- 25 -
TDK-Lambda
EZA2500W series
Quick Manual / Practical (II)
Apply the specified voltage on the grid side and battery side terminals of EZA.
Start the personal computer on which CNVCommCC is installed, and confirm that
it can communicate with EZA according to the operating instructions distributed with
CNVCommCC.
Set parameters via RS485 while referring to "4) Operation of Automatic battery CV
mode," , "
②
Set parameters of EZA" on pages 14 and 15 of this manual.
①
Short the pin 7 (RUN) of the external signal connector CN to SG (signal ground,
e.g. pin 8).
②
EZA starts the main circuit from the Waiting and starts charging or discharging.
③
When pin 7 is opened, EZA stops the main circuit and enters Waiting.
⑤
Start EZA.
④
Check that communication is possible with RS-485.
⑤
Set parameters of EZA.
③
Restart the control board.
The control board reads the values of DIP switch
and rotary switch at restart.
The control board is also restarted by applying the
specified voltage to either the battery or grid side.
CN pin 9 is not used in this case. EZA is ignored even if it is shorting to SG