- 18 -
TDK-Lambda
EZA2500W series
Quick Manual / Practical (II)
7) Operation of Manual CV mode using the external signal connector CN
This section explains how to start and stop EZA using the external signal connector CN.
Prepare the battery, inverter, personal computer, etc. and connect them to EZA with
reference to p4 of this manual, Quick Manual Basics, Practice I, etc.
When using the external signal connector CN, it is necessary to set the EZA
operation mode with the DIP switch in advance.
In Manual CV mode using CN, set the address on RS-485 to “0” and the
communication speed to 19.2kbps.
Set the terminal voltage on both the grid side and the battery side of the
EZA to 0 V. As shown in the photo below, set the only DIP switch 3(Third
from Left) on the back to ON(Lower).
Set the rotary switch on the front panel as shown in the photo below.
②
Set the DIP switch to operate with Manual CV mode via external
signal connector CN.
①
Connect peripheral devices such as battery to EZA.
For details, see p10 of the instruction manual
and p6 of the communication manual.
※
The factory setting is the above setting.