- 5 -
TDK-Lambda
EZA2500 series
Quick Manual / Basic
2) Explain of Terminal Connection and Panels
EZA 2500 terminals and Panels are shown in the figure below.
①
LED of Indicator
The LEDs (3 pcs) indicates operating status of EZA2500.
②
RESET :Tactile Switch
The tactile switch functions as alarm clear button when the alarm is activated due to abnormal
occurrence. When this switch is pushed, a command to clear the alarm is sent to the converter
while in alarm state (ALM LED ON).
This switch does not function when converter is not alarm
state.
③
ADDRESS : Rotary Switch
The rotary switch functions as the RS-485 address setting for this converter. It is used to set
the lowest digits (last 4 bits) and DIP SW is used to set the highest digits.
←
Light up at Discharge operating (Output from Low
Voltage to High voltage)
←
Light up at Charge operating (Output from High
voltage to Low voltage
)
←
Light up at Heavy Alarm
Resetting the control IC (CPU) on the control board can not be done
with this switch. It is necessary to set the applied voltage of both the
high voltage side and the low voltage side to 0 V and start the control
board again.
When controlling 14 or less EZAs with one interface of RS485, it is
recommended that DIP switches 6 to 8 are left unchanged from the
factory and specified by this switch.