- 20 -
TDK-Lambda
EZA2500W series
Quick Manual / Practical (II)
8) Operation of Manual grid CV with battery CC mode using external signal
connector CN
Set the DIP switch 1-3 as shown in the figure below in p18 "
②
Set the DIP switch to operate
with Manual CV mode via external signal connector CN."
①
Set the terminal voltage on both the grid side and the battery side of the EZA to 0 V.
As shown in the photo below, set the DIP switch1 and 3(First and Third from Left) on
the back to ON(Lower).
* In the photo, the RS-485 address is set to “0” and the communication speed is set
to 19.2kbps.
* If the address on RS-485 is 0, make the rotary switch as shown in the photo below.
②
Perform the operations after p19 “
③
Restart the control board.” described above.
When the pin 9 of the external connector CN is shorted to SG, charging
operation will be performed in Manual CV mode.
※
The factory setting is the above setting.