni sul dispositivo di disattivazion...

Страница 16: ...o in conformità con le istruzioni specificate nel manuale di sicurezza e di installazione per ridurre il rischio di pericolo SMALTIMENTO A FINE VITA Il prodotto contiene componenti che richiedono uno smaltimento speciale Accertarsi che l unità sia smaltita adeguatamente alla fine della sua vita utile e in conformità con le normative locali AZIONAMENTO DELL APPARECCHIATURA E COMANDI L identificazio...

Страница 17: ...re l elettricità scaricare i circuiti e rimuovere fonti esterne di tensione prima di toccare componenti AVVERTIMENTO DI CLASSE I L unità è un prodotto di Classe I Per ridurre al minimo il pericolo di scossa elettrica l unità deve essere collegata a terra in modo affidabile e installata in modo professionale Qualsiasi interruzione del conduttore di messa a terra di protezione o scollegamento del te...

Страница 18: ...externo para protección contra descargas eléctricas en caso de falla Posición de encendido Enciende la fuente de alimentación Posición de apagado Apaga la fuente de alimentación IMPORTANTE Este NO es el dispositivo de desconexión principal del equipo Consulte la sección DISPOSITIVO DE DESCONEXIÓN para familiarizarse con el dispositivo de desconexión principal Corriente continua CC Indica que el va...

Страница 19: ...e de acuerdo con las instrucciones especificadas en el manual de seguridad e instalación para reducir el riesgo de peligro ELIMINACIÓN AL FINAL DE LA VIDA ÚTIL El producto contiene componentes que requieren una eliminación especial Asegúrese de que la unidad se deseche correctamente al final de su vida útil y de acuerdo con las normas locales OPERACIÓN DEL EQUIPO Y CONTROLES DE OPERACIÓN La identi...

Страница 20: ...uentes de voltaje externas antes de tocar los componentes ADVERTENCIA DE CLASE I La unidad es un producto de Clase I Para minimizar el riesgo de descarga eléctrica la unidad debe estar conectada a tierra de manera confiable e instalada por un profesional Cualquier interrupción del conductor de tierra de protección o desconexión del terminal de tierra de protección causará un riesgo potencial de de...

Страница 21: ...ur externe pour la protection contre les chocs électriques en cas de défaillance Position de mise en marche ON Met sous tension l alimentation électrique Position d arrêt OFF Coupe l alimentation électrique IMPORTANT Ceci n est PAS le dispositif de déconnexion principal de l équipement Consultez la section DISPOSITIF DE DÉCONNEXION pour en savoir plus sur le dispositif principal de déconnexion Cou...

Страница 22: ... électrique doivent être conformes aux instructions spécifiées dans le manuel d installation et de sécurité afin de réduire les risques de danger ÉLIMINATION EN FIN DE VIE Le produit contient des composants nécessitant une élimination spéciale Veillez à ce qu il soit éliminé comme il se doit à la fin de sa durée de vie et conformément aux règlements locaux FONCTIONNEMENT DE L ÉQUIPEMENT ET COMMAND...

Страница 23: ...ts et retirer les sources de tension externes avant de toucher les composants AVERTISSEMENT CLASSE I L unité est un produit de Classe I Pour réduire les risques de choc électrique l unité nécessite une mise à la terre fiable et une installation professionnelle Toute interruption du conducteur de protection ou déconnexion de la borne de protection entraînera un risque potentiel de choc électrique p...

Страница 24: ... den Anschluss an einen externen Leiter zum Schutz gegen elektrischen Schlag im Falle eines Fehlers vorgesehen ist Schalterstellung EIN Schaltet die Spannungsversorgung EIN Schalterstellung AUS Schaltet die Spannungsversorgung aus WICHTIG Dies ist NICHT die Haupttrennvorrichtung des Geräts Lesen Sie den Abschnitt TRENNVORRICHTUNG um mehr über die Haupttrennvorrichtung zu erfahren Gleichstrom DC Ze...

Страница 25: ...s an die Stromversorgung darf nur gemäß den Anweisungen im Sicherheits und Installationshandbuch erfolgen um das Gefahrenrisiko zu verringern ENTSORGUNG AM LEBENSENDE Das Produkt enthält Komponenten die eine spezielle Entsorgung erfordern Stellen Sie sicher dass das Gerät am Ende seiner Lebensdauer ordnungsgemäß und in Übereinstimmung mit den örtlichen Vorschriften entsorgt wird GERÄTEBEDIENUNG UN...

Страница 26: ...den schalten Sie vor dem Berühren von Bauteilen immer die Stromversorgung ab entladen Sie Stromkreise und entfernen Sie externe Spannungsquellen KLASSE I WARNUNG Das Gerät ist ein Produkt der Klasse I Um die Gefahr eines elektrischen Schlages zu minimieren muss das Gerät zuverlässig geerdet und fachgerecht installiert werden Jede Unterbrechung des Schutzleiters oder Abtrennung der Schutzerdungskle...

Страница 27: ...ra choques elétricos em caso de uma falha Interrutor na posição LIGADO Liga a fonte de alimentação Interrutor na posição DESLIGADO Desliga a fonte de alimentação IMPORTANTE Este NÃO é o dispositivo principal que desconecta o equipamento Consulte a secção DISPOSITIVO DE DESCONEXÃO para saber mais acerca do dispositivo principal de desconexão Corrente contínua DC Indica que o valor junto deste símbo...

Страница 28: ...struções especificadas no manual do utilizador para reduzir os riscos de perigo ELIMINAÇÃO EM FIM DE VIDA O produto contém componentes que requerem condições especiais para eliminação Assegure se que a unidade é apropriadamente descartada no fim da sua vida útil e de acordo com os regulamentos locais OPERAÇÃO DO EQUIPAMENTO E CONTROLOS DE OPERAÇÃO A identificação e descrição dos controlos de opera...

Страница 29: ... alimentação De forma a evitar ferimentos danos desconecte sempre a alimentação e os circuitos de descarga e remova as fontes externas de tensão antes de tocar em qualquer componente AVISO CLASSE I A unidade é um produto de Classe I Para minimizar o perigo de choque elétrico a unidade deverá possuir uma ligação a terra eficaz instalada por um profissional Qualquer seccionamento ou desconexão do co...

Страница 30: ...3 PE with the ground wire firmly connected to an electrical ground safety ground at the power outlet For instruments designed to be hard wired to the supply mains the protective earth terminal must be connected to the safety electrical ground before another connection is made Any interruption of the protective ground conductor or disconnection of the protective earth terminal will cause a potential...

Страница 31: ...its is capable of providing the hazardous energy Therefore the output and connections must not be user accessible Customer s final equipment needs to provide adequate protection for service personnel against inadvertent contact with output wires WARNING There is an electric shock hazard when the power system output is adjusted at or above 60VDC Ensure it is not possible to touch simultaneously bot...

Страница 32: ...26 This page intentionally left blank ...

Страница 33: ...rs the protection levels Over Voltage protection Under Voltage protection and Foldback and preview the settings in the standard units The rear panel includes the necessary connectors to control and monitor the power system operation by remote analog signals or by the built in serial communications RS232 485 USB and LAN IEEE MODBUS TCP and EtherCAT are optional 1 2 2 Control via Communication Ports...

Страница 34: ...r system output reaches 60VDC or above system output bus bars are hazardous 1 2 6 Cooling and Mechanical Construction The Power System series is cooled by an each power supply unit internal fans At installation care must be taken to allow free airflow into the power system via the front panel and out of the power system via the rear panel 1 3 Accessories 1 3 1 Accessories Provided With Power Syste...

Страница 35: ...Nut M10 St St Type DIN439B 24 Pcs Flat washer M10 St St Type DIN125A 48 Pcs Spring washer M10 St St Type DIN127B 24 Pcs Bus bars Kit 4 Hex Screw M8x25 A4 70 Type DIN933 8 Pcs Hex Nut M8 St St Type DIN439B 8 Pcs Flat washer M8 St St Type DIN125A 16 Pcs Spring washer M8 St St Type DIN127A 8 Pcs 1 3 2 Optional Accessories 1 3 2 1 Printed User Manual For ordering printed User Manual the P N is G M 1 3...

Страница 36: ...ower system packing according to order 1 3 2 5 AC Cables AC Cables are not provided with the Power System For recommended AC input cables customer applied refer to Table 1 3 Recommended AC Input Cables for 30kW Table 1 4 Recommended AC Input Cables for 45kW or Table 1 5 Recommended AC Input Cables for 60kW AC Input Range AC Input Cable 190 240 Three phase 111A Min 4 X 35mm2 Three wires plus Safety...

Страница 37: ...ded AC Input Cables for 60kW WARNING In order to prevent inadvertent disconnection of the PE Ground wire if the input connection is made by a jacketed cord then the PE Ground wire must be minimum 10 mm longer than all of the other MAINS current carrying conductors connected to the equipment If input connection is made by separate wires then an appropriate conduit in accordance with local electrici...

Страница 38: ...igh resolution detent rotary Encoder adjusting the output voltage and navigating menu Button An auxiliary function to accept the voltage setting value in Preview mode 4 Voltage Display 4 digit 16 segment Voltage display Normally displays the output voltage In Preview mode the display indicates the setting of the output voltage In Menu navigation the display indicates the selected function 5 Operat...

Страница 39: ... Monitoring range selection Internal Resistance function Constant power limit function and Slew Rate control function Green LED lights when the Configuration menu is active If Configuration menu is active press the CONF button to exit to the main menu 13 PROT Button Indicator Activates the Protection menu The Protection menu provides OVP setting UVL setting UVP function control Foldback function c...

Страница 40: ...tput is enabled Red LED blinks in case of an alarm Refer to User Manual Alarms and Protective Functions section Table 2 1 Front Panel Controls NOTE If a menu is active and there is no key press within 15 seconds power system returns to the main display OFF or actual Voltage and Current display 2 3 Front Panel Display and Indicators Refer to Figure 2 2 and Table 2 2 for description of the Front Pan...

Страница 41: ... Address Indicator If power supply output is ON actual output power is displayed If power supply output is OFF power supply address is displayed The address is displayed while Communication menu is active regardless of the power supply output state 9 ext V ext I Indicators External Voltage External Current Analog Programming Indicators ext V is on if Analog Voltage Programming channel is active ex...

Страница 42: ...ators 2 4 First unit Blank Front Panel Refer to Figure 2 and Table 2 for description of the Blank Front Panel controls and Indicators Figure 2 3 Blank Front Panel Controls No Connection Description 1 Power Switch POWER ON OFF control 2 Manufacturer logo TDK Lambda logo 3 Power LED Power system ON OFF status LED Green LED lights when Power system is ON Power Switch ON 4 REM LED REMOTE status LED Gr...

Страница 43: ... several power supplies in a power system the first unit Serial In is connected to the computer and the remaining units are chained Remote Out to Remote In Connector type Molex 95540 2881 9 Serial Out connector RJ 45 type connector used for chaining power supplies to from a serial communication bus Connector type Molex 95540 2881 10 USB Connector USB interface connector type B Connector type SAMTE...

Страница 44: ... type low level is OK 4 CV CC Output for Constant Voltage Constant Current mode indication 5 LOC REM MON Output for indicating if the unit is in Local digital or Remote analog programming mode 6 LOC REM SELECT Input for selecting between Local digital or Remote analog programming of the output Voltage and Current 7 IPGM Input for Remote analog voltage resistance programming of the Output Current 8...

Страница 45: ...ulse width min 10usec 23 Trigger Out Trigger output positive edge pulse width min 100usec 24 NOT USED 25 I_MON Output for monitoring the power supply output Current 26 V_MON Output for monitoring the power supply output Voltage Table 2 3 J1 Connector Terminals and Functions CAUTION Topreventgroundloops andtomaintaintheisolationofthepowersystem whenprogrammingfrom J1 use an ungrounded programming s...

Страница 46: ...40 CHAPTER 3 OUTLINE 3 1 Power System Outline Power System Front View MODEL NAME OUTPUT RATING AND COMPANY LOGO ...

Страница 47: ...41 Power System Rear View NOTE A locking key 2233x locking that suitable for 2 side panels is attached to rear panel grid with tie wrap ...

Страница 48: ...42 Power System Internal Rear Panel Connections TABLE 1 BUSBAR VOLTAGE THICKNESS T L 10V 20V 10mm 77mm 30V 40V 5mm 67mm 50V 100V 5mm 67mm 150V 600V 3 5mm 67mm ...

Страница 49: ...43 Power System Optional Earth Ground Connection ...

Страница 50: ...44 Power System Side View and Output Bus bars Dimensions All Dimensions are in mm ...

Страница 51: ...ion Reference 1 Inspection Initial physical inspection of the power system Section 4 3 2 Packing Box Packing Box Unpack Section 4 4 3 Installation Installing the power system Ensuring adequate ventilation Section 4 5 4 AC mains AC mains requirements Connecting the Power System to the AC mains Section 4 7 5 Test Turn on checkout procedure Section 4 8 6 Load connection Wire size selection Local Remo...

Страница 52: ...acking box as instructed in Figure 4 1 by remove the straps from the packaging box 2 Unscrew fixing screw to disassemble the top box cover 3 Gently remove the accessories box Figure 4 1 GSPS Unpack Disassemble Top Cover Accessories Box 4 Unscrew screws to disassemble the reinforcing beams as shown in Figure 4 2 and Figure 4 3 Figure 4 2 GSPS Unpack Disassemble the reinforcing beams ...

Страница 53: ...ystem is fan cooled The air intake is at the front panel and the exhaust is at the rear panel Upon installation allow cooling air to reach the front panel ventilation inlets CAUTION Allow minimum 10cm 4 of unrestricted air space at the front and the rear of the unit The power system should be used in an area where the ambient temperature does not exceed 50 C refer to product Spec for operating con...

Страница 54: ...t Connections 1 Unscrew fixing screw to remove the rear panel of the cabinet as shown in Figure 4 5 Figure 4 5 Rear Panel Disassembly 2 Unscrew the fixing screw to remove the rear panel slots of the cabinet as shown in Figure 4 6 Figure 4 6 Rear Panel Output Slots Disassembly ...

Страница 55: ... 1 X 40A for 45kW 3 Phase 480Vac 2x 80A for 60kW 3 Phase 480Vac CAUTION The Power System shall be electrically connected to a supply by either means of permanent connection which can be detached only by the use of a tools or by connector meeting the requirements of IEC 60309 Connection of this Power System to an AC mains should be made by an electrician or other qualified personnel in accordance w...

Страница 56: ...TION The Power System ON OFF switch is not the main disconnect device and does not completely disconnect all the circuits from the AC mains The Power System has circuit breakers are disconnecting all supply lines simultaneously It is prohibited to position the equipment so that it is difficult to operate the disconnecting device WARNING There is a potential shock hazard if the Power System s rear ...

Страница 57: ...nector UKH50 95 240 screws 4 Input Connection for 30KW 3P208 480 45KW 3P480 60KW 3P480 System Models tightening torque 65 70 lbf in 7 3 8 5Nm 5 Input Connection for 45KW 3P208 System Models tightening torque 165 177 lbf in 18 5 20Nm 6 Input Connection for 60KW 3P208 System Models tightening torque 250 265 lbf in 28 3 30Nm 7 Tighten the cable clamp s screw nuts Figure 4 9 AC Wire Inserted Through a...

Страница 58: ...ed and properly assembled 3 Connect the unit to an AC mains as described in Section 4 7 4 Connect a DVM with appropriate cables for the rated voltage to the output terminals 5 Turn the front panel Power switch to On 6 Ensure that the power supply is configured to the default setting refer to User Manual IA761 04 02_ Parameter Setting Memory section 7 When power system is turned ON and all LCD Disp...

Страница 59: ... shunt across the output terminals 3 Ensure that the shunt and the wires current ratings are higher than the power system rating 4 Connect a DVM to the shunt 5 Turn the front panel Power switch to On position 6 Turn on the output by pressing the OUT button so the OUT LED illuminates 7 Observe the power system Current display and rotate the Current encoder 8 Ensure that the output current varies wh...

Страница 60: ...arriage Return character ASCII 13 0x0D after each command 8 Ensure that the output current readback varies while sending CURR YY command The control range is from zero to the maximum rated output for the power system model Send MEAS CURR command to read power system output current YY Programmed current value 9 Compare the DVM reading with the readback current to verify the accuracy of the digital ...

Страница 61: ...ld have enough current carrying capacity to prevent overheat while carrying the power system load current at the rated load or the current that would flow in the event the load wires were shorted whichever is greater Wire size should be selected to enable voltage drop per lead to be less than 1V at the rated current Although units will compensate higher voltage drop in each load wire refer to the ...

Страница 62: ...wires per terminal 400 kcmil 105 C minimum 400 kcmil Panduit LCC400 12 6 two hole long barrel Lug Or equivalent 2000A 3000A 150 X 2 In Parallel per bus bar hole For 30kW 10V For 45kW 20V For 60kW 20V 30V 12 wires per terminal 300 kcmil 105 C minimum 300 kcmil Panduit LCC300 12 6 two hole long barrel Lug Or equivalent 3000A 4500A 240 X 2 In Parallel per bus bar hole For 60kW 10V 12 wires per termin...

Страница 63: ...t voltage of the power system 4 9 5 Making the Load Connections WARNING Hazardous voltages exist at power outputs with output greater or equal to 60Vdc To protect personnel against accidental contact with the hazardous voltages ensure that the load and its connections have no accessible live parts Ensure that the load wiring insulation rating is greater than or equal to the maximum output voltage ...

Страница 64: ... shown in Figure 4 10 and Figure 4 11 Figure 4 10 Output Wires Assembly Figure 4 11 10V 100V Wires Assembly NOTE All bus bars must be tightened by screw and nut even if load wire lug is not connected 2 Assembly the output protection slots as shown in Figure 4 12 ...

Страница 65: ...ase of operation except if separately permitted in other sections in this manual WARNING There is a potential shock hazard when using a power system with an output voltage greater than 60VDC Do not turn ON power system without output protection slots assembled Ensure that the output protection slots are mounted and properly assembled WARNING There is a potential shock hazard if the Power System s ...

Страница 66: ...utput to bus bars are not loss general tightening Torque is 45 48 lbf inch refer to Figure 4 13 Figure 4 13 power supply output screw connection 2 Fix the wires to the Bus bars as shown in Figure 4 14 and Figure 4 1515 Figure 4 14 Fixing Bus Bars Cover to the Rear Panel Figure 4 15 150V 600V Wires Assembly ...

Страница 67: ...ractures under high pressure The result is an increased contact resistance and an excessive temperature rise In addition corrosion caused by pickling or fluxes has been observed on soldered conductor ends Notch fractures at the transition point from the rigid to the flexible conductor area are also possible WARNING There is a potential shock hazard if the Power System s rear cover are not assemble...

Страница 68: ...ge of the power system Ensure that the connections at the load end are shielded to prevent accidental contact with the hazardous voltages 4 10 2 Local Sensing The power system is shipped with unconnected J8 sense connector In this configuration the unit is sensing the output voltage at the output terminals Refer to Table 4 4 for J8 terminals assignment This method does not compensate for voltage d...

Страница 69: ...rop is subtracted from the total voltage available at the output Follow the instructions below to configure the power system for remote sensing 1 Ensure that the Power system AC connection is Off 2 Connect the negative sense lead to terminal J8 S and the positive sense lead to terminal J8 S 3 Set voltage sensing setting to remote sense via front panel or communication 4 Turn On the power system NO...

Страница 70: ... of wire insulation Insert the wire into the terminal while pressing on the white pusher After full insertion release the white pusher for wire locking inside the terminal 4 11 Repackaging for Shipment To ensure safe transportation of the instrument contact the TDK Lambda sales or service facility near you for Return Authorization and shipping information Please attach a tag to the power system de...

Страница 71: ...rom rated output current following 30 minutes warm up 150V 600V models 70PPM O C from rated output current following 30 minutes warm up 4 Temperature stability 0 01 of rated Iout over 8hrs interval following 30 minutes warm up Constant line load temperature 5 Warm up drift 10V 100V models Less than 0 25 of rated output current over 30 minutes following power on 150V 600V models Less than 0 15 of r...

Страница 72: ...apply in analog programming Preset by front panel or communication port 6 Over temperature protection Shuts down the output Auto recovery by autostart mode 7 Output under voltage protection UVP Prevents adjustment of Vout below limit P S output turns Off during under voltage condition Reset by AC input recycle in autostart mode by Power Switch by OUTPUT button by rear panel or by communication FRO...

Страница 73: ...9 01 01 NOTES 1 Minimum voltage is guaranteed to maximum 0 1 of rated output voltage 2 Minimum current is guaranteed to maximum 0 2 of rated output current 3 Model 10V Max ambient temperature is 40 C 4 For cases where conformance to various safety standards IEC etc is required to be described as 190 240Vac 50 60Hz for 3 Phase 200V models and 380 480Vac 50 60Hz for 3 Phase 480V models 5 3 Phase 200...

Страница 74: ...minutes warm up 150V 600V models 70PPM O C from rated output current following 30 minutes warm up 4 Temperature stability 0 01 of rated Iout over 8hrs interval following 30 minutes warm up Constant line load temperature 5 Warm up drift 20V 100V models Less than 0 25 of rated output current over 30 minutes following power on 150V 600V models Less than 0 15 of rated output current over 30 minutes fo...

Страница 75: ...t panel or communication port 6 Over temperature protection Shuts down the output Auto recovery by autostart mode 7 Output under voltage protection UVP Prevents adjustment of Vout below limit P S output turns Off during under voltage condition Reset by AC input recycle in autostart mode by Power Switch by OUTPUT button by rear panel or by communication FRONT PANEL 1 Control functions Multiple opti...

Страница 76: ...trial environment Annex H table H 3 and H 4 FCC Part 15 A VCCI A REVISION IA979 01 02 NOTES 1 Minimum voltage is guaranteed to maximum 0 1 of rated output voltage 2 Minimum current is guaranteed to maximum 0 2 of rated output current 3 For cases where conformance to various safety standards IEC etc is required to be described as 190 240Vac 50 60Hz for 3 Phase 200V models and 380 480Vac 50 60Hz for...

Страница 77: ...urrent following 30 minutes warm up 150V 600V models 70PPM O C from rated output current following 30 minutes warm up 4 Temperature stability 0 01 of rated Iout over 8hrs interval following 30 minutes warm up Constant line load temperature 5 Warm up drift 10V 100V models Less than 0 25 of rated output current over 30 minutes following power on 150V 600V models Less than 0 15 of rated output curren...

Страница 78: ...ming Preset by front panel or communication port 6 Over temperature protection Shuts down the output Auto recovery by autostart mode 7 Output under voltage protection UVP Prevents adjustment of Vout below limit P S output turns Off during under voltage condition Reset by AC input recycle in autostart mode by Power Switch by OUTPUT button by rear panel or by communication FRONT PANEL 1 Control func...

Страница 79: ... Minimum voltage is guaranteed to maximum 0 1 of rated output voltage 2 Minimum current is guaranteed to maximum 0 2 of rated output current 3 Model 10V Max ambient temperature is 30 C Output current derate 30A 1 C 4 For cases where conformance to various safety standards IEC etc is required to be described as 190 240Vac 50 60Hz for 3 Phase 200V models and 380 480Vac 50 60Hz for 3 Phase 480V model...

Отзывы: