- 16 -
TDK-Lambda
EZA2500 series
Quick Manual / Basic
①
②
③
④
⑤
①
We will set up the parameters in the Manual CV mode.
Notes) The following settings differ depending on the battery used. Make sure to
check with the battery manufacturer.
●Setting the battery charge voltage and protection
①
Click the "Other Setting" tab in a state where it can communicate with EZA.
And
click "READ ALL" to read the current parameters of EZA.
②
Write the following parameters to the area surrounded by the red line in the above
figure.
Target Battery Voltage → "50" (V)
Limit of Battery Voltage for Discharging
→
"40" (V)
③
Turn on the radio buttons of "Battery Over Charging Protection" and "Battery Under
Discharging Protection", respectively, surrounded by the red line in the above figure.
④
.Click the ”WRITE”
⑤
Click the ”READ” to display the current value and confirm that the value has been
written.
※
The EZA controls the charging current to be 0A at 50V to prevent overcharging of
the battery, and controls the discharging current to be 0A at 40V to prevent the over
discharging.
⑤
Set parameters of EZA.